| Recommended AC power line sizes |
Recommended AC power line sizes
When installing your storage system, you must determine the AC power line lengths running from the storage
system to the power source.
By properly designing longer AC power feeds, you can preserve voltage levels to the equipment. The longer
power feeds—the wiring from the breaker panel to the power strip, which supplies power to the storage system
and disk shelves—can often exceed 50 feet.
Note:
Total AC wire length = breaker to wall or ceiling extension cable or ceiling drop.
The following tables list the recommended conductor size for 2 percent voltage drop for a particular distance
measured in feet (taken from the Radio Engineer's Handbook). The circuits in the following tables are
described in American Wire Gauge (AWG) measurements:
Table 7:
110V, single-phase 20A circuit
30A circuit
40A circuit
50A circuit
25 feet
12 AWG
10 AWG
8 AWG
8 AWG
50 feet
8 AWG
6 AWG
6 AWG
4 AWG
75 feet
6 AWG
4 AWG
4 AWG
2 AWG
Table 8:
220V, single-phase 20A circuit
30A circuit
40A circuit
50A circuit
25 feet
14 AWG
12 AWG
12 AWG
10 AWG
50 feet
12 AWG
10 AWG
8 AWG
8 AWG
75 feet
10 AWG
8 AWG
6 AWG
6 AWG
The following table lists the approximate equivalent wire gauge (AWG to Harmonized Cordage).
Table 9:
AWG
8
10
12
Harmonized, mm-mm
mm-mm = millimeter
squared
4.0
2.5
1.5
48