background image

En-8

TIMER OPERATION

Before using the timer function, be sure that the Remote Controller is set to the correct current time (

 P. 5).

To Use the ON timer or OFF timer

1

  Press the START/STOP button (Fig. 6 

Q

)

 

(if the unit is already operating, proceed to step 2).

 

The indoor unit’s OPERATION Indicator Lamp (red) (Fig. 3 

5

) will light.

2

  Press the TIMER MODE button (Fig. 6 

N

) to select the 

OFF timer or ON timer operation.

 

Each time the button is pressed the timer function changes in the following 
order:

 

       CANCEL  

OFF  

ON

 PROGRAM(OFF 

 ON, OFF 

 ON)

 

The indoor unit’s green TIMER Indicator Lamp (Fig. 3 

6

) will light.

3

  Use the TIMER SET buttons (Fig. 6 

O

) to adjust the 

desired OFF time or ON time.

 

Set the time while the time display is 

fl

 ashing  (the 

fl

 ashing will continue for 

about 

fi

 ve seconds).

 button: 

Press to advance the time.

 button: 

Press to reverse the time.

 

About 

fi

 ve seconds later, the entire display will reappear.

To Use the Program timer

1

  Press the START/STOP button (Fig. 6 

Q

).

 

(if the unit is already operating, proceed to step 2).

 

The indoor unit’s OPERATION Indicator Lamp (red) (Fig. 3 

5

) will light.

2

  Set the desired times for OFF timer and ON timer.

 

See the section “To Use the ON timer or OFF timer” to set the desired mode 
and times.

 

About three seconds later, the entire display will reappear.

 

The indoor unit’s TIMER Indicator Lamp (green) (Fig. 3 

6

) will light.

3

  Press the TIMER MODE button (Fig. 6 

N

) to select the 

PROGRAM timer operation (OFF   ON or OFF   ON 
will display).

 

The display will alternately show “OFF timer” and “ON timer”, then change to 
show the time setting for the operation to occur 

fi

 rst.

  The program timer will begin operation. (If the ON timer has been selected 

to operate 

fi

 rst, the unit will stop operating at this point.)

 About 

fi

 ve seconds later, the entire display will reappear.

About the Program timer

  The program timer allows you to integrate OFF timer and ON timer operations in a 

single sequence. The sequence can involve one transition from OFF timer to ON timer, 
or from ON timer to OFF timer, within a twenty-four hour period.

 The 

fi

 rst timer function to operate will be the one set nearest to the current time. The 

order of operation is indicated by the arrow in the Remote Controller’s Display (OFF 

 ON, or OFF 

 ON).

  One example of Program timer use might be to have the air conditioner automatically 

stop (OFF timer) after you go to sleep, then start (ON timer) automatically in the morn-
ing before you arise.

To Cancel the Timer

Use the TIMER button to select “CANCEL”.
The air conditioner will return to normal 
operation.

To Change the Timer Settings

Perform steps 

2

 and 

3

.

To Stop Air Conditioner Operation while 
the Timer is Operating

Press the START/STOP button.

To Change Operating Conditions

If you wish to change operating conditions 
(Mode, Fan Speed, Thermostat Setting, 
SUPER QUIET mode), after making the timer 
setting wait until the entire display reappears, 
then press the appropriate buttons to change 
the operating condition desired.

To Cancel the Timer

Use the TIMER MODE button to select “CAN-
CEL”.
The air conditioner will return to normal opera-
tion.

To Change the Timer Settings

1.  Follow the instructions given in the section “To 

Use the ON Timer or OFF Timer” to select the 
timer setting you wish to change.

2.  Press the TIMER MODE button to select 

either OFF   ON or OFF   ON.

To Stop Air Conditioner Operation while 
the Timer is Operating

Press the START/STOP button.

To Change Operating Conditions

If you wish to change operating conditions 
(Mode, Fan Speed, Thermostat Setting, SUPER 
QUIET mode), after making the timer setting 
wait until the entire display reappears, then 
press the appropriate buttons to change the 
operating condition desired.

9315345325-03_OM.indb   Sec1:8

9315345325-03_OM.indb   Sec1:8

2/25/2013   10:08:40 AM

2/25/2013   10:08:40 AM

Summary of Contents for Inverter AOBR30JFT

Page 1: ...JFC Outdoor Unit AOBR30JFT COOL MODEL ROOM AIR CONDITIONER WALL MOUNTED TYPE KEEP THIS OPERATION MANUAL FOR FUTURE REFERENCE GUARDE ESTE MANUAL DE USO PARA FUTURAS CONSULTAS GUARDE ESTE MMANUAL DE FUNCIONANENTO PARA REFERÊNCIA FUTURA 9315345325 03_OM indb 1 9315345325 03_OM indb 1 2 25 2013 10 08 18 AM 2 25 2013 10 08 18 AM ...

Page 2: ...lants in the direct path of the air flow Do not drink the water drained from the air conditioner Do not use in applications involving the storage of foods plants or animals precision equipment or art works Do not apply any heavy pressure to radiator fins Operate only with air filters installed Do not block or cover the intake grille and outlet port Ensure that any electronic equipment is at least ...

Page 3: ...e REMOVABLE OPEN PANEL The indoor unit s Open Panel can be removed for easy cleaning and maintenance MILDEW RESISTANT FILTER The AIR FILTER has been treated to resist mildew growth thus allowing cleaner use and easier care SUPER QUIET OPERATION When the FAN button is used to select QUIET the unit begins super quiet operation the indoor unit s airflow is reduced to produce quieter operation POLYPHE...

