CAPACITY COMPENSATION RATE FOR PIPE LENGTH
5.
AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL
: AO
G12LALL
HEATING
Pipe length (m)
5
7.5
10
15
20
25
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.943
0.916
0.896
10
-
-
1.010
0.943
0.916
0.896
7.5
-
1.000
1.010
0.943
0.916
0.896
5
1.000
1.000
1.010
0.943
0.916
0.896
0
1.000
1.000
1.010
0.943
0.916
0.896
2
Indoor unit is
lower than
outdoor unit.
-5
0.995
0.995
1.005
0.939
0.912
0.892
-7.5
-
0.993
1.002
0.936
0.909
0.890
-10
-
-
0.999
0.934
0.907
0.887
-15
-
-
-
0.925
0.898
0.878
COOLING
Pipe length (m)
5
7.5
10
15
20
25
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.903
0.894
0.867
10
-
-
0.964
0.918
0.909
0.881
7.5
-
0.988
0.968
0.922
0.912
0.885
5
0.992
0.992
0.972
0.925
0.916
0.888
0
1.000
1.000
0.980
0.933
0.923
0.895
2
Indoor unit is
lower than
outdoor unit.
-5
1.000
1.000
0.980
0.933
0.923
0.895
-7.5
-
1.000
0.980
0.933
0.923
0.895
-10
-
-
0.980
0.933
0.923
0.895
-15
-
-
-
0.933
0.923
0.895
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H