![Fulham Hotspot FHSCP-UNV Series Installation And Operation Instructions Manual Download Page 8](http://html1.mh-extra.com/html/fulham/hotspot-fhscp-unv-series/hotspot-fhscp-unv-series_installation-and-operation-instructions-manual_2345159008.webp)
Installation Instructions
FHSCP-UNV Series Compatibility and Suitability of Use Guidelines
Addendum (Rev.11152019)
The purpose of this addendum is to sufficiently identify electrical compatibility and predictable emergency light output of the LED
luminaire when used with the F
ulham FHSCP-UNV
Series LED emergency drivers. Verification of these operating traits does
not constitute a code-compliant, as-installed emergency egress system. It is still the responsibility of the Designer/ Specifier to
assure appropriate light levels are achieved during emergency operation of the luminaire in accordance with Federal, state and
local municipal codes regarding path of egress illumination.
A)
Determining Electrical Compatibility
•
Verify Class 2 compliant driver per driver manufacture specifications.
•
Verify that the Emergency Driver (
FHSCP-UNV
Series) selected does not exceed the power delivered to the LED
array (voltage and current) of the normal driver.
B)
Calculating Lumen Output During Emergency Operation
•
Assess luminaire/fixture data.
•
DESIGNLIGHTS CONSORTIUM
• Log onto the DesignLights Consortium website (www.designlights.org).
• Click on “search the DLC Qualified Product List” button on the DLC homepage.
• In the “search by keyword” text window enter: luminaire manufacturer name and part number.
• Click on “Search” tab to open the “Qualified Products List.”
• Determine per “RATED DATA” efficacy shown in lumens per watt - (lm/w).
• Multiply lumens per watt by
FHSCP-UNV
rated output (example: lm/w x 5 watts). Refer to table
“
FHSCP-UNV
MODEL SPECIFICATION CHART” below for the wattage of the specific
FHSCP-
UNV
model to be used in the luminaire. (lm/w) x (
FHSCP-UNV
Watts) = Minimum emergency
lumens of fixture.
• Determine per “RATED DATA” the “wattage of the luminaire.
FHSCP-UNV MODEL SPECIFICATION CHART
MODEL #
OUTPUT POWER (CONSTANT)
FHSCP-UNV-5WL
5.0 WATTS
FHSCP-UNV-7.8WL
7.8 WATTS
FHSCP-UNV-10.7WL
10.7 WATTS
FHSCP-UNV-13.7WL
13.7 WATTS
FHSCP-UNV-17WL
17.0 WATTS
C)
Determining Adequacy of Means-of-Egress Lighting Levels
•
Follow industry standards by utilizing available .ies files and lighting design software for yourdedicated
emergency luminaires, with the above calculated emergency lumens, and validate your as-installed plans in
accordance with the applicable life safety codes governing your project.
While the
FHSCP-UNV
series has been found compliant with the requirements of UL Standard 924, it is ultimately
the responsibility of the Designer/Specifier to assure the as-installed system delivers code- compliant path of
egress illumination in accordance with Federal, State or local municipal requirements.
NiCd
.
2020 REV D2
Fulham extends a limited warranty only to the original purchaser or to the first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please reference the Fulham Product Catalog (www.fulham.com).
Due to a program of continuous improvement, Fulham reserves the right to make modifications or variations in design or construction to the
equipment described. © Fulham Company Limited, All Rights Reserved.
Page 8 of 8