GENERAL
This INSTALLATION MANUAL briefly outlines where
and how to install the air conditioning system. Please
read over the entire set of instructions for the indoor
and outdoor units and make sure all accessory parts
listed are with the system before beginning.
1. TYPE OF COPPER PIPE AND INSULATION MATERIAL
Copper tubing for connectin the outdoor unit to the indoor
unit and insulation material is available for purchase locally.
When you purchase them, please specify the following.
A. Deoxidized annealed copper pipe for refrigerant piping as:
Table 3
Small pipe
Large pipe
Outer diameter
Thickness
Outer diameter
Thickness
1/4”(6.35 mm)
1/32”(0.8 mm)
3/8”(9.52 mm)
1/32”(0.8 mm)
Name and Shape
Wall hook bracket
Remote
control unit
Battery (penlight)
Cloth tape
Remote control
unit holder
Tapping screw (big)
(ø4
×
20)
Tapping screw (small)
(ø3
×
12)
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as re-
quired.
INDOOR UNIT ACCESSORIES
Q’ty
1
1
2
1
1
8
2
Use
For indoor unit installation
Use for air conditioner
operation
For remote control unit
For indoor unit installation
Use as remote control unit
holder
For wall hook bracket
installation
For remote control unit
holder installation
Connection pipe assembly
Connection cord (3-conductor)
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
Name
Q’ty
1
1
1
1
1
1
1 set
1
1 set
1
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch cir-
cuit and provide a special switch and receptacle. Do not extend the
power cord.
The following items are necessary to install this air conditioner. (The
items are not included with the air conditioner and must be purchased
separately.)
CAUTION
9000 BTU/h 12000 BTU/h
MINIMUM CIRCUIT AMPACITY
12 A
15 A
MAXIMUM OVERCURRENT PROTECTION
15 A
20 A
(TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER)
Cut each pipe to the appropriate 12” (30 cm)
to16” (40 cm) to dampen vibration between units.
B. Foamed polyethylene insulation for copper pipes as
required to precise length of piping. Wall thickness
of the insulation should not be less than 5/16” (8 mm).
C. Use insulated copper wire for field wiring.
CAUTION
Check local electrical codes and regulations
before obtaining wire. Also, check any specified
instructions or limitations.
ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 25 ft (7.5 m) is charged in
the outdoor unit at the factory.
When the piping is longer than 25 ft (7.5 m), additional charging is necessary.
For the additional amount, see the table below.
Pipe length
Additional
refrigerant
25 ft (7.5 m)
None
Table 5
33 ft (10 m)
1.8 oz (50 g)
Between 25 ft (7.5 m) and 49 ft (15 m), when using a connection pipe
other than that in the table, charge additional refrigerant with 0.7 OZ/
3.3 ft (20g/1 m) as the criteria.
49 ft (15 m)
5.3 oz (150 g)
CAUTION
(1) When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(2) The maximum length of the piping is 15 m. If the
units are further apart than this, correct opera-
tion can not be guaranteed.
2. ADDITIONAL MATERIALS REQUIRED FOR INSTALLATION
A. Refrigeration (armored) tape
B. Insulated staples or clamps for connecting wire
(See your local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping
3. OPERATING RANGE
Table 4
Heating Mode
About 17 to 75 °F
88 °F or less
Outdoor temperature
Indoor temperature
Cooling/Dry Mode
About 32 to 115 °F
About 64 to 90 °F
About 80% or less
About 50% or less
Indoor
Humidity
Outdoor
temperature
68°F or obove
Outdoor
temperature
below 68°F