background image

 

Wave

FINISHING

(1) Insulate between pipes.

For rear, right, and bottom piping, overlap the connection pipe
heat insulation and indoor unit pipe heat insulation and bind
them with vinyl tape so that there is no gap.

For left and left rear piping, butt the connection pipe heat insula-
tion and indoor unit pipe heat insulation together and bind them
with and vinyl tape so that there is no gap.

For left and left rear piping, wrap the area which accommodates
the rear piping housing section with cloth tape.

For left and left rear piping, bind the connection cord to the top
of the pipe with vinyl tape.

For left and left rear piping, bundle the piping and drain hose
together by wrapping them with cloth tape over the range within
which they fit into the rear piping housing section.

(2) Temporarily fasten the connection cord along the connection pipe

with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.)

(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with

sealer so that rain water and wind cannot blow in.

(5) Fasten the drain hose to the outside wall, etc.

Fig. 16

Pipe

(Saddle)

(Outside wall cap)

(Sealer putty)

(Outdoors)

Fig. 15

Connection pipe
(heat insulation)

Bind the pipes together
to that there is no gap.

Overlap the insulation

Indoor unit pipe
(heat insulation)

Vinyl tape

Pipe

Drain hose

Cloth tape

Wrap with cloth tape

Left piping

Connection cord

Pipe

Drain hose

For connection from the left rear

Connection cord

Drain hose

Wall pipe

Connection pipe

Drain hose

GOOD

BAD

BAD

BAD

Lifted up

Saddle

End in water

Wall

FRONT PANEL REMOVAL AND INSTALLATION

THE OPEN PANEL REMOVAL

(1) Open the open panel.
(2) Pull down the knob.
(3) Lift the open panel upward, until the axle at the top of the open

panel is removed.

THE OPEN PANEL INSTALLATION

(1) The fixing axle of the open panel is installed on the front panel.
(2) Lay down the open panel.

THE FRONT PANEL REMOVAL

(1) Remove screw covers, then remove two screws.
(2) Remove the cord cover.
(3) Remove three screws.
(4) The front panel bottom is pulled to the front, and bottom hooks is

removed indoor unit.

(5) The front panel is pulled to the front, raising the upper surface,

and a front panel is removed.

THE FRONT PANEL INSTALLATION

(1) Firstly, fit the lower part of the front panel, and insert top and bot-

tom hooks. (Two top sides, two bottom sides)

(2) Five screws is attached.
(3) Two screw covers are attached.
(4) The cord cover is attached.
(5) The open panel is attached.

Front Panel

Front panel

Open panel

Open panel

Knob

Front panel

Screws (3 position)

Check the following:

View from indoors

Front panel

Top hook (two sides)

Top holes
(two sides)

Bottom hole

Bottom hooks

CUSTOMER GUIDANCE

 CAUTION

(1) The power source capacity must be the sum of

the air conditioner current and the current of other
electrical appliances. When the current contracted
capacity is insufficient, change the contracted ca-
pacity.

(2) When the voltage is low and the air conditioner is

difficult to start, contact the power company the
voltage raised.

Explain the following to the customer in accordance with the operat-
ing manual:
(1) Starting and stopping method, operation switching, temperature

adjustment, timer, air flow switching, and other remote control unit
operations.

(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation manuals to the customer.

POWER

Fig. 17

(1) Match the terminal block numbers and connection

cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the elec-
tric parts.

(2) Connect the connection cords firmly to the terminal

block. Imperfect installation may cause a fire.

 CAUTION

(3) Always fasten the outside covering of the connection

cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)

(4) Always connect the ground wire.

(5) Do not use the earth screw for an external connector.

Only use for interconnection between two units.

ELECTRICAL WIRING (INDOOR UNIT)

HOW TO THE INSTALL THE INTER-UNIT WIRE HARNESS

1. Remove the screws, then remove the conduit holder and earth terminal.
2. Fasten the inter-unit wire harness to the conduit holder using the lock nut.

IMPORTANT: Refer to Fig. 19 about the length of inter-unit wire harness.

3. Use the screws to install the conduit holder and earth terminal with which

Inter-unit wire harness is included.

4. Remove the screws, then remove the cord cover and terminal cover.
5. Connect inter-unit wire harness to the terminal.

Refer to the wiring diagram.

6. Use the screws to install the cord cover and terminal cover.

Connection cord

Screw

Cord cover

(There is a

terminal block

inside.)

Connection cord

Screw

Cord cover

A. For solid core wiring (or F-cable)

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 15/16" (25 mm) to expose the solid wire.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using pliers, bend the solid wire to form a loop suitable for the termi-

nal screw.

(4) Shape the loop wire properly, place it on the terminal board and

tighten securely with the terminal screw using a screwdriver.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 3/8" (10 mm) to  expose the strand wiring.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using a round terminal fastener or pliers, securely clamp a round

terminal to each stripped wire end.

(4) Position the round terminal wire, and replace and tighten the termi-

nal screw using a screwdriver.

A. Solid wire

Str

ip 15/16" (25 mm)

Insulation

Loop

B. Strand wire

Str

ip 3/8" (10 mm)

Round
terminal

Wire

Screw with
special washer

Round
terminal

Terminal
board

Terminal block

Wire

Screw with
special washer

Round
terminal

HOW TO CONNECT WIRING TO THE TERMINALS

TEST RUNNING

The method of adjusting inter-unit wire harness

To connect inter-unit wire harness to the terminal correctly, please
refer to Fig. 19 to adjust the length of the part of Inter-unit Wire
harness ahead from conduit holder.

WIRED REMOTE CONTROL UNIT AND EXTERNAL CONNECT KIT (OPTIONAL)

BEFORE INSTALL WIRED REMOTE CONTROL UNIT

The wired remote control unit and the external connect kit are options. They aren't included in main body of air-
conditioner.

When you use wired remote control unit, some functions may not be used.

please use the recommended wired remote control unit.

(Before installing, Please read the FEATURES AND FUNCTIONS section of OPERATING MANUAL to confirm the
concerned contents.)

 CAUTION

(1) Before installing, be sure to disconnect all power supply.

(2) Don't touch the heat exchanger.

(3) During installing or removing operation, be sure not to have wire catched by parts or draw it hard. Or it

may result troubles to the air-conditioner.

(4) Avoid place in direct sunlight.

(5) Select place that will not be affected by the heat from a stove, etc.

(6) Insure the length of wire is not over the recommended maxuim length.

(7)  Before setting up the wired remote control unit, please confirm whether air-conditioner can receive the

signal.

1. FRONT PANEL, CONTROL BOX COVER AND CONTROL BOX COVER C REMOVAL.

(1)  Refer to " FRONT PANEL REMOBAL AND INSTALLATION " to remove the front panel.
(2)  Remove screws then remove the control box cover and the control box cover C.

Cotrol box cover

Screw

Screw

Connector (for wired remote control)

2. Connecting to control unit of wire

2.1 Connecting to wired remote control unit.

(1) Connect the wire of wired remote control unit to the connector (for wired remote control).
(2) Use cord clamper and screw to fasten the wire of wired remote control unit.
(3) Through the pass space the wire of wired remote control unit.
(4) Install the control box cover and the control box cover C. (Do not get in between control box and control box cover.)

2.2 Connecting to external connect kit.

(1) Connect the wire of external input/output to the board of external connect kit.

(2) Hook the wire to the rib.
(3) Fix the binder stopper with the screw and bind the wire with the binder.
(4) Through the pass space the wire of external connect kit.
(5) Install the control box cover and the control box cover C. (Do not get in between control box and control box cover.)

3. FRONT PANEL INSTALLATION

Install front panel by the reverse procedures as stated in "1. FRONT PANEL, CONTROL BOX COVER AND CONTROL BOX COVER C REMOVAL.".

Fig. 14

7

-1

5/32" (1

90mm)

1

5/1

6" (25mm)

1

5

/1

6" (25mm)

7

-1

1/1

6" (1

95mm)

(1:1)

14AWG

EARTH WIRE

CONDUIT PLATE

CONDUIT CONNECTOR

Fig. 19

Fig. 13

Fig. 12

LOCK NUT

CONDUIT HOLDER

CONDUIT CONNECTOR

SCREW

Cord clamper

Perform test operation and check items 1 and 2 below.

For the test operation method, refer to the operating manual.

The outdoor unit, may not operate, depending on the room temperature. In this case, press the test run button on the remote control unit
while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)

To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously
flash slowly.)

1. INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the air flow-direction louver operate normally?
(4) Is the drain normal?

2. OUTDOOR UNIT

(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?

Fig. 18

Transmitter section

Test run button

 WARNING

(1) The rated voltage of this product is 208/230 V AC

60 Hz.

(2) Before turning on the power, check if the voltage

is within the 208 V-10% to 230V+10% range.

(3) Always use a special branch circuit and install a

special receptacle to supply power to the room
air conditioner.

(4) Use a circuit breaker and receptacle matched to

the capacity of the air conditioner.

(5) Do not extend the power cord.

(6) Perform wiring work in accordance with stand-

ards so that the air conditioner can be operated
safely and positively.

(7) Install a leakage circuit breaker in accordance with

the related laws and regulations and electric com-
pany standards.

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation or
forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the forced
cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the

low-pressure valve slightly.

(2) Close the valve stem of 2 way valve completely.
(3) Start the cooling operation or following forced cooling operation.

When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5) Stop the operation.

• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
  (It is not necessary to press on keeping for more than 10 seconds.)

 

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.

REMOTE CONTROL UNIT INSTALLATION

 CAUTION

(1) Check that the indoor unit correctly receives the

signal from the remote control unit, then install
the remote control unit holder.

(2) Select the remote control unit holder selection

site by paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat
from a stove, etc.

1. REMOTE CONTROL UNIT HOLDER INSTALLATION

Install the remote control unit with a distance of 23 ft(7
m) between the remote control unit and the photocell
as the criteria. However, when installing the remote con-
trol unit, check that it operates positively.

Install the remote control unit holder to a wall, pillar,
etc. with the tapping screw (Fig.20).

Remote control unit
holder fixing

Remote control
unit holder

Tapping
screw
(small)

Remote control
unit mounting

Remote
control unit

Push

Set

Fig. 20

IMPORTANT

This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched
with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated
capacity and efficiency. Installation of this product should follow the manufacturer's refrigerant charging and air flow
instructions. Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life.

Bearing

Mounting shaft

EARTH  WIRE

Screw
[ ] mark

1 2 3 4

Screw

Terminal cover

Screw

Terminal cover

Screw

Cotrol box cover C

Wire of wired remote control unit

Pass space

EXTERNAL INPUT: CONNECT TO NO.CN14
ENTERNAL OUTPUT: CONNECT TO NO.CN16

(

)

External input

External output

rid

binder stopper

screw

binder

pass space

Reviews: