- (01 - 06) -
C
A
SS
ET
TE T
YP
E
AU
G
30
-3
6LR
LE
C
A
SS
ET
TE T
YP
E
AU
G
30
-3
6LR
LE
SPECIFICATIONS
3.
Type
CASSETTE MODEL
INVERTER HEATPUMP
Model name
AU
G30LRLE
AU
G36LRLE
Power source
230V~ 50Hz
Available voltage range
198-264V~ 50Hz
Capacity
Cooling
Rated
kW
8.50
10.00
Btu/h
29000
34100
Min.-Max.
kW
2.80 - 10.00
2.80 - 11.20
Btu/h
9500 - 34100
9500 - 38200
Heating
Rated
kW
10.00
11.20
Btu/h
34100
38200
Min.-Max.
kW
2.70 - 11.20
2.70 - 12.70
Btu/h
9200 - 38200
9200 - 43300
Input power
Cooling
Rated
kW
2.65
3.12
Max.
3.88
4.22
Heating
Rated
2.77
3.02
Max.
3.88
4.56
Current
Cooling
Rated
A
11.6
13.7
Heating
12.2
13.3
EER
Cooling
kW/kW
3.21
3.21
COP
Heating
3.61
3.71
Moisture removal
l/h (pints/h)
2.5(5.3)
3.5(7.4)
Maximum operating current *
Cooling
A
17.0
18.5
Heating
17.0
20.0
Fan
Airflow
rate
Cooling
High
m
3
/h
1600
1800
Med
1400
1400
Low
1270
1270
Quiet
1150
1150
Heating
High
1600
1800
Med
1400
1400
Low
1270
1270
Quiet
1150
1150
Type × Q'ty
Turbo Fan × 1
Motor output
W
80
80
Sound pressure level
Cooling
High
dB(A)
40
43
Med
38
38
Low
36
36
Quiet
32
32
Heating
High
40
43
Med
38
38
Low
36
36
Quiet
32
32
Heat exchanger type
Dimensions (H × W × D)
mm
252 × 2030 × 26.6
252 × 2093 × 26.6
Fin pitch
1.2
Rows x Stages
2 × 12
Pipe type
Copper
Fin type
Aluminium
Dimensions
( H×W×D)
Net
mm
288×840×840
Gross
360×960×985
Weight
Net
kg
26
Gross
31
Connection pipe
Size
Liquid
mm
Ø9.52 (3/8 in.)
Gas
Ø15.88 (5/8 in.)
Method
Flare
Drain hose
Material
PVC
Size
VP25 [Ø25(I.D.), Ø32(O.D.)]
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Cassette grille
Model name
UTG-UG
A-W
Material
PS
Colour
WHITE
Approximate colour of MUNSELL N 9.25 /
Dimensions
(H × W × D)
Net
mm
50×950×950
Gross
115×1020×1000
Weight
Net
kg
5.5
Gross
8.5
Remote controller type
Wired [Wireless (option)]
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
The maximum current and the maximum input value are maximum values when operated within the operation range.
*The maximum current is the total current of indoor unit and outdoor unit.
Summary of Contents for AU*G30LRLE series
Page 2: ...1 INDOOR UNIT DTR_AU052E_02 2013 04 01 CASSETTE TYPE AU G30LRLE AU G36LRLE ...
Page 42: ...DTR_AO135E_01 2013 02 28 SINGLE TYPE AO G30LETL AO G36LETL 2 OUTDOOR UNIT ...
Page 48: ... 02 05 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL MODEL AO G36LETL ...
Page 53: ... 02 10 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL SOUND LEVEL CHECK POINT 88888 ...