The maximum value of the indoor fan speed is set as shown in Figure5, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
01-06
5. HEATING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure4.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow
of [HEAT] operation modes QUIET, LOW, MED, HIGH, as shown in Table4.
6. COOL AIR PREVENTION CONTROL (Heating mode)
( Fig.4 : Airflow change - over ( Heating : AUTO ) )
TR-Ts > -1.5°C
=
-2.5°C > TR-Ts
-1.5°C > TR-Ts > -2.5°C
=
TR-Ts > -1°C
=
-2°C > TR-Ts
-1°C > TR-Ts > -2°C
=
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
Low mode
Med mode
Med+ mode
Switch the airflow [AUTO] at cooling mode, and the indoor fan motor will run as shown in Figure6.
7. MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
( Fig.6 : Indoor Fan Control )
Compressor
ON
OFF
Indoor fan
Setting air flow
Indoor fan
(as shown in Table 5)
S-Lo
OFF
10
30
60
180
60
180
60
10
30
(SEC)
( Table5 : Indoor fan speed )
X zone
J zone
Y zone
30,36LMTA
780rpm
680rpm
680rpm
780rpm
Dry
Cooling
( Fig.5 : Cool Air Prevention Control )
Cool air
prevention
S-Lo
42°C
30°C
34°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Hi
*Me+
or setting fan mode
or setting fan mode
*Lo
or setting fan mode
39°C
37°C
37°C
32°C
28°C
*Lower speed is selected.