SPECIFICATIONS
Page 7 of 7
2017-736-7 Rev A
MECHANICAL DATA
100%-1%,0%
LiFePO4
E313578
FHSAC1-UNV-40C
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com.
Specifications subject to change without notice.
Important Safety Instructions
When using electrical equipment and this lighting device basic safety precaution should
be followed at all times including but not limited to the following:
·CAUTION
: Do not let power supply cords touch hot surfaces.
·CAUTION
: Do not mount near gas or electric heaters.
·
IMPORTANT:
An un-switched AC power source of 120VAC to 277VAC is required for the
·This device is designed for use in fixtures listed for
dry and damp locations
.
PLEASE READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS FOR YOUR OWN SAFETY
·CAUTION:
Make sure all electrical connections conform to the National Electrical Code and all applicable local
regulations.
·CAUTION:
Battery is rechargeable LiFePO4 type and must be recycled or disposed of properly.
·CAUTION:
Do not use this emergency driver with accessory equipment other than recommended by
manufacturer; failure to follow this may cause an unsafe condition. Servicing should only be performed
by qualified service personnel.
·CAUTION:
Do not use this emergency driver for other than intended use.
·CAUTION:
Equipment should be mounted in locations and at heights where it will not readily be subjected
to tampering by unauthorized personnel.
yellow/black and white leads.
·
IMPORTANT: A switched or un-switched AC power source of 120VAC to 277VAC is acceptable
for the black lead only.
TESTING SYSTEM:
The emergency battery requires a minimum charge time of one (1) hour before testing the circuit.
A minimum of twelve (12) hours is required for a full charge.
ASSEMBLY and FIELD INSTALLATION WIRING: WARNING:
AC power must be off before proceeding with assembly,
installation or servicing of emergency driver. Additionally ensure that the battery is disconnected (Battery Switch set to OFF).
RATED EMERGENCY OPERATION:
Ninety (90) minutes for the 10W load or one hundred eighty (180) minutes for the 5W
load. The 10W or 5W option is determined by the position of Dip Switch 1 (Emergency Power Selection Switch).
BATTERY DISABLE PROCEDURE:
Unit must be powered within 6 months. To ship a fixture with the battery
connected without draining the battery the procedure is:
1. Driver is installed in a fixture.
2. Battery is switched to the “ON” position.
3. Fixture is powered and tested.
4. Fixture is un-powered, the unit enters EM mode.
5. Battery is switched to “OFF”, wait about 3 seconds then switch the battery back to the “ON” position.
Note:
Not recommended for installations where unit will be without power for more than 6 months.