European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                            www.e-2-s.com              Fax: +44 (0)208 740 4200 
Document No. D210-00-001-IS 

Issue 4        28-03-17                         Sheet 1 of 8

 

                                                           

INSTRUCTION MANUAL (ATEX / IECEx) 

BExS110D and BExS110D-R Sounder

 

For use in Flammable Gas and Dust Atmospheres

 

 

 

 

 

 

 

 

1) Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGIZED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD 

 COVER BOLTS CLASS A4-80 

 USE HEAT RESISTING CABLES AND CABLE 

GLANDS (RATED 110°C) AT AMB. 
TEMPERATURES OVER 40°C 

 

2)  Rating & Marking Information 

 

All units have a rating label, which carries the following 
important information: - 

 

Model No.:

  

BExS110D or BExS110D-R 

 

Input Voltage:

     DC Units    12V or 24V or 48V 

              AC Units    115V or 230V 

 

BExS110D or BExS110D-R Codes:  

Ex d IIC T4 Gb Ta. -50°C to +55°C  
Ex d IIB T4 Gb Ta. -50°C to +70°C 
Ex tb IIIC T100°C Db Ta. -50°C to +55°C 
Ex tb IIIC T115°C Db Ta. -50°C to +70°C  

 

Certificate No.

    KEMA 99ATEX6312X 

  IECEx 

KEM 

10.0003X 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

The units can be installed in locations with the following 
conditions: 

 

Area Classification Gas: 

Zone 1 

Explosive gas air mixture likely to occur in 
normal operation. 

Zone 2 

Explosive gas atmosphere not likely to 
occur in normal operation but may be 
present for short periods. 

 

Gas Groupings: 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene (up to 55°C 
ambient) 

 

Temperature Classification: 

T1 450ºC 

 

T2 300ºC 
T3 200ºC 
T4 135ºC 

 

Area Classification Dust: 

Zone 21 

Explosive dust air mixture likely to occur in 
normal operation. 

Zone 22 

Explosive dust air mixture not likely to 
occur in normal operation, and if it does, it 
will only exist for a short time. 

 

Dust Groupings: 

Group IIIA 

Combustible Dusts 

Group IIIB 

Non-Conductive Dust 

Group IIIC 

Conductive Dust 

 

Maximum Surface Temperature for Dust Applications: 

100ºC at +55 ºC ambient 

115 ºC at +70 ºC ambient 

 

IP Rating:  

IP66/67 to EN/IEC60529 and IP6X to 
EN/IEC60079-0, EN/IEC60079-31 

 

Equipment Category:

 

2G / 2D 

 

Equipment Protection Level:

 

Gb / Db 

 

Ambient Temperature Range:

 

-50°C to +55°C Gas Groups IIA, IIB and IIC 

-50°C to +70°C Gas Groups IIA and IIB 

-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

0518 

II  2G 
II  2D 

Epsilon x 
Equipment Group and 
Category: 

CE Marking 
Notified Body No. 

BExS110D 

BExS110D-R 

Summary of Contents for BExS110D-R

Page 1: ...99ATEX6312X IECEx KEM 10 0003X The units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely to occur in normal operation Zone 2 Explosive gas atmosphere not likely to occur in normal operation but may be present for short periods Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen and Acetylene up to 55 C am...

Page 2: ...d Mounting The location of the sounder should be made with due regard to the area over which the warning signal must be visible They should only be fixed to services that can carry the weight of the unit The BEx sounder should be secured to any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by loosening...

Page 3: ...o NPT M20 to M25 It is important to note that stopping plugs cannot be fitted onto adapters only directly onto the M20 entries Any other adapters used must be suitably rated and ATEX IECEx certified adapters 10 Earthing Both AC and DC sounder units must be connected to an earth The units are provided with internal and external earth terminals which are both located on the terminal chamber section ...

Page 4: ... Operation Simply connect the supply voltage to the L and N supply terminals see fig 4 12 2 2 AC Units Second Third Stage Tone Selection To select the second and third stage tones on the BExS110 AC sounder Stage two S2 Operation Power L and N link the Common C and S2 terminal Dip switch alters stage 2 tone Stage three S3 Operation Power L and N link the Common C and S3 terminals Dip switch alters ...

Page 5: ...e the facility to use either ve or ve switching to change the tone to the second and third stages Negative switching is the default setting For ve switching connect the two headers on the pcb to the left hand marked ve and centre pins For ve switching connect the headers to the right hand marked ve and the centre pins Refer to Fig 7 Fig 7 Stage Switching Polarity 13 4 Line Monitoring On BExS110D D...

Page 6: ...e set by adjusting the volume control potentiometer see Fig 9 For maximum output set the potentiometer fully clockwise BExS110D AC BExS110D DC Fig 9 Location of Volume Control Potentiometer 15 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 1...

Page 7: ... 1 0 Tone 31 Tone 1 12 Alternating 800 1000Hz at 0 875Hz 1 1 0 1 0 Tone 4 Tone 5 13 Intermittent 2400Hz at 1Hz 0 0 1 1 0 Tone 15 Tone 5 14 Intermittent 800Hz 0 25s on 1s off 1 0 1 1 0 Tone 4 Tone 5 15 Continuous at 800Hz 0 1 1 1 0 Tone 2 Tone 5 16 Intermittent 660Hz 150mS on 150mS off 1 1 1 1 0 Tone 18 Tone 5 17 Alternating 544Hz 100mS 440Hz 400mS 0 0 0 0 1 Tone 2 Tone 27 18 Intermittent 660Hz 1 8...

Page 8: ...8 0 106 7 103 4 102 1 104 2 106 0 107 2 106 8 103 4 101 7 3 500 1200Hz 0 3Hz 0 5 Sec Slow Whoop 106 8 108 9 108 8 107 0 107 6 104 6 106 1 107 6 109 6 109 1 106 9 105 6 9 1200 500Hz 1Hz DIN PFEER P T A P 105 6 106 8 107 4 106 4 106 2 103 6 104 1 105 3 106 8 106 7 105 0 103 3 15 800Hz Continuous 100 1 103 3 105 6 107 6 103 0 100 3 10 2 102 9 105 2 106 8 102 4 99 6 16 660Hz 150mS ON 150mS OFF Intermi...

Reviews: