background image

En-4

Do not touch the circuit board and circuit board parts 

 

directly with your hands. 

Otherwise, injury or electric shock could result.

Tightening the mounting screws too tight will damage the 

 

case of this unit.

6.1. Select the wiring method

Method 1  From the top of the receiver unit: No additional  

   

work is necessary.

Method 2  From behind the receiver unit: Perform the  

   

following procedure to route the wiring behind  

   

the receiver unit.

Screw

Holder 

(PCB)

Holder cover

1

2

1

1

 Remove the screw.

2

 Remove holder (PCB)  

  from holder cover.

1

 Route the wiring as  

  shown in the figure.

2

1

Hook Holder cover

Screw

1

 Reattach holder cover. (Make sure that the hook on  

  the holder cover is caught on the holder [PCB].)

2

 Fix holder (PCB) by the screw.

6.2. Select the installation method

Method 1  Receiver unit embedded in a wall or ceiling:  

   

Refer to “I. Embedding the receiver unit.”

Method 2  Receiver unit attached to a wall or ceiling:  

   

Refer to “II. Attaching the receiver unit.”

Method 3  Receiver unit cannot be imbedded in or attached  

   

to a wall or ceiling: Refer to “III.  

   

Attaching the receiver unit to the indoor unit.”

I. Embedding the receiver unit

Unit: mm

58-62

120-14

0

Screws (M4 x 20mm)

Wall or ceiling

1

2

2

1

 Make a hole in the wall  

  or ceiling.

  (Depth: 25 mm or more)

1

 Affix the insulation to the 

 

  holder cover.

2

 Attach the holder cover  

  and the bracket (cover)  

  to the wall or ceiling  

  with the screws (included 

  with the standard parts).

Ex. Installation on the wall

5 m

120°

Indoor unit

Ceiling

5 m

Receiver 

unit

Remote 

controller

Signal reception 

angle

Ex. Installation on the ceiling

5 m

120°

Indoor unit

Ceiling

Remote 

controller

5 m

Receiver unit

Signal reception angle

If the wiring length is 10 m, replace with receiver unit cable C 

(optional parts).
Receiver unit cable A (5m).

6.  INSTALLING THE RECEIVER UNIT

 

WARNING

Always use the accessories and specified installation 

 

work parts. Check the state of the installation parts. Not 

using the specified parts will cause units to fall off, water 

leakage, electric shock, fire, etc.

Install at a place that can withstand the weight of the unit 

 

and install positively so that the unit will not topple or fall.

When installing this unit, make sure that there are no 

 

children nearby. 

Otherwise, injury or electric shock could result.

After installing this unit, perform the test run to confirm 

 

that the unit is operating properly. Then, explain the 

operation of this unit to the customer.

Install a circuit breaker. 

 

Otherwise, electric shock or fire could result.

 

CAUTION

Do not set the DIP switch or rotary switch of this unit 

 

except as specified in this installation manual or the 

instruction manual supplied with the air conditioner. 

Setting the switches other than specified will cause an 

accident or trouble.

Before opening the case of this unit, completely discharge 

 

static electricity charged on your body. Not doing so will 

cause trouble.

1

2

3

1

2

9374584048-02_IM_EN.indd   4

28/1/2554   14:37:11

Summary of Contents for UTB-*WB series

Page 1: ... Contents 1 SAFETY PRECAUTIONS 2 2 MAIN UNIT AND ACCESSORIES 3 3 OPTIONAL PARTS 3 4 FUNCTIONS AND DIMENSION 3 5 SELECTING THE INSTALLATION LOCATION 3 6 INSTALLING THE RECEIVER UNIT 6 1 Select the wiring method 4 6 2 Select the installation method 4 7 WIRING 5 8 TURNING ON THE POWER 7 9 ERROR CODE DISPLAY 7 English ...

Page 2: ...electric shock or a fire Perform installation work in accordance with the installation manual Request an authorized service personnel to perform installation work Do not install this unit by yourself Improper installation will cause injury electric shock fire etc In the event of a malfunction burning smell etc immediately stop operation turn off the electrical breaker and consult authorized servic...

Page 3: ...st 1 m away from a light source 4 Do not install the receiver unit where it will be exposed to direct sunlight 5 Do not install the receiver unit where it will be exposed directly to the airflow from the indoor unit 2 MAIN UNIT AND ACCESSORIES Description Q ty Application Installation manual 1 This book Receiver unit 1 For receiving the signal from the wireless remote controller Cover 1 For receiv...

Page 4: ...ver to the wall or ceiling with the screws included with the standard parts Ex Installation on the wall 5 m 1 2 0 Indoor unit Ceiling 5 m Receiver unit Remote controller Signal reception angle Ex Installation on the ceiling 5 m 120 Indoor unit Ceiling Remote controller 5 m Receiver unit Signal reception angle If the wiring length is 10 m replace with receiver unit cable C optional parts Receiver u...

Page 5: ...ok metal to the indoor unit with the screw s 7 WIRING WARNING Before starting installation work turn off the power of this unit and the connection destination Do not turn on the power again until installation is completed Otherwise it will cause electric shock or fire Use the accessories or specified power cable and connection cables Do not modify power cable and connection cables other than those...

Page 6: ...it cable A 5m Receiver unit MAX 10 m CONNECT Heat shrink tubing ø25 L130 Connect the cables and then use heat shrink tubing to protect the connection from dust and water droplets After shrinking both ends of the heat shrink tubing seal the ends with elec trical tape Provide a trap in the receiver unit wiring To prevent water droplets from entering the receiver unit EXAMPLE CAUTION Do not bind up t...

Page 7: ...e error code 9 ERROR CODE DISPLAY Error display Error content OPERATION LAMP TIMER LAMP FILTER SIGN LAMP No error 1 2 Remote controller communication error 1 3 Communication error between Outdoor unit 1 4 Network communication error 1 5 Scan error 1 6 Peripheral device communication error 2 1 Initial setting error 2 6 Address setting error 2 8 Other setting error 3 1 Indoor unit power supply abnor...

Page 8: ......

Reviews: