6-2. Models: AOHG45KRTA and AOHG54KRTA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
20
30
40
50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30
—
—
—
—
0.900
0.879
0.858
20
—
—
—
0.937
0.915
0.894
0.872
10
—
—
0.973
0.952
0.931
0.908
0.887
7.5
—
0.988
0.977
0.956
0.934
0.913
0.891
5
0.992
0.992
0.981
0.960
0.938
0.916
0.894
0
1.000
1.000
0.989
0.967
0.945
0.923
0.901
Indoor unit is lower than
outdoor unit *2
-5
1.000
1.000
0.989
0.967
0.945
0.923
0.901
-7.5
—
1.000
0.989
0.967
0.945
0.923
0.901
-10
—
—
0.989
0.967
0.945
0.923
0.901
-20
—
—
—
0.967
0.945
0.923
0.901
-30
—
—
—
—
0.945
0.923
0.901
HEATING
Pipe length (m)
5
7.5
10
20
30
40
50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30
—
—
—
—
0.978
0.968
0.958
20
—
—
—
0.988
0.978
0.968
0.958
10
—
—
0.998
0.988
0.978
0.968
0.958
7.5
—
1.000
0.998
0.988
0.978
0.968
0.958
5
1.000
1.000
0.998
0.988
0.978
0.968
0.958
0
1.000
1.000
0.998
0.988
0.978
0.968
0.958
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.995
0.993
0.983
0.973
0.963
0.953
-7.5
—
0.993
0.991
0.981
0.971
0.961
0.951
-10
—
—
0.988
0.978
0.968
0.958
0.948
-20
—
—
—
0.968
0.958
0.949
0.939
-30
—
—
—
—
0.949
0.939
0.929
- 54 -
6-2. Models: AOHG45KRTA and AOHG54KRTA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG36-54KRTA
OUTDOOR UNIT
AOHG36-54KRTA