2 .5
Installing the hydraulic unit
2 .5 .1
Installation precautions
•
Choose the location of the appliance after discussion
with the client.
•
The room in which the appliance operates must
comply with the prevailing regulations.
•
To facilitate maintenance and to allow access to the
various components, we recommend that you provide
sufficient space all around the hydraulic unit.
350 mm
mini
1000 mm
300 mm
mini
•
According to standard EN 378-1 (safety
requirements and HP environment), the room
where the HP is installed shall have a volume
higher than: Unit refrigerant load in kg / 0.44kg/m
3
If not, it must be ensured that:
- whether the room is mechanically ventilated,
- or room door is remain opened when the installer
works on the HP.
•
Be careful not to bring inflammable gas near to the
heat pump during its installation, in particular when
it requires brazing. The appliances are not fireproof
and should therefore not be installed in a potentially
explosive atmosphere.
- To avoid condensation inside the condenser, remove
the refrigerant circuit caps
only when completing the
refrigerant connections
- If the refrigerant connection only occurs at the end of
the installation, be sure that the refrigerant circuit caps*
remain in place and tight throughout the installation
duration.
* (hydraulic unit side and outdoor unit side).
- After every intervention on the refrigeration circuit and
before final connection, take care to replace the plugs
in order to avoid any pollution from the refrigeration
circuit (The sealing with tape is prohibited).
(S)
1
2
118 mm
(S)
538 mm
mini
418 mm
mini
300 mm
mini
350 mm
mini
188 mm
figure 15 - Mounting bracket
2 .5 .2
Positioning the hydraulic unit
- Fix the support solidly (4 screws and plugs) to a flat,
hard-wearing wall (not a light partition) ensuring that it
is correctly levelled.
- Hook the appliance onto its support.
Installation and operation manual "1764 - EN"
Air to Water Heat Pump, split system
- 18 -
Summary of Contents for WOYA060LFCA
Page 23: ... Installation and operation manual 1764 EN 23 Air to Water Heat Pump split system ...
Page 29: ... Installation and operation manual 1764 EN 29 Air to Water Heat Pump split system ...
Page 33: ...Installation and operation manual 1764 EN 33 Air to Water Heat Pump split system ...
Page 35: ... Installation and operation manual 1764 EN 35 Air to Water Heat Pump split system ...
Page 71: ...Installation and operation manual 1764 EN 71 Air to Water Heat Pump split system ...
Page 73: ... Installation and operation manual 1764 EN 73 Air to Water Heat Pump split system ...
Page 79: ... Installation and operation manual 1764 EN 79 Air to Water Heat Pump split system ...
Page 86: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 86 ...
Page 87: ...Installation and operation manual 1764 EN 87 Air to Water Heat Pump split system ...
Page 88: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 88 ...
Page 89: ...Installation and operation manual 1764 EN 89 Air to Water Heat Pump split system ...
Page 90: ...Installation and operation manual 1764 EN Air to Water Heat Pump split system 90 ...
Page 91: ... Installation and operation manual 1764 EN 91 Air to Water Heat Pump split system ...