5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH,
while the indoor fan only runs.
When Fan mode is set at [AUTO], it operates on [MED] Fan Speed.
01-05
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure3.
On the other hand, if switched in [HIGH] [QUIET], the indoor motor will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED, HIGH, as shown in Table4.
( Fig.3 : Airflow change - over ( Cooling : AUTO ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
High mode
Med mode
Low mode
1. Fan speed
4. DRY OPERATION
Refer to the Table4.
During the dry mode operation, the fan speed setting can not be changed.
( Table4 : Indoor Fan Speed )
Operation mode
Air flow mode
Speed (rpm)
Cooling/ Fan
Hi
Hi
Me+
Me
Me
Heating
Lo
Lo
Quiet
Quiet
1370
Powerful
Powerful
1520
1260
1150
950
780
600
540
1370
1520
1150
950
780
Dry
S-Lo
X zone: 780
J zone: 680
Cool air prevention
S-Lo
540