SERVICE PARTS INFORMATION 5
Check Point 1 : Check rotation of Fan
Outdoor unit fan motor
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
SERVICE PARTS INFORMATION 4
Indoor unit fan motor
02-46
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 2 : Check resistance of Outdoor Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Outdoor fan motor and Main PCB.
Pin number
(wire color)
Terminal function
(symbol)
1 (Red)
2
4 (Black)
5 (White)
6 (Yellow)
DC voltage (Vm)
No function
3
No function
Earth terminal (GND)
Control voltage (Vcc)
Speed command (Vsp)
7 (Brown)
Feed back (FG)
Pin number
(wire color)
Terminal function
(symbol)
1 (Red)
2
4 (Black)
5 (White)
6 (Yellow)
DC voltage(Vm)
No function
3
No function
(GND)
Control voltage (Vcc)
Speed command (Vsp)
7 (Brown)
Feed back (FG)
Check Point 2 : Check resistance of Indoor unit Fan Motor
Refer to below. Circuit-test "Vm" and "GND" terminal.
(Vm: DC voltage, GND: Earth terminal)
>>If they are short-circuited (below 300 k ), replace Indoor unit fan motor and Controller PCB.
Summary of Contents for AUXG30KRLB
Page 2: ...1 CONTROL AND FUNCTIONS 2020 06 01 SR_CH04_AU006EF_01 ...
Page 4: ...8 8 High temperature and high pressure release control 04 36 CONTENTS continued ...
Page 5: ......
Page 42: ...2 TROUBLE SHOOTING CASSETTE type INVERTER ...
Page 90: ...Jun 2020 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...