En-4

5.4. Installing the wall hook bracket

• Remove the wall hook bracket from the indoor unit. (Remove screw).
(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically. 

If the wall hook bracket is titled, water will drip to the 

fl

 oor.

(2) Install the wall hook bracket so that it is strong enough to support the weight of the unit.

• Fasten the wall hook bracket to the wall with 5 or more screws through the holes near the 

outer edge of the bracket.

• Check that there is no rattle at the wall hook bracket.

Wall hook bracket

Tapping screw

(large)

 CAUTION

Install the wall-hook bracket both horizontally and vertically aligned. 
Misaligned installation may cause water leakage.

5.5. Forming the drain hose and pipe

[Rear piping, Right piping, Bottom piping]

• Install the indoor unit piping in the direction of the wall hole and bind the drain hose 

and pipe together with vinyl tape.

• Install the piping so that the drain hose is at the bottom.
• Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

 CAUTION

•  Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.
•  When inserting, be sure not to attach any material besides water. If any other material is 

attached, it will cause deterioration and water leakage.

•  After removing drain hose, be sure not to forget mounting drain cap.
•  Be sure to 

fi

 x the drain hose with tape to the bottom of piping.

•  Prevent drain water freezing under low temperature environment.

When installing indoor unit’s drain hose outdoors, necessary measure for frost 
protection should be taken to prevent drain water freezing.
Under low temperature environment (when outdoor temperature under 32 °F (0 °C)), 
after cooling operation is executed, water in the drain hose could be frozen. Once drain 
water is frozen, the drain hose will be blocked and water leakage may result at the 
indoor unit.

Installation method of Drain cap 

Use a hexagonal wrench 3/16 in. (4 mm) at opposite side 
to insert the drain cap, till the drain cap contacts the tip of 
drain cock.

Right piping

Bottom piping

Bind with vinyl tape

Refrigerant pipes (top)

Rear piping

Indoor unit drain hose (bottom)

No gap

Hexagonal 
wrench

Drain 

cock

Drain cap

For left outlet piping, 

cut off the piping 

outlet cutting groove 

with a hacksaw. 

Indoor unit 

drain hose

Drain cap

Remove the drain cap by pull-

ing at the projection at the end 

of the cap with pliers, etc.

Removal method of drain hose

Remove the screw at the left of drain 
hose and pull out drain hose.

Installation method of drain hose

Vertically insert the drain hose toward the 
inside, so that the drain 

fi

 xture (white) can ac-

curately align with the screw hole around the 
drain cock.
After inserting and before replacing, please 
reinstall and 

fi

 x the removed screws.

•  Please hold around the joint of the drain hose during working.
•  As the screw is inside, be sure to use screwdriver treated with magnet.

Screw

Drain 

fi

xture

Drain hose

Screw hole

Drain cock

Drain hose

Screw

Drain 

fi

xture

• For left piping and left rear piping, align the marks on the wall hook bracket and shape the 

connection pipe.

• Bend the connection piping at a bend radius of 2-3/4 in. (70 mm) or more and install no 

more than 1-6/16 in. (35 mm) from the wall.

• After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on 

the hooks at the top and bottom of the wall hook bracket.

[Installing the indoor unit]

•  Hang the indoor unit from the hooks at the top of the wall hook bracket.
•  Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate 

the bottom of the indoor unit from the wall.

Unit: in. (mm)

Indoor unit

Wall hook bracket

(Spacer)

Connection pipe small

Align the marks

Indoor unit

Connection pipe large

Top hooks

Bottom hooks

Wall hook bracket

Bend R2-3/4 
(70) with a pipe 
bender

After hooking the indoor unit to the top hook, hook the 

fi

 ttings of the indoor unit to the 2 

bottom hooks while lowering the unit and pushing it against the wall.

5.6. Flare connection (Pipe connection)

 CAUTION

 Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. Oth-

erwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to leak 

and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

5.6.1. Flaring

Use special pipe cutter and 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.

9320456016_IM.indb   4

9320456016_IM.indb   4

12/4/2014   2:20:58 PM

12/4/2014   2:20:58 PM

Summary of Contents for ASU12RLS3

Page 1: ... fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor uni...

Page 2: ...ing with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight change in the co...

Page 3: ...r volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not ...

Page 4: ...t pipes top Rear piping Indoor unit drain hose bottom No gap Hexagonal wrench Drain cock Drain cap For left outlet piping cut off the piping outlet cutting groove with a hacksaw Indoor unit drain hose Drain cap Remove the drain cap by pull ing at the projection at the end of the cap with pliers etc Removal method of drain hose Remove the screw at the left of drain hose and pull out drain hose Inst...

Page 5: ...ut correctly Tighten the flare nuts with a torque wrench using the specified tightening method Otherwise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water fro...

Page 6: ...erminal screw tightening torques Tightening torque lbf in N m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wirin...

Page 7: ...roller holder Tapping screw small remote controller mounting Remote controller 2 Push 1 Set Overlap the insulation Vinyl tape Wrap with cloth tape Cloth tape Drain hose Connection cable Pipe Drain hose Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear Pipe Connection pipe heat insulation Indoor unit pipe heat insulation Bind the pipes together so t...

Page 8: ...ng intake grille and front panel See 9 FRONT PANEL REMOVAL AND INSTALLATION and 9 1 Front panel removal 11 2 2 Removing control cover Screw 2 Control cover Control box Screw 1 Remove the screw 1 and 2 then remove the control cover 11 2 3 Installing relay control board and relay wire terminal Control unit board Connector CN2 Relay wire Notice 2 Clasps Connector CND01 Relay control board Clasp 2 Not...

Page 9: ...es to the function settings used to control the indoor unit according to the installation conditions Incorrect settings can cause the indoor unit to malfunction After the power is turned on perform the FUNCTION SETTING according to the installation conditions using the remote controller The settings may be selected between the following two Function Number or Setting Value Settings will not be cha...

Page 10: ...the FUNCTION SETTING be sure to turn off the power and turn it on again 13 2 Temperature correction NOTE When changing Function 95 perform this setting before other Room temp control settings Function 30 31 92 93 If Function 95 is not set first Room temperature control settings Function 30 31 92 93 will be reset and you must re do them again Heat Insulation condition building insulation Heat insul...

Page 11: ...r to the operating manual 1 Stop the air conditioner operation 2 Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display 3 Press the START STOP button to stop the test run 15 CUSTOMER GUIDANCE Explain the following to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjus...

Page 12: ...rip detection 9 5 Compressor rotor position detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator green TIMER i...

Reviews: