background image

LO

HI

Gas

Liquid

R410A

1

OUTDOOR UNIT

 WARNING

(1) Install the unit where it will not be tilted by more than

5˚.

(2) When installing the outdoor unit where it may exposed

to strong wind, fasten it securely.

(1) If possible, do not install the unit where it will exposed to direct sun-

light. (If necessary, install a blind that does not interfere with the air
flow.)

(2) Install the outdoor unit in a place where it will be free from being dirty

or getting wet by rain as much as possible.

(3) Install the unit when connection to the indoor unit is easy.
(4) Do not place animals and plants in the path of the warm air.
(5) Take the air conditioner weight into account and select a place where

noise and vibration are small.

(6) Select a place so that the warm air and noise from the air conditioner

do not disturb neighbors.

(7) Provide the space shown in Fig. 3 so that the air flow is not blocked.

Also for efficient operation, leave open three of the four directions
front, rear, and both sides.

(8) During heating operation, drain water flows from the outdoor unit.

Therefore, install the outdoor unit in a place where the drain water
flow will not be obstructed. (Reverse cycle model only)

Fig. 3

INSTALLATION PROCEDURE

Install the air conditioner as follows:

SPLIT TYPE AIR CONDITIONER

INSTALLATION INSTRUCTION
SHEET

(PART NO. 9359992097)

 WARNING

This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of
the user.

 CAUTION

This mark indicates procedures which, if improperly performed, might possibly result in personal harm to
the user, or damage to property.

This air conditioner uses new refrigerant HFC (R410A).

The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:

(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models, some of the piping and

installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the
conventional piping and flare nuts with the R410A piping and flare nuts.

(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with con-

ventional refrigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2
UNF 20 threads per inch.]

(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when

storing the piping, securely seal the openings by pinching, taping, etc.

(4) When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and

always charge from the liquid phase side whose composition is stable.

Special tools for R410A

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount
of residual oil is less than 40 mg/10 m. Do not use copper pipes having a
collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with
contaminants.
As an air conditioner using R410A incurs pressure higher than when using
R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 1. Never
use copper pipes thinner than 0.8 mm (Nominal diameter is 1/4 in., 3/8 in.,
1/2 in.), even when it is available on the market.

For authorized service personnel only.

 WARNING

(1) For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.

(2) Connect the indoor unit and outdoor unit with the air conditioner piping and cords available from our standards parts. This

installation instruction sheet describes the correct connections using the installation set available from our standard parts.

(3) Installation work must be performed in accordance with national wiring standards by authorized personnel only.

(4) Do not turn on the power until all installation work is complete.

Be careful not to scratch the air conditioner when handling it.

After installation, explain correct operation to the customer, using the operating manual.

Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.

Refrigerant

R410A

Contents of change

Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm

2

) for high pressure.

–0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm

2

) for low pressure.

To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.

Tool name

Gauge manifold

Charge hose

Vacuum pump

Gas leakage detector

Table 1   Thicknesses of Annealed Copper Pipes

Nominal

diameter (inch)

1/4

3/8

1/2

Thickness (mm)

R410A

[ref.] R22

0.80

0.80

0.80

0.80

0.80

0.80

Outer diameter

(mm)

6.35

9.52

12.70

INDOOR UNIT INSTALLATION

1. Position the ceiling hole and hanging bolts as

shown in Fig. 4.

Fig. 4

(4 directions)

(3 directions)

100 mm (4”) or more

Piping position

(2 directions)

100 mm (4”) or more

100 mm (4”) or more

(2 directions)

SELECTING THE MOUNTING POSITION

Pipe

Pipe

INDOOR UNIT

(1) Install the indoor unit on a place having a sufficient strength so that it

withstands against the weight of the indoor unit.

(2) The inlet and outlet ports should not be obstructed; the air should be

able to blow all over the room.

(3) Leave the space required to service the air conditioner. (Fig. 2)
(4) The ceiling rear height is 250 mm (9-3/8”) or more.
(5) A place from where the air can be distributed evenly throughout the

room by the unit.

(6) A place from where drainage can be extracted outdoors easily.

Fig. 2

Especially, the installation place is very important for the split type air con-
ditioner because it is very difficult to move from place after the first instal-
lation.
Decide the mounting position together with the customer as follows:
The discharge direction can be selected as shown below.

Fig. 1

 CAUTION

Since 2-way outlet as shown below causes performance
problems, do not set it.

Strong and durable ceiling

Obstruction

250 mm
(9-3/8”)
or more

1,000 mm (39”)
or more

1,000 mm (39”)
or more

STANDARD PARTS

The following installation parts are furnished. Use them as required.

INDOOR UNIT ACCESSORIES

Name and Shape

Coupler heat insulation

Special nut A (large flange)

Special nut B (small flange)

Template

Remote control unit

Battery (penlight)

Remote control unit holder

Tapping screw (ø3 

×

 12)

Q’ty

2

4

4

1

1

2

1

2

Application

For indoor side pipe joint

For installing indoor unit

For installing indoor unit

For ceiling hole cutting

Use for air conditioner
operation

For remote control unit

For mounting the remote
control unit

For remote control unit
holder installation

440 mm (17-5/16”)

(Hanging bolt position)

606 mm (23-27/32”)

(

650 mm) (Grille measurement)

(

650 mm (25-15/32”)

(Hanging bolt position)

400 mm (15-3/4”)

66 mm (2-19/32”)

2. Hanging preparations

Firmly fasten the hanging bolts as shown in Fig. 5 or by another method.

Fig. 5

Hanging bolt

M10

Hole-in anchor
Hole-in plug

Concrete

Insert

(5-5/32

”)

131 mm

(4-3/8

”)

111 mm

47 mm (1-27/32

”)

60 mm (2-3/8”)

Drain pipe (I. D. ø32 mm)

    600 mm (    23-5/8”)
(Ceiling opening measurement)

46 mm (1-27/32”)

86 mm (3-3/8”)

250 mm (9-27/32

”)

54 mm (2-1/8

”)

3. Body installation

(1) Install special nut A, then special nut B onto the hanging bolt. (Fig. 7)
(2) Raise the body and mount its hooks onto the hanging bolt between

the special nuts. (Fig. 7)

(3) Turn special nut B to adjust the height of the body. (Fig. 7)
(4) Leveling

Using a level, or vinyl hose filled with water, fine adjust so that the
body is level.

 WARNING

Perform final tightening by tightening the double nut firmly.

Fig. 7

Vinyl hose

Special nut A

Special nut B

Hook

Hanging bolt

30 mm
or more

After installing the
body, tighten the nuts.

15 mm (19/32”)

Ceiling

Fig. 8

2

INSTALLING DRAIN PIPE

Note: Install the drain pipe.

Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.

Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32
mm (1-1/4”)] and connect it with adhesive (polyvinyl chloride) so that
there is no leakage.

When the pipe is long, install supporters.

Do not perform air bleeding.

Always heat insulate the indoor side of the drain pipe.

When desiring a high drain pipe height, raise it up to 400 mm (15”) or
less from the ceiling within a range of 150 mm (6”) from the body. A
rise dimension over this range will cause leakage.

Fig. 9

Max. 400 mm (15”)

Rise

Trap

Supporter

1.5 to 2.0 m (5 to 6.5 ft)

Air bleeding

150 mm (6”) or less

4

CONNECTING THE  PIPING

 WARNING

Do not use the existing (for R22) piping and flare nuts.

If the existing materials are used, the pressure inside the
refrigerant cycle will rise and cause breakage, injury, etc.
(Use the special R410A materials.)

 CAUTION

(1) Do not use mineral oil on flared part.

Prevent mineral oil from getting into the system as this
would reduce the lifetime of the units.

(2) While welding the pipes, be sure to blow dry nitrogen

gas through them.

(3) The maximum lengths of this product are shown in ta-

ble 2. If the units are further apart than this, correct
operation can not be guaranteed.

1. FLARING

(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and

remove the burrs.

(3) Insert the flare nut (always use the flare nut attached to the indoor

and outdoor units respectively) onto the pipe and perform the flare
processing with a flare tool.
Use the special R410A flare tool, or the conventional (for R22) flare
tool.
When using the conventional flare tool, always use an allowance ad-
justment gauge and secure the A dimension shown in table 4.

Fig. 11

Check if [L] is flared uniformly
and is not cracked or scratched.

Die

A

Pipe

L

When bending the pipe, do not
bend it as is. The pipe will be
collapsed. In this case, cut the
heat insulating pipe with a
sharp cutter as shown in Fig.
13, and bend it after exposing
the pipe. After bending the pipe
as you want, be sure to put the
heat insulating pipe back on the
pipe, and secure it with tape.

 CAUTION

(1) To prevent breaking of the pipe, avoid sharp bends.

Bend the pipe with a radius of curvature of 150 mm or
over.

(2) If the pipe is bent repeatedly at the same place, it will

break.

Extend the pipe
by unwinding it.

Fig. 13

Cut line

Pipe

Heat insulating
pipe

Cutter

3. Connection pipes

(1) Indoor unit side

Fig. 14

 CAUTION

(1) Be sure to apply the pipe against the port on the in-

door unit correctly. If the centering is improper, the flare
nut cannot be tightened smoothly. If the flare nut is
forced to turn, the threads will be damaged.

(2) Do not remove the flare nut from the indoor unit pipe

unit immediately before connecting the connection
pipe.

When the flare nut is tightened properly by your hand, hold the body side
coupling with a separate spanner, then tighten with a torque wrench. (Fig.
15)

Fig. 15

2. Bending pipes

The pipes are snapped by your hands. Be careful not to collapse them.

Fig. 12

Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bent or stretched, the material will harden,
making it difficult to bend or stretch them any more. Do not bend or stretch
the pipes more than three times.

Indoor unit

Small pipe

Large pipe

Tighten with two wrenches.

Wrench (fixed)

Flare nut

Connection pipe

Indoor unit
pipe

Torque wrench

To prevent gas leakage,
coat the flare surface with
alkylbenzene oil (HAB).
Do not use mineral oil.

VACUUM PROCESS

 CAUTION

(1) Do not purge the air with refrigerants but use a vacuum

pump to vacuum the installation! There is no extra re-
frigerant in the outdoor unit for air purging!

(2) Use a vacuum pump for R410A exclusively. Using the

same vacuum pump for different refrigerants may dam-
age the vacuum pump or the unit.

1. VACUUM

(1) Remove the cap, and connect the gauge manifold and the vacuum

pump to the charging valve by the service hoses.

(2) Vacuum the indoor unit and the connecting pipes until the pressure

gauge indicates –0.1 MPa (–76 cmHg).

(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump

for at least 15 minutes.

(4) Disconnect the service hoses and fit the cap to the charging valve to

the specified torque.

(5) Remove the blank caps, and fully open the spindles of the 2-way and

3-way valves with a hexagon wrench (Torque : 6 to 7 N · m (60 to 70
kgf · cm).

(6) Tighten the blank caps of the 2-way valve and 3-way valve to the

specified torque.

5

- Continued on back -

 CAUTION

(1) When moving and installing the air conditioner, do not

mix gas other than the specified refrigerant (R410A)
inside the refrigerant cycle.

(2) When charging the refrigerant R410A, always use an

electronic balance for refrigerant charging (to meas-
ure the refrigerant by weight).

(3) When charging the refrigerant, take

into account the slight change in the
composition of the gas and liquid
phases, and always charge from the
liquid phase side whose composi-
tion is stable.

(4) Add refrigerant from the charging valve after the com-

pletion of the work.

(5) If the units are further apart than the maximum pipe

length, correct operation can not be guaranteed.

3. GAS LEAKAGE INSPECTION

 CAUTION

After connecting the piping, check the joints for gas leak-
age with gas leak detector.

Fig. 6

1,000 mm (39”) or more

CONNECTION PIPE REQUIREMENT

Table 2

10 cm (4”)
or more

10 cm (4”)
or more

60 cm (2’)
or more

60 cm (2’)
or more

60 cm (2’)
or more

[12000 and 14000 BTU/h models]

Air

30 cm (1’)
or more

30 cm (1’)
or more

60 cm (2’)
or more

30 cm (1’)
or more

60 cm (2’)
or more

[18000 BTU/h model]

MODEL

Diameter

Maximum length

Maximum Height
(between indoor and outdoor)

Small

Large

12000 BTU/h model

14000 and 18000

BTU/h models

6.35 mm (1/4 in.) 6.35 mm (1/4 in.)

9.52 mm (3/8 in.) 12.70 mm (1/2 in.)

20 m (66 ft)

20 m (66 ft)

8 m (26 ft)

8 m (26 ft)

 

 CAUTION

Install heat insulation around both the gas and liquid pipes.
Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Re-
verse cycle model only)
In addition, if the humidity level at the installation location
of the refrigerant piping is expected to exceed 70%, install
heat insulation around the refrigerant piping. If the ex-
pected humidity level is 70-80%, use heat insulation that
is 15 mm or thicker and if the expected humidity exceeds
80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified,
condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 20 °C).

ELECTRICAL REQUIREMENT

  Electric wire size and fuse capacity:

Table 3

  Use pipe with water-resistant heat insulation.

Always use H07RN-F or equivalent to the connection cord.

Install the circuit breaker nearby the units. (Both indoor unit and out-
door unit)

MODEL

Power supply cord
 (mm

2

)

Connection cord
(mm

2

)

Fuse capacity (A)

MAX.

MIN.

MAX.

MIN.

12000 and 14000

18000 BTU/h model

BTU/h models

3.0

3.0

2.0

2.5

2.5

2.5

1.5

1.5

15

20

Application

For mounting grille

For mounting grille

For mounting grille

For discharged air

Name and Shape

Bolt

Washer

Spring washer

Blower cover insulation

GRILLE ACCESSORIES

Q’ty

4

4

4

2

OUTDOOR UNIT ACCESSORIES

Application

For outdoor unit drain piping
work
[Heat & Cool model
(Reverse cycle) only]

Q’ty

1

2

1

Name and Shape

Drain pipe

Drain cap

18000 BTU/h model

12000 and 14000
BTU/h models

3

Air flow

Bottom

603 mm (23-23/32”)

Drain pipe mounting hole

Bottom plate

Drain pipe

343 mm  (13-1/2

”)

Drain cap

[18000 BTU/h model]

Air flow

Bottom

504 mm (21-1/4”)

Drain pipe mounting hole

Bottom plate

Drain pipe

285 mm (11-7/32

”)

Drain cap

OUTDOOR UNIT

INSTALLATION

Set the unit on a strong stand, such as one made of concrete blocks to
minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trouble.

Since the drain water flows out of the outdoor unit during heating op-
eration, install the drain pipe and connect it to an commercial 16 mm
hose. (Heat & Cool model (Reverse cycle) only)

When installing the drain pipe, plug all the holes (• hole at one place or
two places) other than the drain pipe mounting hole in the bottom of the
outdoor unit with putty so there is no water leakage. (Fig. 10) (Heat &
Cool model (Reverse cycle) only)

 CAUTION

Installation in cold regions. Do not use the accessory drain
pipe and drain cap.
(If the drain pipe and drain cap are used, the drain water in
the pipe may freeze in extremely cold weather.)

Fig. 10

[12000 and 14000 BTU/h models]

Table 4   Pipe outside diameter

Pipe outside

diameter

 6.35 mm (1/4 in.)

9.52 mm (3/8 in.)

12.70 mm (1/2 in.)

A (mm)

Conventional (R22) flare tool
Clutch type

Wing nut type

1.0 to 1.5

1.5 to 2.0

1.0 to 1.5

1.5 to 2.0

1.0 to 1.5

2.0 to 2.5

Flare tool for

R410A, clutch type

0 to 0.5
0 to 0.5
0 to 0.5

 CAUTION

Be sure to connect the large pipe after connecting the small
pipe completely.

(2) Outdoor unit side

Tighten the flare nut of the connection pipe at the outdoor unit valve
connector. The tightening method is the same as that as at the indoor
side.

Table 5  Flare nut tightening torque

Do not remove the cap from the connection pipe before connecting
the pipe.

Flare nut

6.35 mm (1/4 in.) dia.

9.52 mm (3/8 in.) dia.

12.70 mm (1/2 in.) dia.

Tightening torque

14 to 18 N · m (140 to 180 kgf · cm)

33 to 42 N · m (330 to 420 kgf · cm)

50 to 62 N · m (500 to 620 kgf · cm)

Connecting pipe

Blank cap

Hexagon wrench

3-way valve

Charging port

Cap

Service hose
with valve core

Outdoor unit

Use a 4 mm
hexagon wrench.

Fig. 16

Gauge manifold

Vacuum pump

Service hose

[12000 and 14000 BTU/h models]

 CAUTION

Use a clean gauge mani-
fold and charging hose
for R410A exclusively.

Gauge manifold

Vacuum pump

Service hose

[18000 BTU/h model]

t

 CAUTION

Use a clean gauge mani-
fold and charging hose
for R410A exclusively.

t

2. Additional charge

Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor
unit at the factory.
When the piping is longer than 7.5 m, additional charging is necessary.
For the additional amount, see the table below.

Table 7

6

INSTALLING THE  COUPLER

HEAT INSULATION

After checking for gas leaks, insulate by wrapping insulation around the
two parts (large and small) of the indoor unit coupling, using the coupler
heat insulation.

Fig. 18

 CAUTION

Must fit tightly against body without any gap.

Body

Be sure to overlap the
insulation

Coupler heat insulation

No gap

Coupler heat insulation

Table 6

Tightening torque

20 to 25 N · m (200 to 250 kgf · cm)

20 to 25 N · m (200 to 250 kgf · cm)

25 to 30 N · m (250 to 300 kgf · cm)

10 to 12 N · m (100 to 120 kgf · cm)

9.52 mm (3/8 in.)

12.70 mm (1/2 in.)

Blank cap (2-way valve)

Blank cap

(3-way valve)

Charging port cap

7.5 m
(25 ft)

None

None

12000 and 14000 BTU/h

models

g/m

(oz/ft)

10 m

(33 ft)

25 g

(0.9 oz)

50 g

(1.8 oz)

15 m

(49 ft)

75 g

(2.6 oz)

150 g

(5.3 oz)

20 m

(66 ft)

125 g

(4.4 oz)

250 g

(8.8 oz)

10 g/m

(0.35 oz/3.3 ft)

20 g/m

(0.71 oz/3.3 ft)

Additional

refrigerant

Pipe length

18000 BTU/h model

Fig. 17

Reviews: