8-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External input
and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
Mode
Function
setting
External input
and output
PCB (Rotary
SW)
External input
Indoor unit
Input
External input and output PCB
Terminal
Input 1
Input 2
Signal type
0-1
60-00
1
Operation/Stop
Operation/Stop
Not available
Edge
Operation
Stop
Pulse
0-2
60-00
2
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
1—8
60-01 to
60-08
3 - 9, A
(Setting prohibited)
9
60-09
B
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
10
60-10
C
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
11
60-11
D
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
Mode
Function
setting
External input
and output
PCB (Rotary
SW)
External output
Indoor unit
Output
External input and output PCB
CN47
Output 1
Output 2
Output 3
0-1
60-00
1
Operation/Stop
Operation/Stop
Error status
Indoor unit fan
operation status
0-2
60-00
2
Operation/Stop
Error status
Indoor unit fan
operation status
External heater
output
1—8
60-01 to
60-08
3 - 9, A
(Setting prohibited)
9
60-09
B
Error status
Operation/Stop
Indoor unit fan
operation status
External heater
output
10
60-10
C
Indoor unit fan
operation status
Operation/Stop
Error status
External heater
output
11
60-11
D
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
NOTE:
Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (R.C. disabled)
- 24 -
8-3. Combination of external input and output
8. External input and output
CASSETTE TYPE
AUXG18, 22KRLB
CASSETTE TYPE
AUXG18, 22KRLB