DANGER
This part (Choke coil) generates high voltages.
Never touch this part.
SPECIAL INSTALLATION
SETTING
PUMP DOWN (Refrigerant collecting operation)
Perform the following procedures to collect the refrigerant when moving
the indoor unit or the outdoor unit.
(1) Press the push-button switch (SW2) on the circuit board once.
The LED on the circuit board starts flashing (one second ON/one se-
cond OFF). This indicates the start of PUMP DOWN operation.
When the switch is pressed while the compressor is in operation, PUMP
DOWN operation starts automatically.
When the switch is pressed while the compressor is in stop, the com-
pressor starts to operate automatically, and then move on to PUMP
DOWN operation.
(2) PUMP DOWN operation continues for about 1 minute. When PUMP
DOWN operation is completed, the compressor stops automatically.
Then close the 2-way valve and 3-way valve immediately.
(3) Turn the power off.
ERROR CONTENTS
(outdoor unit)
1. Make a TEST RUN in accordance with the in-
stallation instruction sheet for the indoor unit.
2. OUTDOOR UNIT LEDS
When a malfunction occurs in the outdoor unit, the LED on the circuit
board lights to indicate the error. Refer to the following table for the de-
scription of each error according to the LED.
Error contents
Communication error
(Indoor unit - Outdoor unit)
Discharg pipe temperature sensor
Outdoor heat exchanger temperature sensor
Outdoor temperature sensor
Compressor temperature sensor
Heat sink temperature sensor
Pressure switch abnormal
IPM error
Compressor rotor position cannot detect
Compressor cannot operate
Outdoor fan abnormal (upper fan)
Outdoor fan abnormal (lower fan)
Protect operation
No error
LED
1 flash
2 flash
3 flash
4 flash
7 flash
8 flash
9 flash
12 flash
13 flash
14 flash
15 flash
16 flash
5 sec. ON/
1 sec. OFF
repeated
lighting
CAUTION
Always turn on the power 12 hours prior to the start of the
operation in order to ensure compressor protection
PUMP DOWN SW (SW2)
2005.06.07
17
Summary of Contents for AUY30LUAS
Page 9: ...Model AOY45LJBYL 2005 06 22 8 ...
Page 19: ...481 481 481 481 1 Models AUY30LUAS AUY36LUAS AUY45LUAS DISASSEMBLY ILLUSTRATION 2005 06 24 18 ...
Page 21: ...146 1 184 1 146 2 47 1 138 187 235 564 735 896 Models AUY30LUAS AUY36LUAS 2005 06 27 20 ...
Page 23: ...138 187 735 184 1 235 Model AUY45LUAS 2005 06 27 22 ...
Page 24: ...Models AUY30LUAS AUY36LUAS AUY45LUAS 2005 06 27 23 ...
Page 25: ...Models AOY30LMAWL AOY36LMAWL 2005 06 07 24 1 6 7 3 4 5 2 ...
Page 26: ...17 18 10 13 11 9 15 14 8 Models AOY30LMAWL AOY36LMAWL 2005 06 07 25 ...
Page 27: ...2005 06 07 26 22 23 31 18 20 29 12 28 12 19 24 26 27 25 30 Models AOY30LMAWL AOY36LMAWL ...
Page 28: ...2005 06 07 27 37 38 33 34 Models AOY30LMAWL AOY36LMAWL 36 35 ...
Page 29: ...1 6 7 5 2 3 4 3 Model AOY45LJBYL 2005 06 07 28 ...
Page 30: ...13 12 11 10 9 15 14 Model AOY45LJBYL 2005 06 22 29 ...
Page 31: ...22 20 21 23 24 19 17 18 26 25 Model AOY45LJBYL 2005 06 07 30 ...
Page 32: ...31 38 27 34 35 36 28 39 40 41 30 32 29 33 37 Model AOY45LJBYL 2005 06 07 31 ...
Page 38: ...0504G2853 ...