E R R O R C O N T E N T S
The OPERATION, TIMER and SWING lamps operate
as follows according to the error contents.
Error display
OPERATION
TIMER
SWING
(RED)
(GREEN)
(ORANGE)
Error contents
Indoor unit circuit board error
Indoor unit room temperature sensor wire opened
Indoor unit room temperature sensor wire short circuited
Indoor unit piping sensor wire opened
Indoor unit piping sensor short circuited
Serial error
Outdoor unit circuit board error or miswiring
between outdoor unit and indoor unit
Outdoor unit compressor temperature sensor error
Outdoor unit piping sensor
Outdoor unit outdoor temperature sensor error
2 times
2 times
3 times
3 times
5 times
Indoor unit fan error
6 times
5 times
9 times
IPM error
10 times
Current transformer error
11 times
Active filter module error
12 times
Compressor location error
13 times
Outdoor fan motor error
14 times
Outdoor unit discharge temperature sensor error
5 times
3 times
4 times
:
Fast flashing
:
Slow flashing
:
Off
DIP switch
DIP-SW
1
2
3
Current
Model
(Max.)
OFF
OFF
OFF
16.5A
AOY30LMAL
ON
OFF
OFF
14.5A
AOY24LMAL
OFF
ON
OFF
12.0A
ON
ON
OFF
9.5A
5
2004.07.22
Summary of Contents for AWY24LBAJ
Page 13: ...Models AWY24LBAJ AWY30LBAJ 122 D I S A S S E M B L Y I L L U S T R A T I O N 12 2004 06 16 ...
Page 14: ...998 329 735 45 999 158 345 120 Models AWY24LBAJ AWY30LBAJ 13 2004 07 23 588 146 1 588 1 146 ...
Page 15: ...Models AWY24LBAJ AWY30LBAJ 14 2004 06 16 ...
Page 16: ...Models AWY24LBAJ AWY30LBAJ 15 2004 06 16 ...
Page 17: ...Models AWY24LBAJ AWY30LBAJ 16 2004 06 16 ...
Page 18: ...Models AWY24LBAJ AWY30LBAJ 17 2004 06 16 ...
Page 19: ...Models AWY24LBAJ AWY30LBAJ 18 2004 06 16 855 428 70 1 70 2 230 385 868 253 3 759 1 63 ...
Page 20: ...Models AWY24LBAJ AWY30LBAJ 19 2004 11 12 ...
Page 21: ...Models AOY24LMAL AOY30LMAL 20 2004 07 23 7 183 1 949 1 ...
Page 27: ...0406G2619 ...