10. Electrical characteristics
Model name
AOYG09KATA
AOYG12KATA
AOYG14KATA
Power
supply
Voltage
V
230 ~
Frequency
Hz
50 Hz
Max operating current *1
A
6.9
7.7
9.2
Starting current
A
4.4
5.8
6.6
Wiring
spec.
*2
Circuit breaker current
A
10
13
Power cable
mm
2
1.5
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length
m
16
21
Model name
AOYG18KATA
AOYG22KATA
Power
supply
Voltage
V
230 ~
Frequency
Hz
50 Hz
Max operating current *1
A
10.1
11.6
Starting current
A
7.9
8.8
Wiring
spec.
*2
Circuit breaker current
A
13
16
Power cable
mm
2
1.5
Connection
cable *3
Cross-sectional area
mm
2
1.5
Limited wiring length
m
21
26
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
- 76 -
10. Electrical characteristics
OUTDOOR UNIT
AOYG09-22KATA
OUTDOOR UNIT
AOYG09-22KATA
Summary of Contents for AUXG09KVLA
Page 5: ...12 1 Models AOYG09KATA AOYG12KATA AOYG14KATA AOYG18KATA and AOYG22KATA 78 CONTENTS continued ...
Page 6: ......
Page 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG09KVLA AUXG12KVLA AUXG14KVLA AUXG18KVLA AUXG22KVLA ...
Page 56: ... 50 11 3 Others 11 Optional parts CASSETTE TYPE AUXG09 22KVLA CASSETTE TYPE AUXG09 22KVLA ...
Page 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09KATA AOYG12KATA AOYG14KATA AOYG18KATA AOYG22KATA ...