Page 4: ...K L J N W R S T U O V a Z b X Fig 7 To facilitate explanation the accompanying illustra tion has been drawn to show all possible indicators in actral operation however the display will only show those indicators appropriate to the current operation 9315345325 03_OM indb Sec1 3 9315345325 03_OM indb Sec1 3 2 25 2013 10 08 39 AM 2 25 2013 10 08 39 AM ...

Page 5: ...isplay a SLEEP Display b SWING Display NAME OF PARTS Fig 1 Indoor Unit 1 Operating Control Panel Fig 2 2 MANUAL AUTO button When kept on pressing the MANUAL AUTO button for more than 10 seconds the forced cooling operation will start The forced cooling operation is used at the time of installation Only for authorized service personnel s use When the forced cooling operation starts by any chance pr...

Page 6: ...ncluded with this product 2 Insert batteries Be sure to align the battery polarities correctly 3 Close the battery compartment lid Set the Current time 1 Press the CLOCK ADJUST button Fig 6 W Use the tip of a ball point pen or other small object to press the button 2 Use the TIMER SET buttons Fig 6 O to adjust the clock to the current time button Press to advance the time button Press to reverse t...

Page 7: ... Set the Fan Speed Press the FAN button Fig 6 P Each time the button is pressed the fan speed changes in the following order AUTO HIGH MED LOW QUIET About three seconds later the entire display will reappear When set to AUTO Cooling As the room temperature approaches that of the thermostat setting the fan speed becomes slower Fan The fan runs at the low fan speed The fan will operate at a very low...

Page 8: ...et in the ther mostat The monitor operation range is 2 C relative to the thermostat set ting If the mode automatically selected by the unit is not what you wish select one of the mode operation COOL DRY FAN About Mode Operation Cooling Use to cool your room Dry Use for gently cooling while dehumidifying your room You cannot heat the room during Dry mode During Dry mode the unit will operate at low...

Page 9: ...t the Program timer The program timer allows you to integrate OFF timer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operation is indicated by the arrow in the Remote Contro...

Page 10: ...tomatically modifies the thermostat setting in accordance with the set time setting When the set time has elapsed the air conditioner completely stops During Cooling Dry operation When the SLEEP timer is set the thermostat setting is automatically raised 1 C every 1 hour When the thermostat has been raised a total of 2 C the thermostat setting at that time is maintained until the set time has elap...

Page 11: ...range When used in a room with infants children elderly or sick persons the air direction and room temperature should be considered carefully when making settings Vertical Air Direction Adjustment Press the SET button Vertical Fig 6 R Each time the button is pressed the air direction range will change as follows 1 2 3 4 5 6 Types of Air flow Direction Setting 1 2 3 During Cooling Dry modes 1 2 3 4...

Page 12: ...e left right swing operation will stop Before cleaning the air conditioner be sure to turn it off and disconnect the Power Supply Cord Be sure the Intake Grille Fig 1 8 is installed securely When removing and replacing the air filters be sure not to touch the heat exchanger as personal injury may result CAUTION CLEANING AND CARE To avoid excessive wear of the part and components or malfunctioning ...

Page 13: ...ct the two lower tabs and pull out 2 Remove dust with a vacuum cleaner or by washing After washing allow to dry thoroughly in a shaded place 3 Replace the Air Filter and close the Intake Grille 1 Align the sides of the air filter with the panel and push in fully making sure the two lower tabs are returned properly to their holes in the panel 2 Close the Intake Grille For purposes of example the il...

Page 14: ...For storage of the Air Cleaning Filters use the filters as soon as possible after the package has been opened The air cleaning effect decreases when the filters are left in the opened package Generally the filters should be exchanged about every three months Please buy delicated air cleaning filters UTR FA13 1 Sold separately to exchange the used dirty air cleaning filters Negative air ions deodor...

Page 15: ...er stopping the unit the sound of water flowing in the air conditioner s piping may be heard Also noise may be particularly noticeable for about 2 to 3 minutes after starting operation sound of coolant flowing During operation a slight squeaking sound may be heard This is the result of minute expansion and contraction of the front cover due to temperature changes Smells Some smell may be emitted f...

Page 16: ...ted by setting before the power failure If a power failure occurs during TIMER operation the timer will be reset and the unit will begin or stop operation at the new time setting In the event that this kind of timer fault occurs the TIMER Indicator Lamp will flash see Page 3 Use of other electrical appliances electric shaver etc or nearby use of a wireless radio transmitter may cause the air condi...

Page 17: ...NERGY EFICIENCY RATIO kW kW 3 41 AIRFLOW INDOOR UNIT m3 h 1 100 OUTDOOR UNIT m3 h 3 600 MAX PRESSURE MPa 4 12 REFRIGERANT R410A kg 1 90 DIMENSIONS WEIGHT NET INDOOR UNIT HEIGHT mm 320 WIDTH mm 998 DEPTH mm 228 WEIGHT kg 14 OUTDOOR UNIT HEIGHT mm 830 WIDTH mm 900 DEPTH mm 330 WEIGHT kg 58 9315345325 03_OM indb Sec1 16 9315345325 03_OM indb Sec1 16 2 25 2013 10 08 41 AM 2 25 2013 10 08 41 AM ...

Page 18: ...9315345325 03_OM indb 17 9315345325 03_OM indb 17 2 25 2013 10 08 46 AM 2 25 2013 10 08 46 AM ...

Page 19: ...9315345325 03_OM indb 18 9315345325 03_OM indb 18 2 25 2013 10 08 46 AM 2 25 2013 10 08 46 AM ...

Page 20: ...9315345325 03_OM indb 19 9315345325 03_OM indb 19 2 25 2013 10 08 46 AM 2 25 2013 10 08 46 AM ...

Reviews: