En-3

ELECTRICAL WIRING

General-purpose building 

control computer

(MODBUS device)

TRANSMISSION CABLE

OUTDOOR UNIT

MASTER OR SLAVE

OUTDOOR UNIT

INDOOR UNIT

Power supply 

cable

MODBUS cable

Transmission cable 

to VRF network 

MODBUS CONVERTOR

SWITCH 

(Disconnect 

switch)

FUSE (2A)

1Ø 50/60 Hz

208-240 V

MODBUS 

CABLE

POWER

SUPPLY 

CABLE

Note :

• Do not bind the power supply cable and transmission cable to avoid an 

erroneous operation.

• Use shield cable for transmission cable.  

The shield metal should be earthed (grounded). 

• Do not forget to earth (ground) the MODBUS Convertor. 
• Install the disconnect switch to the easily accessible location.
• Install the fuse (2A) to the L (L1) line of power supply cable.
• Before connecting cables, turn off the power of the VRF units connected 

to the convertor.

6.2.  Unit wiring

6.2.1.  Power supply cable

Keep the ground cable longer than the other cables.

Power supply cable

25m

m

(1in

)

Earth (Ground)

cable

15m

m

(9/1

6 in

)

(1)  Use ring terminals with insulating sleeves as shown in the figure below 

to connect to the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate 

tool so that the cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so 

that there is no stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. 

Do not use a screwdriver that is too small, otherwise, the screw heads 

may be damaged and prevent the screws from being properly tight-

ened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws 

may break.

(6)  See the table for the terminal screw tightening torques.
(7)  Do not fix 2 or more power supply cables with 1 screw.

6.1.  Wiring method

PROPER SYSTEM DIAGRAM

MODBUS Network

Indoor unit

VRF network system

Outdoor unit

Lighting facilities

Security system

Automatic fire

alarm interface 

Ventilation system 

General-purpose  

MODBUS master unit

(MODBUS device)

MODBUS

Convertor

(UTY-VMGX)

VRF

Outdoor unit

Indoor unit

Transmission cable

(non-polar

2-conductor) 

Maximum controllable indoor unit 

number per 1 MODBUS Convertor

128

Maximum controllable outdoor unit 

number per 1 MODBUS Convertor

100

Maximum connectable MODBUS 

Convertor number per 1 VRF System

9

Maximum number of connected 

MODBUS Convertor units to one 

MODBUS master unit

Without repeater

31

With repeater

247*

* Due to the limit in the number of slave addresses
 

Summary of Contents for UTY-VMGX

Page 1: ...English INSTALLATION MANUAL MODBUS CONVERTOR FOR VRF For authorized service personnel only PART NO 9374707133 03 UTY VMGX Original instructions ...

Page 2: ...purposes such as storing food raising animals growing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sun light Do not operate this unit when your hands are wet Touching the unit with wet hands will cause an electric shock If children may approach the unit take ...

Page 3: ...n away from television and ra dio to avoid distorted images and noise Otherwise a malfunction could result Perform wiring so that water does not enter this unit along the external wiring Always install a trap to the wiring or take other countermeasures Otherwise it will cause trouble or electric shock or fire Confirm the name of each unit and name of each terminal block of the unit and connect the...

Page 4: ...bles using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tight ened 5 Do not tight...

Page 5: ...6 in Tightening torque for installing cables to MODBUS connector 0 22 to 0 25 N m 1 9 to 2 2 lbf in 2 2 to 2 5 kgf cm 7 INSTALLING THE MODBUS CONVERTOR WARNING Always use the accessories and specified installation work parts Check the state of the installation parts Not using the specified parts will cause units to fall off electric shock fire etc Install at a place that can withstand the weight o...

Page 6: ...e cable as shown below 1 Remove the cable tie holder attached to the sheet metal 2 Attach the cable tie holder to the screw hole in the direction where the cable is wired 3 Fix the cable with the cable tie 7 2 Connecting the transmission cables 1 Turn the power off 2 Make a hole in the center of the dust proof bushing using a driver 3 Pass the transmission cables through the hole of dust proof bus...

Page 7: ... Factory setting When setting address please be sure that the address of MODBUS Convertor is not overlap the address of other controller like Touch Panel Controller Network Convertor for Group Remote Controller When the rotary switch is set to 16 or more MODBUS convertor Remote Controller Address setting is 15 2 Terminal resistance setting SW SET2 1 When there is no other terminal resistance in th...

Page 8: ...3 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 17...

Page 9: ...erminal resistances Set the terminal resistances at the both ends to be valid and set the terminal resistances other than at the both ends to be invalid ON Terminal resistance valid OFF Terminal resistance invalid Default The switches from 5 to 8 are read at the time of power on Even if these switches are changed after power on the setting is not reflected 10 Unused SW SET2 2 SET6 1 SET7 1 to 3 No...

Page 10: ...itch SET2 3 to ON 2 The indoor unit registered to the convertor starts the test run 3 Check that the indoor unit registered to the convertor performs the test run 4 Turn the test run switch SET2 3 to OFF 5 The indoor unit which performs the test run stops it When 60 minutes passes after the start of test run test run of indoor unit ends automatically Always turn the test run switch SET2 3 to OFF 1...

Page 11: ...ach manual Error indications Error contents LED1 green LED2 orange LED3 red 1 5 Scan error 1 6 Peripheral unit communication error Error indications Error contents LED5 green LED6 orange LED7 red 11 1 Peripheral unit main PCB error Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing ...