1
Fig. 1
INDOOR UNIT
OUTDOOR UNIT
Connection pipe
Large
3/4” (ø19.05 mm)
Small
3/8” (ø9.53 mm)
Max. height 49 ft (15 m)
Max. length 99 ft (30 m)
ELECTRICAL REQUIREMENT
GENERAL
This INSTALLATION MANUAL briefly outlines where
and how to install the air conditioning system. Please
read over the entire set of instructions for the indoor
and outdoor units and make sure all accessory parts
listed are with the system before beginning.
1. TYPE OF COPPER PIPE AND INSULATION
MATERIAL
Copper tubing for connecting the outdoor unit to the indoor
unit and insulation material is available for purchase locally.
When you purchase them, please specify the following.
(1) Deoxidized annealed copper pipe for refrigerant piping as:
2. ADDITIONAL MATERIALS REQUIRED FOR
INSTALLATION
(1) Refrigeration (armored) tape
(2) Insulated staples or clamps for connecting wire
(See your local electrical codes.)
(3) Putty
(4) Refrigeration lubricant
(5) Clamps or saddles to secure refrigerant piping
Always make the air conditioner power supply a spe-
cial branch circuit and provide a special switch and
receptacle. Do not extend the power cord.
3. OPERATING RANGE
Cut each pipe to the appropriate 12” (30 cm)
to 16” (40 cm) to dampen vibration between units.
(2) Foamed polyethylene insulation for copper pipes as
required to precise length of piping. Wall thickness of
the insulation should not be less than 5/16” (8 mm).
(3) Use insulated copper wire for field wiring.
Outer diameter
Thickness
Small pipe
3/8” (9.53 mm)
1/32” (0.8 mm)
Large pipe
3/4” (19.05 mm)
3/64” (1.0 mm)
Table 1
Temperature
Indoor
Outdoor
air intake
air intake
Cooling
Maximum
90°F DB, 73°F WB 115°F DB
Minimum
65°F DB, 57°F WB
70° F DB
Table 2
(1) Limit the height difference between
the indoor and outdoor units to
within 49 ft. (15 m).
(2) The maximum length of the piping
is 99 ft. (30 m). If the units are fur-
ther apart than this, correct opera-
tion can not be guaranteed.
MINIMUM CIRCUIT AMPACITY
20A
MAXIMUM OVERCURRENT PROTECTION
30A
(TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER)
Check local electrical codes and regula-
tions before obtaining wire. Also , check
any specified instructions or limitations.
Power supply
1ø 230/208V • 60Hz
Special branch circuit breaker
(Fuse/Breaker capacity : 30A)
30,000 BTU/h Type only
30,000 BTU/h Type only
Temperature
Indoor
Outdoor
air intake
air intake
Cooling
Maximum
90°F DB, 73°F WB 115°F DB
Minimum
65°F DB, 57°F WB
32° F DB
Table 2
36,000 BTU/h Type only
(1) Limit the height difference between
the indoor and outdoor units to
within 99 ft. (30 m).
(2) The maximum length of the piping
is 164 ft. (50 m). If the units are fur-
ther apart than this, correct opera-
tion can not be guaranteed.
36,000 BTU/h Type only