Multiple outdoor unit installation
• Provide at least 250 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side.
When 3 units or more are arranged in a line, provide the space as shown in the following ex-
ample “
When an obstruction in the upper space:
”.
•
When the upper space is open:
Unit: mm
Obstacles at rear only
Obstacles at front only
200 or more
250 or more
1,000 or more
250
or
mo
re
Obstacles at front and rear
200 or more
1,000 or more
250
or
mo
re
•
When an obstruction in the upper space:
Unit: mm
Obstacles at rear and above.
1,500 or more
200 or more
250 or more
250 or more
Max. 300
1,500 or more
- 58 -
3-1. Models: AOYG09KATA, AOYG12KATA, AOYG14KATA, AOYG18KATA, and
AOYG22KATA
3. Installation space
OUTDOOR UNIT
AOYG09-22KATA
OUTDOOR UNIT
AOYG09-22KATA