Switch buttons and the functions
S134
S133
S132
S131
S130
(1)
(2)
(3)
(4)
(5)
LED lamps
Switch buttons
LED lamp
Function or operation method
(1) POWER/MODE
Green
Lights on while power on.
Local setting in outdoor unit or error code is displayed with blink.
(2) ERROR
Red
Blinks during error operation.
(3) PUMP DOWN (L1)
Orange Lights on during pump down operation.
(4)
LOW NOISE MODE
(L2 and L3)
Orange
Lights on during “Low noise mode” when local setting is activated.
(Lighting pattern of L2 and L3 indicates low noise level.)
(5)
PEAK CUT MODE
(L4, L5, and L6)
Orange
Lights on during “Peak cut mode” when local setting is activated.
(Lighting pattern of L4, L5, and L6 indicates peak cut level.)
Switch button
Function or operation method
S134
MODE
Switches between “Local setting” and “Error code display”.
S133
SELECT
Switches between the individual “Local settings” and the “Error code
displays”.
S132
ENTER
Switches between the individual “Local settings” and the “Error code
displays”.
S131
EXIT
Returns to “Operation status display”.
S130
PUMP DOWN
Starts the pump down operation.
- 66 -
13-1. Control PCB and switch buttons location
13. Function settings
OUTDOOR UNIT
AOHG36-54KRTA
OUTDOOR UNIT
AOHG36-54KRTA