SPARC Enterprise T1000 Server Site Planning Guide
3
Environmental Specifications
Specification
Operating
Non-operating
Operating temperature:
• Sea level to 3000 ft
(900m)
• Above 3000 ft (900m)
• 41
°
F to 95
°
F (5
°
C to 35
°
C)
• Decrease maximum
temperature as altitude
increases, 1.6
°
F/1000 ft
(1
°
C/300m)
-40 to 60
°
C
-40 to 60
°
C
Humidity
20 to 80% RH,
non-condensing,
27
°
C wet bulb,
IEC 60068-2-3&56
98% RH 38
°
C,
non-condensing,
IEC 60068-2-3&56
Altitude
0-3,000 meters (0-10,000 feet)
IEC 60068-2-13
0 - 12,000 meters (0-40,000 feet)
IEC 60068-2-13
Vibration
0.2 Gs, Swept sine 5-500-5Hz,
1 octave/min, all axes,
IEC 60068-2-13
1.0 Gs, Swept sine 5-500-5Hz, 1
octave/min, all axes,
IEC 60068-2-13
Shock
5 Gs peak 11 milliseconds,
half-sine pulse,
IEC 60068-2-27
30 Gs peak 11 milliseconds,
half-sine pulse,
IEC 60068-2-27