background image

(m

3

/min)

80
70
60
50

40
30
20
10

0

0

2

4

6

8

12000 and 14000 BTU/h models

18000 BTU/h model

L=5m

DUCT
STATIC
PRESSURE

(Pa)

N

L

1

(L)

2

(N)

3 4 5 6

N

L

1

(L)

2

(N)

3 4 5

N

L

1(L)2(N) 3 4 5 6

N

L

1(L)2(N) 3

JM1

JM2

JM3

10

REMOTE CONTROL UNIT

INSTALLATION

Install the remote control unit so that the front is facing the photocell.
(Fig. 36)

Fig. 36

Install the remote control unit with a distance of 5 m between the re-
mote control unit and the grille photocell as the criteria.
However, when installing the remote control unit, check that it operates
positively.

 CAUTION

(1) Check that the indoor unit correctly receives the sig-

nal from the remote control unit, then install the remote
control unit holder.

(2) Select the remote control unit holder selection site by

paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from
a stove, etc.

Remote control unit

Photocell

1. REMOTE CONTROL UNIT HOLDER

INSTALLATION

Install the remote control unit holder to a wall, pillar, etc. with the tap-
ping screws.

Fig. 37

1

 Set

Remote Control Unit
holder fixing

Remote Control
Unit mounting

2

 Push

Remote
control unit

Tapping
screws
(small)

Remote control
unit holder

2. SWITCHING REMOTE CONTROL UNIT SIGNAL

CODES

Air conditioner settings

Fig. 38

Indoor unit
Printed circuit board

Table 8

Jumper wire

JM3

Connect

Disconnect

Connect

Disconnect

Remote control unit

signal code

A (Primary setting)

B

C

D

JM2

Connect

Connect

Disconnect

Disconnect

(4) Press the MASTER CONTROL button again to return to the clock

display and change the signal code.

Confirm the setting of the remote control unit signal code and the printed
circuit board setting.
If these are not confirmed, the remote control unit cannot be used to oper-
ate for the air conditioner.

Remote control unit settings

(1) Press the START/STOP button and display only the clock.

Fig. 39

(2) Press the MASTER CONTROL button continuously for more than five

seconds to display the current signal code.

Fig. 40

(3) Change the signal code with the 

 button (

).

Fig. 41

11

TEST RUNNING

Perform test operation and check items 1 and 2 below.

For the operation method, refer to the operating manual.

The outdoor unit may not run, depending on the room temperature.
In this case, the ‘TEST RUN’ signal is received during air conditioner
operation (use a metallic object to short the two metal contacts under
the battery compartment lid and send the ‘TEST RUN’ signal from the
remote control unit).

Fig. 42

Short the two metal contacts under
the battery compartment lid.

To end test operation, press the remote control unit START/STOP but-
ton.
(When the air conditioner is run by pressing the remote control unit
TEST RUN button, the OPERATION and TIMER lamps will simultane-
ously flash slowly.)

SWING

TIMER OPERATION

MANUAL

AUTO

OPERATION
LAMP (Red)

SWING LAMP
(Orange)

TIMER LAMP
(Green)

Operation can be checked by lighting and flashing of the grille display
section OPERATION and TIMER lamps.
Perform judgment in accordance with the following.

Test running

When the air conditioner is run by pressing the remote control unit test
run button, the OPERATION and TIMER lamps flash slowly at the same
time.

Error

The OPERATION, TIMER and SWING lamps operate as follows
(Table 9) according to the error contents.

Error display

OPERATION

lamp

TIMER

lamp

SWING 

lamp

Error contents

Model information abnormal
(permanent type)

Drain abnormal (permanent 
type)

Indoor fan abnormal

Room air temperature 
thermistor open circuit

Room air temperature 
thermistor short circuit

Piping thermistor open
circuit

Piping thermistor short
circuit

Goes off

Goes off

Goes off

Goes off

Blinks

Goes off

Blinks

Blinks

Blinks

Blinks

Blinks

Blinks

Blinks

Pulses
4 times

Pulses
6 times

Pulses
2 times

Pulses
3 times

Table 9

CHECK ITEMS

(1) INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?

(2) OUTDOOR UNIT

(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?

Do not operate the air conditioner in the test running state for a long
time.

12

OPENING THE  DUCT
CONNECTION HOLE

Fig. 43

Fresh air

Distribution
duct

Distribution
duct

 CAUTION

(1) When performing hole opening work, be careful not to

damage the drain pan.

(2) When connecting the distribution duct, to make the air

flow easily, block the outlet port with the blower cover
insulation as shown by the hatched lines in Fig. 43. For
the blocking direction, refer to Fig. 26.

1. DIMENSION

(1) Fresh air duct connection hole and screw positions.

Fig. 44

Unit: mm

79

55

50

36

74

50.8

(2) Distribution duct connection hole and screw positions.

