Wave
FINISHING
(1) Insulate between pipes.
●
For rear, right, and bottom piping, overlap the connection pipe
heat insulation and indoor unit pipe heat insulation and bind
them with vinyl tape so that there is no gap.
●
For left and left rear piping, butt the connection pipe heat insula-
tion and indoor unit pipe heat insulation together and bind them
with and vinyl tape so that there is no gap.
●
For left and left rear piping, wrap the area which accommodates
the rear piping housing section with cloth tape.
●
For left and left rear piping, bind the connection cord to the top
of the pipe with vinyl tape.
●
For left and left rear piping, bundle the piping and drain hose
together by wrapping them with cloth tape over the range within
which they fit into the rear piping housing section.
(2) Temporarily fasten the connection cord along the connection pipe
with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with
sealer so that rain water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Fig. 16
Pipe
(Saddle)
(Outside wall cap)
(Sealer putty)
(Outdoors)
Fig. 15
Connection pipe
(heat insulation)
Bind the pipes together
to that there is no gap.
Overlap the insulation
Indoor unit pipe
(heat insulation)
Vinyl tape
Pipe
Drain hose
Cloth tape
Wrap with cloth tape
Left piping
Connection cord
Pipe
Drain hose
For connection from the left rear
Connection cord
Drain hose
Wall pipe
Connection pipe
Drain hose
GOOD
BAD
BAD
BAD
Lifted up
Saddle
End in water
Wall
FRONT PANEL REMOVAL AND INSTALLATION
THE OPEN PANEL REMOVAL
(1) Open the open panel.
(2) Pull down the knob.
(3) Lift the open panel upward, until the axle at the top of the open
panel is removed.
THE OPEN PANEL INSTALLATION
(1) The fixing axle of the open panel is installed on the front panel.
(2) Lay down the open panel.
THE FRONT PANEL REMOVAL
(1) Remove screw covers, then remove two screws.
(2) Remove the cord cover.
(3) Remove three screws.
(4) The front panel bottom is pulled to the front, and bottom hooks is
removed indoor unit.
(5) The front panel is pulled to the front, raising the upper surface,
and a front panel is removed.
THE FRONT PANEL INSTALLATION
(1) Firstly, fit the lower part of the front panel, and insert top and bot-
tom hooks. (Two top sides, two bottom sides)
(2) Five screws is attached.
(3) Two screw covers are attached.
(4) The cord cover is attached.
(5) The open panel is attached.
Front Panel
Front panel
Open panel
Open panel
Knob
Front panel
Screws (3 position)
Check the following:
View from indoors
Front panel
Top hook (two sides)
Top holes
(two sides)
Bottom hole
Bottom hooks
CUSTOMER GUIDANCE
CAUTION
(1) The power source capacity must be the sum of
the air conditioner current and the current of other
electrical appliances. When the current contracted
capacity is insufficient, change the contracted ca-
pacity.
(2) When the voltage is low and the air conditioner is
difficult to start, contact the power company the
voltage raised.
Explain the following to the customer in accordance with the operat-
ing manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control unit
operations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation manuals to the customer.
POWER
Fig. 17
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the elec-
tric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
CAUTION
(3) Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
(4) Always connect the ground wire.
(5) Do not use the earth screw for an external connector.
Only use for interconnection between two units.
ELECTRICAL WIRING (INDOOR UNIT)
HOW TO THE INSTALL THE INTER-UNIT WIRE HARNESS
1. Remove the screws, then remove the conduit holder and earth terminal.
2. Fasten the inter-unit wire harness to the conduit holder using the lock nut.
IMPORTANT: Refer to Fig. 19 about the length of inter-unit wire harness.
3. Use the screws to install the conduit holder and earth terminal with which
Inter-unit wire harness is included.
4. Remove the screws, then remove the cord cover and terminal cover.
5. Connect inter-unit wire harness to the terminal.
Refer to the wiring diagram.
6. Use the screws to install the cord cover and terminal cover.
Connection cord
Screw
Cord cover
(There is a
terminal block
inside.)
Connection cord
Screw
Cord cover
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 15/16" (25 mm) to expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using pliers, bend the solid wire to form a loop suitable for the termi-
nal screw.
(4) Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip
the insulation to about 3/8" (10 mm) to expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
board.
(3) Using a round terminal fastener or pliers, securely clamp a round
terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the termi-
nal screw using a screwdriver.
A. Solid wire
Str
ip 15/16" (25 mm)
Insulation
Loop
B. Strand wire
Str
ip 3/8" (10 mm)
Round
terminal
Wire
Screw with
special washer
Round
terminal
Terminal
board
Terminal block
Wire
Screw with
special washer
Round
terminal
HOW TO CONNECT WIRING TO THE TERMINALS
TEST RUNNING
The method of adjusting inter-unit wire harness
To connect inter-unit wire harness to the terminal correctly, please
refer to Fig. 19 to adjust the length of the part of Inter-unit Wire
harness ahead from conduit holder.
WIRED REMOTE CONTROL UNIT AND EXTERNAL CONNECT KIT (OPTIONAL)
BEFORE INSTALL WIRED REMOTE CONTROL UNIT
•
The wired remote control unit and the external connect kit are options. They aren't included in main body of air-
conditioner.
