CONNECTION PIPE REQUIREMENT
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 !C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat
insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker
and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(maK) or less (at 20 !C).
Use pipe with water-resistant heat insulation.
CAUTION
The maximum lengths of this product are shown in the following table. If the units are further apart than this, correct
operation can not be guaranteed.
Name and Shape
Q'ty
Application
For outdoor unit drain
piping work (May not be
supplied, depending on
the model.)
For filling in a gap at the
entrance of connection
cords
1
2
1
Drain pipe
Drain cap
Insulation (seal)
STANDARD PARTS
The following installation parts are furnished.
Use them as required.
MAX.
50 m
70 m
Pipe length
MIN.
5 m
30 m
Maximum height
(between indoor
and outdoor)
Model Type
Liquid
Gas
30,000 BTU/h class
36,000 BTU/h class
9.52 mm (3/8 in.) 15.88 mm (5/8 in.)
45,000 BTU/h class
Diameter
WARNING
For the air conditioner to operate satisfactorily. install it as outlined in this installation instruction sheet.
Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available standards parts. This
installation instruction sheet describes the correct connections using the installation set available from our standard parts.
Installation work must be performed in accordance with national wiring standards by authorized personnel only.
Also, do not use an extension cord.
Do not turn on the power until all installation work is complete.
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is not extra refrigerant in the outdoor unit for air purging.
Use a vacuum pump for R410A exclusively.
Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
Use a clean gauge manifold and charging hose for R410A exclusively.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it
produces a toxic gas.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
1
2
3
4
5
6
7
8
9
10
11
2005.06.27
36
Summary of Contents for AUY30LUAS
Page 9: ...Model AOY45LJBYL 2005 06 22 8 ...
Page 19: ...481 481 481 481 1 Models AUY30LUAS AUY36LUAS AUY45LUAS DISASSEMBLY ILLUSTRATION 2005 06 24 18 ...
Page 21: ...146 1 184 1 146 2 47 1 138 187 235 564 735 896 Models AUY30LUAS AUY36LUAS 2005 06 27 20 ...
Page 23: ...138 187 735 184 1 235 Model AUY45LUAS 2005 06 27 22 ...
Page 24: ...Models AUY30LUAS AUY36LUAS AUY45LUAS 2005 06 27 23 ...
Page 25: ...Models AOY30LMAWL AOY36LMAWL 2005 06 07 24 1 6 7 3 4 5 2 ...
Page 26: ...17 18 10 13 11 9 15 14 8 Models AOY30LMAWL AOY36LMAWL 2005 06 07 25 ...
Page 27: ...2005 06 07 26 22 23 31 18 20 29 12 28 12 19 24 26 27 25 30 Models AOY30LMAWL AOY36LMAWL ...
Page 28: ...2005 06 07 27 37 38 33 34 Models AOY30LMAWL AOY36LMAWL 36 35 ...
Page 29: ...1 6 7 5 2 3 4 3 Model AOY45LJBYL 2005 06 07 28 ...
Page 30: ...13 12 11 10 9 15 14 Model AOY45LJBYL 2005 06 22 29 ...
Page 31: ...22 20 21 23 24 19 17 18 26 25 Model AOY45LJBYL 2005 06 07 30 ...
Page 32: ...31 38 27 34 35 36 28 39 40 41 30 32 29 33 37 Model AOY45LJBYL 2005 06 07 31 ...
Page 38: ...0504G2853 ...