En-10
■
Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of room temp. sensor - correction temp. value
Example of correction :
When the temperature of room temp. sensor is 78 °F and the setting value is
“03” (-2 °F), the corrected temp. will be 80 °F (78 °F [-2 °F]).
The temperature correction values show the difference from the “Standard setting” (00)
(manufacturer’s recommended value).
(
♦
... Factory setting)
Function number
Setting
value
Setting description
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0 °F (0.0 °C)
02
-1 °F ( -0.5 °C)
More
Cooling
Less
Heating
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
Less
Cooling
More
Heating
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
■
Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to “Both” (01).
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(
♦
... Factory setting)
Function number
Setting
value
Setting description
35
(For cooling)
36
(For heating)
00
No correction
♦
01
No correction 0 °F (0.0 °C)
02
-1 °F ( -0.5 °C)
More
Cooling
Less
Heating
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
Less
Cooling
More
Heating
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
■
Setting record
•
Record any changes to the settings in the following table.
Function
number
Setting Description
Setting Value
95
Heat Insulation condition (building insulation)
30
Room temperature control for indoor unit sen-
sor
Cooling
31
Heating
35
Room temperature control for wired
remote controller sensor
Cooling
36
Heating
After completing the Function setting, be sure to disconnect the power and reconnect it
again.
6. TEST
RUN
■
Check items
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do
air
fl
ow direction louvers operate normally?
(4) Is the drain normal?
(5) Do not have an abnormal noise and vibration during operation?
Do not operate the air conditioner in test run for a long time.
■
Operation method
Before starting the test run, wait for 1 minute after connecting the power supply.
By the wireless remote controller
To start the test run, press [START/STOP(
)], [TEST RUN] on the remote controller
by using the tip of a ballpoint pen or other small object.
By the indoor unit
To start the test run, keep on pressing the indoor unit button for more than 10 seconds.
To end test operation, press the remote controller [START/STOP(
)].
(When the air conditioner is running by pressing [TEST RUN], the “OPERATION” Lamp
and “TIMER” Lamp will simultaneously
fl
ash slowly.)
7. FINISHING
(1) Insulate between pipes.
• Insulate suction and discharge pipes separately.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and
indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water
does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
(6) Check the drainage.
*Locally purchased
Pipe
Saddle*
Outside wall cap*
Sealer putty*
(Outdoors)
Wall
Overlap the insulation
Vinyl tape*
Wrap with cloth tape.
Cloth tape (accessory)
Drain hose
Pipe
Connection pipe
(heat insulation)
Indoor unit pipe
(heat insulation)
Bind the pipes together
so that there is no gap.
GOOD
Drain hose
Saddle
Lifted up
Wave
End in water
PROHIBITED
(7) Open the intake grille of the indoor unit. Set an air cleaning
fi
lter (accessories)
to each
fi
lter folder (accessories) and attach to the air
fi
lter. For details of how to
assemble the air
fi
lter, please refer to the operating manual.
8. CUSTOMER
GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air
fl
ow
switching, and other remote control unit operations.
(2) Air
fi
lter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.
9387603095_IM.indb 10
9387603095_IM.indb 10
2019/11/18 15:54:55
2019/11/18 15:54:55