Fig. 45

Unit: mm

6-ø3.3 Self tapping
screw holes (for 4mm)
P.D 170

130

284

45

˚

ø150

 CAUTION

The air conditioner cannot take in fresh air by itself.
When connecting a fresh air duct, always use a duct fan.

OUTLET AIR

Fig. 46

Duct (inside dia. 150 mm)

Static pressure required to
take in fresh air

L

FRESH AIR

Fig. 47

P

Duct

Duct Fan

(m

3

/min)

70

60

50
40

30

20
10

0

0                   0.1                  0.2                 0.3 

(Pa)

DUCT
STATIC
PRESSURE

13

INSTALLING THE  OPTION

PARTS (ADDITIONAL GRILLE)

THE ADDITIONAL GRILLE

Mount the assembled additional grille to the indoor unit (grille) that has
been removed from the main unit.

Make sure all areas are properly installed the reinforcement plate.

Mount 4 additional grilles. (Fig. 49)

After confirming proper meshing of the additional grilles, secure them
in place using the 8 screws provided.

Fig. 48

Fig. 49 Illustration of completed mounting

POSITION THE CEILING HOLE AND HANGING BOLTS

Fig. 50

 CAUTION

When installing the additional grille, please refer to the in-
stallation instruction sheet supplied with the additional
grille.

Additional grille

Screw (long)

Reinforcement plate

Screw (short)

Indoor unit (grille)

Additional grille

A

Indoor unit (grille)

Reinforcement
plate

400mm (15-3/4”)

606mm(23-27/32

”)

720mm(    28-11/32

”)

 770mm (     30-5/16”)

(Hanging bolt position)

(Ceiling opening measurement)

(Grille measurement)

(Hanging bolt position)

PART NO. 9359992097

9

POWER

 WARNING

(1) The rated voltage of this product is 230 V A.C. 50 Hz.

(2) Before turning on the verify that the voltage is within

the 198 V to 264 V range.

(3) Always use a special branch circuit and install a spe-

cial breaker to supply power to the air conditioner.

(4) Use a circuit breaker matched to the capacity of the  air

conditioner. (Install in accordance with standard)

(5) The circuit breaker is installed in the permanent wir-

ing. Always use a circuit that can trip all the poles of
the wiring and has an isolation distance of at least 3
mm between the contacts of each pole.

(6) Perform wiring work in accordance with standards so

that the air conditioner can be operated safely and posi-
tively.

(7) Install a leakage circuit breaker in accordance with the

related laws and regulations and electric company
standards.

 CAUTION

(1) The power source capacity must be the sum of the air

conditioner current and the current of other electrical
appliances. When the current contracted capacity is in-
sufficient, change the contracted capacity.

(2) When the voltage is low and the air conditioner is diffi-

cult to start, contact the power company the voltage
raised.

(3) This air conditioner must be connected to a power

source that has an electrical impedance of 0.25 

 or

less or has a supply current of 100 A or greater. If the
power supply does not meet the specifications, con-
tact the power company.

8

(Piping direction)

Blower cover
insulation

A-A Section view

A

A

2 direction example

Fit the blower cover insulation.

Motor cover assembly

Wire

Wire hook

Wire hook

Wire

Bolting the grille assembly to the body

Install the grille assembly to the body with the four bolts, spring washers,
and washers.

GRILLE INSTALLATION

1. Blower cover insulation

Install the blower cover insulation only when the outlet direction is not
specified.
Two blower cover insulations are packed with the grille assembly. Install
the blower cover insulation at the diffuser position shown in Fig. 26. At the
time, use the piping position as the criteria.

Fig. 26

2. Installing grille assembly to body

Hang the grille assembly on the wires attached to the indoor unit as shown
in Fig. 27.

Fig. 27

No gap between ceiling and
grille around entire periphery.

Display PCB
wire harness

Fig. 28

Wireless unit connection wire wiring

Connect the connector in accordance part A detail view.
Then clamp the lead wire with clamp so that it does not touch the rotating
parts.

Fig. 29

Bolt

Washer

A

Fig. 30 Part A detail view

Display PCB wire harness

Wire (Louver)

Joint wire (Louver)

(2) Close the intake grille, then slide the two grille stoppers outward.

Fig. 32

2. Removing the intake grille

(1) Slide the two grille stoppers inward, then open the intake grille.

Fig. 33

(2) Remove the grille hook screws, then open the intake grille.

Fig. 34

(3) Open the intake grille so that it is at an angle of 20° to 40°, then

remove the grille.

Fig. 35

Grille hook

INSTALLING/REMOVING THE INTAKE GRILLE

1. Installing the intake grille

(1) Fully insert the intake grille hooks into the rectangular holes in the

panel.

Fig. 31

Grille stopper

Grille stopper

Intake grille

Panel

Rectangular hole

Grille hook

 CAUTION

(1) The louver angle cannot be changed if the power is not

on, (If moved by hand, it may be damaged.)

(2) The grille assembly is directional relative to the air con-

ditioner body.

(3) Install so that there is no gap between the grille as-

sembly and the air conditioner body.

A. Solid wire

Str

ip 25 mm (15/16

”)

Insulation

Loop

B. Strand wire

Str

ip 10 mm (3/8

”)

Round
terminal

Wire

Screw with
special washer

Round terminal

Terminal
board

Wire

Screw with
special washer

Round
terminal

HOW TO CONNECT WIRING TO THE TERMINALS

A. For solid core wiring (or F-cable)

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 25 mm (15/16”) of expose the solid wire.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using pliers, bend the solid wire to form a loop suitable for the

terminal screw.

(4) Shape the loop wire properly, place it on the terminal board and

tighten securely with the terminal screw using a screwdriver.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip

the insulation to about 10 mm (3/8”) of expose the strand wiring.

(2) Using a screwdriver, remove the terminal screw(s) on the terminal

board.

(3) Using a round terminal fastener or pliers, securely clamp a round

terminal to each stripped wire end.

(4) Position the round terminal wire, and replace and tighten the ter-

minal screw using a screwdriver.

Fig. 19

7

ELECTRICAL WIRING

(1) Remove the control box cover and install the connection cord.

(Figs. 20 and 21)

Fig. 20

Control box cover

1

(L)

2

(N)

3

4

5

Connection cord

Terminal board

Cord clamp

1

(L)

2

(N)

3

4

5

Connection cord

Terminal board

Cord clamp

[12000, 14000 and 18000  BTU/h Heat & Cool models (Reverse
cycle)]

Fig. 23

Terminal cover

[18000 BTU/h Cooling model]

Terminal
board

Control box

Cord clamp

Insulation tube

Power supply
cord

Connection cord

Terminal
board

Control box

Cord clamp

Insulation tube

Power supply
cord

Connection cord

[18000 BTU/h Heat & Cool model (Reverse cycle)]

Insulation tube

Insulation tube (Use VW-1,
0.5 to 1.0 mm thick, PVC
tube as the insulation tube)

After passing the connection
cord through the insulation
tube, fasten it with the cord
clamp.

Connection cord

Cord clamp

Connection cord

Green/Yellow

1

(L)

2

(N)

3

4

5

L

N

1

(L)

2

(N)

3

4

5

EARTH

EARTH

Green/Yellow

1

(L)

2

(N)

3

4

5

6

L

N

1

(L)

2

(N)

3

4

5

6

EARTH

EARTH

Indoor unit
side terminal

Power supply

Outdoor unit
side terminal

[12000,14000 and 18000 BTU/h Heat & Cool models  (Reverse
cycle)]

Indoor unit
side terminal

Power supply

Outdoor unit
side terminal

8

Wire

1. Indoor unit side

 WARNING

(1) Before starting work, check that power is not being sup-

plied to indoor unit and the outdoor unit.

(2) Match the terminal board numbers and connection cord

colors with those of the outdoor unit side.
Erroneous wiring may cause burning of the electric
parts.

(3) Connect the connection cords firmly to the terminal

board. Imperfect installation may cause a fire.

(4) Always fasten the outside covering of the connection

cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)

(5) Always connect the ground wire.

Fig. 21

[12000 and 14000 BTU/h Cooling models]

Connection cord

Terminal board

Cord clamp

2. Outdoor unit side

 WARNING

(1) Before starting work, check that power is not being

supplied to the indoor unit and outdoor unit.

(2) Match the terminal board numbers and connection cord

colors with those of the indoor unit side.
Erroneous wiring may cause burning of the electric
parts.

(3) Connect the connection cords and the power supply

cord firmly to the terminal board. Imperfect installation
may cause a fire.

(4) Always fasten the outside covering of the connection

cord and the power supply cord with cord clamps. (If
the insulator is chafed, electric leakage may occur.)

(5) Always connect the ground wire.

(1) Remove the terminal cover of the outdoor unit, and insert the end of

the connection cord and the power supply cord into the terminal board.

(2) Fasten the connection cord and the power supply cord with the cord

clamps.

(3) Install the terminal cover.

Terminal board

Cord clamp

Insulation tube

Connection cord

Power supply cord

65 mm

80 mm

Control box

 CAUTION

When routing the ground wires, leave slack as shown in
the illustrations.

[12000 and 14000 BTU/h Heat & Cool models (Reverse cycle)]

Terminal board

Cord clamp

Insulation tube

Connection cord

Power supply cord

Control box

45 mm

65 mm

Fig. 25

[12000 and 14000 BTU/h Cooling models]

Fig. 24

[18000 BTU/h Cooling model]

[18000 BTU/h Cooling model]

Terminal cover

Fig. 22

[12000 and 14000 BTU/h Cooling models]

45 mm

45 mm

45 mm

45 mm

Indoor unit
side terminal

Power supply

Outdoor unit
side terminal

1

(L

)

2

(N

)

3

4

5

L

N

1

(L)

2

(N)

3

EARTH

Green/Yellow

1

(L)

2

(N)

3

4

5

EARTH

Spring washer

Reviews: