9. ELECTRICAL  WIRING

HOW TO CONNECT WIRING TO THE TERMINALS

A. For solid core wiring (or F-cable)

(1) Cut the wire end with a wire cutter or wire cut-

ting pliers, then strip the insulation to about
15/16” (25 mm) to expose the solid wire. 

(2) Using a screwdriver, remove the terminal screw

(s) on the terminal board. 

(3) Using pliers, bend the solid wire to form a loop

suitable for the terminal screw. 

(4) Shape the loop wire properly, place it on the ter-

minal board and tighten securely with the termi-
nal screw using a screwdriver.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire cut-

ting pliers, then strip the insulation to about 3/8”
(10 mm) to expose the strand wiring. 

(2) Using a screwdriver, remove the terminal screw

(s) on the terminal board. 

(3) Using a round terminal fastener or pliers, securely

clamp a round terminal to each stripped wire end. 

(4) Position the round terminal wire, and replace and

tighten the terminal screw with a screwdriver.

• Install the drain pipe with downward gradient (1/50 to

1/100) and so there are no rises or traps in the pipe. 

• Use general hard polyvinyl chloride pipe (VP25) [outside

diameter 1-1/2” (38 mm)]. 

• During installation of the drain pipe, be careful to avoid

applying pressure to the drain port of the indoor unit. 

• When the pipe is long, install supporters. (Fig. 31 ) 

• Do not perform air bleeding. 

• Always heat insulate (11/32” (8 mm) or over thick) the

indoor side of the drain pipe.

(1) Install insulation for the drain pipe. (See Figs. 32 and 33.) 

Cut the included insulation material to an appropriate
size and adhere it to the pipe.

(2) If “ 

q

Right rear piping “: fasten the drain pipe with

VT wire so that the pipe slopes correctly within the
indoor unit. (Fig. 34)

8. DRAIN  PIPING

Fig. 31 

Drain pipe 

Arrange the drain pipe
lower than this position. 

GOOD

Lifted
up

BAD

BAD

Wave

End in water 

Supporter

5 to 6.5 ft (1.5 to 2 m)

Fig. 32 

Drain pipe 

Insulation for Drain pipe
(To be obtained locally.

Length should be at least

11/32” (8 mm).) 

Indoor unit 
(drain port) 

Drain pipe insulation
(accessories)

Fig. 33 

Indoor unit 

No gap 

Drain pipe insulation 

Drain pipe 

13/32” (10 mm)
or over

Fig. 34 

VT wire 

Drain hose 

Indoor unit (rear view)

Fig. 35 

Solid wire 

Strand wire 

Loop

Insulation

Strip 15/16”

(25 mm)

Strip 3/8”

(10 mm)

Screw with
special washer 

Round
terminal

Terminal
board

Round
terminal

Screw with
special washer 

Round terminal 

Wire

Wire

Terminal block

Summary of Contents for SPLIT TYPE AIR CONDITIONER

Page 1: ...dges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floo...

Page 2: ... polyethylene insulation for copper pipes as required to precise length of piping Wall thickness of the insulation should not be less than 5 16 8 mm 3 Use insulated copper wire for field wiring Outer diameter Thickness Small pipe 3 8 9 53 mm 1 32 0 8 mm Large pipe 3 4 19 05 mm 3 64 1 0 mm Table 1 Temperature Indoor Outdoor air intake air intake Cooling Maximum 90 F DB 73 F WB 115 F DB Minimum 65 F...

Page 3: ...ge For indoor side pipe joint large pipe Coupler heat insulator small For indoor side pipe joint small pipe Nylon fastener For fixing the coupler heat insulator Special nut A large flange For installing indoor unit Special nut B small flange For installing indoor unit Installation template For positioning the indoor unit Auxiliary pipe assembly For connecting the piping Name and Shape Q ty Applica...

Page 4: ... over the room 3 Do not install the unit where it will be exposed to direct sunlight 4 Install the unit where connection to the outdoor unit is easy 5 Install the unit where the drain pipe can be easily installed 6 Take servicing etc into consideration and leave the spaces shown in Fig 2 or 3 Also install the unit where the filter can be removed FOR HALF CONCEALED INSTALLATION 2 OUTDOOR UNIT 1 Lea...

