Page 2 of 5
20
-
Rev B
17 719
Fulham Co. Inc.: 12705 South Van Ness Ave., Hawthorne, CA 90250 Tel.: 1-323-779-2980 Fax.: 1-323-754-9060.
Specifications subject to change without notice.
[email protected] www.fulham.com
1. Use flat head screwdriver to loosen the screws on the lens.
2. Remove lens, from sign, set aside.
3. Remove EXIT stencil from housing, set aside.
Drill a 3/4"hole through the desired mounting knock out located on the frame of the sign. For
ceiling mount, knock out will be located on the top of the housing. For wall mount, knock out
will be located on the side of the housing.
4. Using provided hardware, thread nut onto pipe nipple. Slide pipe nipple through canopy
center hole.
5. Remove backing from self adhesive junction box gasket and adhere to back of mounting
canopy.
Remove backing from self adhesive pipe thread gasket and adhere to front of mounting
canopy.
6. Place screws (provided) in holes on the canopy.
7. Route Exit input wires through knockout in EXIT frame, pipe nut and metal mounting plate.
8. Make wiring connection. For 120V, use black and white wires and for 277V, use red and
white wires.
WARNING: Properly insulate the unused lead with a wire nut (provided) or other approved
means.
9. Push wire connections into the J-Box. Secure mounting plate to junction box (hardware not
included).
10. Secure the canopy to the steel mounting plate with screws installed in step 7.
11. Place pipe nipple through the mounting hole of the housing until the gasket is touching the
housing frame.
Thread a second nut onto the pipe nipple on the inside of the housing to lock the canopy into
place. Once canopy is locked into position there will not be any side-to-side movement of the
canopy.
12. Remove proper chevron(s) as required. When removing chevrons it may be helpful to
remove the color diffuser panel to allow easier access to the chevrons. If removing color
diffuser panel it is important to remember to reinstall the diffuser panel once chevron(s) have
been removed.
13. Connect battery to lamp board (battery back up models only).
14. Secure face plate(s) to the housing.
15. Secure lens to face plate and securely to torque screws.
16. Apply continuous AC power and press ''Test" button to check operetion.
GENERAL INSTALLATION GUIDELINES
FOR WET LOCATION EXIT FIXTURE
(FHEX26/FHEC34)