•
When you use wired remote control unit, some functions may not be used.
•
please use the recommended wired remote control unit.
(Before installing, Please read the FEATURES AND FUNCTIONS section of OPERATING MANUAL to confirm the
concerned contents.)
CAUTION
(1) Before installing, be sure to disconnect all power supply.
(2) Don't touch the heat exchanger.
(3) During installing or removing operation, be sure not to have wire catched by parts or draw it hard. Or it
may result troubles to the air-conditioner.
(4) Avoid place in direct sunlight.
(5) Select place that will not be affected by the heat from a stove, etc.
(6) Insure the length of wire is not over the recommended maxuim length.
(7) Before setting up the wired remote control unit, please confirm whether air-conditioner can receive the
signal.
1. FRONT PANEL, CONTROL BOX COVER AND CONTROL BOX COVER C REMOVAL.
(1) Refer to " FRONT PANEL REMOBAL AND INSTALLATION " to remove the front panel.
(2) Remove screws then remove the control box cover and the control box cover C.
Cotrol box cover
Screw
Screw
Connector (for wired remote control)
2. Connecting to control unit of wire
2.1 Connecting to wired remote control unit.
(1) Connect the wire of wired remote control unit to the connector (for wired remote control).
(2) Use cord clamper and screw to fasten the wire of wired remote control unit.
(3) Through the pass space the wire of wired remote control unit.
(4) Install the control box cover and the control box cover C. (Do not get in between control box and control box cover.)
2.2 Connecting to external connect kit.
(1) Connect the wire of external input/output to the board of external connect kit.
(2) Hook the wire to the rib.
(3) Fix the binder stopper with the screw and bind the wire with the binder.
(4) Through the pass space the wire of external connect kit.
(5) Install the control box cover and the control box cover C. (Do not get in between control box and control box cover.)
3. FRONT PANEL INSTALLATION
Install front panel by the reverse procedures as stated in "1. FRONT PANEL, CONTROL BOX COVER AND CONTROL BOX COVER C REMOVAL.".
Fig. 14
7
-1
5/32" (1
90mm)
1
5/1
6" (25mm)
1
5
/1
6" (25mm)
7
-1
1/1
6" (1
95mm)
(1:1)
14AWG
EARTH WIRE
CONDUIT PLATE
CONDUIT CONNECTOR
Fig. 19
Fig. 13
Fig. 12
LOCK NUT
CONDUIT HOLDER
CONDUIT CONNECTOR
SCREW
Cord clamper
●
Perform test operation and check items 1 and 2 below.
●
For the test operation method, refer to the operating manual.
●
The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit
while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)
●
To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously
flash slowly.)
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
Fig. 18
Transmitter section
Test run button
WARNING
(1) The rated voltage of this product is 208/230 V AC
60 Hz.
(2) Before turning on the power, check if the voltage
is within the 208 V-10% to 230V+10% range.
(3) Always use a special branch circuit and install a
special receptacle to supply power to the room
air conditioner.
(4) Use a circuit breaker and receptacle matched to
the capacity of the air conditioner.
(5) Do not extend the power cord.
(6) Perform wiring work in accordance with stand-
ards so that the air conditioner can be operated
safely and positively.
(7) Install a leakage circuit breaker in accordance with
the related laws and regulations and electric com-
pany standards.
PUMP DOWN OPERATION (FORCED COOLING OPERATION)
To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or
forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced
cooling operation.)
(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the
low-pressure valve slightly.
(2) Close the valve stem of 2 way valve completely.
(3) Start the cooling operation or following forced cooling operation.
When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)
(4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm
2
).
(5) Stop the operation.
• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
(It is not necessary to press on keeping for more than 10 seconds.)
CAUTION
During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.
REMOTE CONTROL UNIT INSTALLATION
CAUTION
(1) Check that the indoor unit correctly receives the
signal from the remote control unit, then install
the remote control unit holder.
(2) Select the remote control unit holder selection
site by paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat
from a stove, etc.
1. REMOTE CONTROL UNIT HOLDER INSTALLATION
•
Install the remote control unit with a distance of 23 ft(7
m) between the remote control unit and the photocell
as the criteria. However, when installing the remote con-
trol unit, check that it operates positively.
•
Install the remote control unit holder to a wall, pillar,
etc. with the tapping screw (Fig.20).
Remote control unit
holder fixing
Remote control
unit holder
Tapping
screw
(small)
Remote control
unit mounting
Remote
control unit
2
Push
1
Set
Fig. 20
IMPORTANT
This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched
with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated
capacity and efficiency. Installation of this product should follow the manufacturer's refrigerant charging and air flow
instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.
Bearing
Mounting shaft
EARTH WIRE
Screw
[ ] mark
1 2 3 4
Screw
Terminal cover
Screw
Terminal cover
Screw
Cotrol box cover C
Wire of wired remote control unit
Pass space
EXTERNAL INPUT: CONNECT TO NO.CN14
ENTERNAL OUTPUT: CONNECT TO NO.CN16
(
)
External input
External output
rid
binder stopper
screw
binder
pass space