Page 5: ...ing position for Suspension bolt Ceiling Wall Template Drilling position for piping Fig 7 1 3 16 30 mm Suspension bolt pitch 63 1 600 mm 1 3 16 30 mm INDOOR UNIT TOP VIEW Dimensions Space Required for Installation For Half Concealed Installation Suspension bolt pitch should be as shown in Fig 7 Side cover B Right side 1 LOCATION OF CEILING SUSPENSION BOLTS 13 32 10 mm 6 3 32 155 mm 11 13 16 300 mm...

Page 6: ... Installation When installing the indoor unit in a semi concealed orientation make sure to reinforce the insulation of the unit on all sides Drops of water may fall from the unit if it is not thoroughly insulated Anchor Bolt Strength 7 23 to 10 85 ft lbs 100 to 150 kgf Fig 11 Ceiling panel 13 32 to 19 32 10 to 15 mm Special nut A Included Special nut B Included M10 Nut Obtained locally 3 DRILLING ...

Page 7: ...ks 4 CONNECTING THE PIPING 2 Remove outdoor unit cabinet A and cabinet D Fig 18 After removing the screws remove cabinet A by pushing it down Valve Cabinet A mounting direction Cabinet D Use the accessory screws at these points only Pipe Flare nut Small pipe Small width across flats 7 8 22 mm Large pipe Large width across flats 1 13 32 36 mm Table 3 1 OUTDOOR UNIT PROCESSING When the outdoor unit ...

Page 8: ...0 to 350 kgf cm Large pipe 57 86 to 72 37 ft lbs 800 to 1 000 kgf cm Table 4 Flare nut tightening torque Outdoor unit side 1 Tighten the flare nut of the connection pipe at the outdoor unit valve connector The tightening method is the same as that as at the indoor side 2 Seal with the accessory putty so that water does not enter at the top of the pipe insulation installed to the connection pipe la...

Page 9: ... from the closed state Table 5 4 Tighten the cap and charging valve of the two valves to the specified torque Table 6 5 VACUUMING AND ADDITIONAL CHARGE Table 6 Table 5 Cap Charging valve Tightening torque Large valve Small valve 10 85 to 14 47 ft lbs 150 to 200 kgf cm 5 07 to 6 51 ft lbs 70 to 90 kgf cm Open valve state Closed valve state If the handle is not fully open performance will drop and a...

Page 10: ...hard polyvinyl chloride pipe VP25 outside diameter 1 1 2 38 mm During installation of the drain pipe be careful to avoid applying pressure to the drain port of the indoor unit When the pipe is long install supporters Fig 31 Do not perform air bleeding Always heat insulate 11 32 8 mm or over thick the indoor side of the drain pipe 1 Install insulation for the drain pipe See Figs 32 and 33 Cut the i...

Page 11: ...rs Fig 38 1 Before starting work check that power is not being supplied to the outdoor unit 2 Match the terminal board numbers and connection cord colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts 3 Connect the connection cord firmly to the terminal board Imperfect installation may cause a fire 4 Always fasten the outside covering of the connection cord...

Page 12: ...V A C 60Hz 2 Before turning on verify that the volt age is within the 187 to 253V range 3 Always use a special branch circuit and install a special receptacle to supply power to the air conditioner 4 Use a circuit breaker and receptacle matched to the capacity of the air conditioner 5 The circuit breaker is installed in the permanent wiring Always use a cir cuit that can trip all the poles of the ...

Page 13: ...nit correctly receives the signal from the remote control unit then install the remote control unit holder 2 Select the remote control unit hold er selection site by paying careful attention to the following Avoid places in direct sunlight Select a place that will not be affected by the heat from a stove etc 1 REMOTE CONTORL UNIT HOLDER INSTALLATION Install the remote control unit holder to a wall...

Page 14: ...isconnect Connect C Disconnect Disconnect D Table 8 1 When removing the cabinet iron plate be careful not to damage the indoor unit internal parts and sur rounding area outer case 2 When processing the cabinet iron plate be careful not to injure your self with burrs etc 2 Fasten the round flange optional to the fresh air intake as shown in Fig 47 If using half concealed installation attach to the ...

Page 15: ...tor shortcircuited High pressure abnormal Outdoor discharge thermistor open circuited Outdoor discharge thermistor shortcircuited Discharge temperature abnormal Outdoor air temperature thermistor open circuited Outdoor air temperature thermistor shortcircuited Goes off Goes off Goes off Goes off Blinks Goes off Blinks Goes off Goes off Goes off Blinks Goes off Goes off Blinks Goes off Goes off Bli...

Page 16: ...June 2000 353 Rt 46 W Fairfield NJ 07004 888 888 FGAI www fujitsugeneral com ...

Reviews: