En-6

OPERATING MANUAL

Note for timer settings:

Any interruption of the power supply, such as a blackout or cutting off of a circuit breaker, makes the set internal clock incorrect.
In such a case, the TIMER indicator on the indoor unit blinks, and you need to readjust the setting.

Timer Operation

ON timer or OFF timer

You can set the ON timer or OFF timer with the following steps.

1

  Press the TIMER SETTING button to start the setting.

The WEEKLY indicator will be 

À

 ashing on the remote controller.

2

  Press the SELECT button to choose the desired mode. The mode 

will change as follows:

WEEKLY

ON/OFF

(ON)

ON/OFF

(OFF)

ON/OFF

(ON

OFF)

SLEEP

(OFF)

3

  Press the NEXT button. Continue to setting for each mode.

* To cancel timer setting during the setting process, press the 

TIMER SETTING button again.

4

  Adjust the time by pressing the SELECT button while the clock 

indicator is blinking. Each time you press the button, the time will 
change by 

5/

5 minutes. Pressing down will change the time by 

10/

10 minutes.

5

  Press the SEND button.

To redo the timer setting, perform step 1 to 5 again.
To cancel the ON/OFF timer, press the ON/OFF button while the ON/
OFF indicator is on. (Erases the indicator)

Program timer (combined use of the ON timer and the OFF timer)

You can set an integrated ON

±

OFF or OFF

±

ON timer.

Either of the timer whose con

¿

 gured starting time is closer to the 

current time works 

¿

 rst, and the order of timer operation is displayed 

as follows:

Timer

Indicator on remote controller display

ON

±

OFF timer

OFF

±

ON timer

To set the program timer, conduct the same steps 

1

~

5

 for the ON/

OFF timer. (Select ON

OFF in Step 2)

Notes:

‡

 If you change the setting value for the timer after the program timer 

is set, the counting down of the timer will be reset at that moment.

‡

 Time setting for each combination should be within a span of 24 hours.

SLEEP timer

To set the SLEEP timer, 

¿

 rst follow steps 

1

~

3

 for the ON/OFF timer.

4

  Adjust the time by pressing the SELECT button while the clock 

indicator is blinking.
Each time you press the button, the time changes as follows:

9H

00M

7H

00M

5H

00M

3H

00M

2H

00M

1H

00M

0H

30M

hours

(30 min.)

5

  Press the SEND button.

To cancel the SLEEP timer, press the SLEEP button while the SLEEP 
indicator is on. (Erases the indicator)

To help you to fall asleep comfortably and prevent e

[

cessive 

cooling in sleep, the SLEEP timer controls the temperature setting 
automatically in accordance with the set time shown as follows. The 
air conditioner completely turns off after the set time has elapsed.

Set temperature

Set time

1 hour

ƒ

C

ƒ

C

In COOL or DRY mode

WEEKLY timer

ON and OFF timer can be combined, and up to 4 reservations (program 

 ) per day and 2

 reservations per week.

Before setting the program, please set the week and time of the air 
conditioner 

¿

 rst.

If the week and time are not set, the weekly timer will not operate 
correctly at the set time.
Please refer to "remote controller preparation"  (page 2).

E

[

ample of WEEKLY timer 1

No timer settings

Program 

9:00  

OFF

Program 

11:00  

OFF

Program 

17:00  

OFF

Program 

23:00  

OFF

Monday to 

Friday

Saturday

Sunday

Program 

7:00 

ON 

26

ƒ

C

Program 

9:00 

OFF

Wake up

Leave for work

Program 

17:00 

ON 

2

ƒ

C

Program 

23:00 

OFF

Come back home

Go to sleep

ON

ON

ON

ON

E

[

ample of WEEKLY timer 2

You can specify a given temperature in the ON setting in WEEKLY 
timer.

Program 
7:00  

ON  

2

ƒ

C

Program 
9:00  

ON  

26

ƒ

C

Program 
17:00  

ON  

27

ƒ

C

Program 
23:00  

ON  

2

ƒ

C

* You can set the temperature for AUTO, COOL, and DRY modes within 
the range of 1

30

ƒ

C.

Notes:

‡

 Operations modes other than the temperature setting will be the 

same at the last time operation was stopped, so Cooling 

ĺ

 Dry 

ĺ

 

Cooling 

ĺ

 Dry type of operations cannot be automatically set.

‡

 If you set the ON timer and OFF timer on the same time, the air 

conditioner will run the ON timer. If two ON timer are set at the same 
time, the air conditioner will run in the order of the program number.

‡

 If there is a power interruption, such as due to a power outage 

during the WEEKLY timer setting or a circuit breaker cutting out, 
the internal timer of the air conditioner will be incorrect. (See page 
9 "Auto

restart".) In such a case, the main timer lamp will notify you 

of this by 

À

 ashing, so carry out matching of the time and date. (See 

page 2 "remote controller preparation".)

‡

 You cannot use the WEEKLY timer together with the other timers.

If you want to run the product on WEEKLY timer after using the ON/
OFF Timer, Program Timer, or SLEEP Timer while the WEEKLY 
timer is running, you need to activate the WEEKLY timer again.

(continued)

9333003023_OM_EN.indd   6

8/12/2013   8:53:48 AM

Summary of Contents for ASTG07CMCA

Page 1: ...be sure to keep away from re or any Àammables and consult authorized service personnel If you see lightning or hear thunder there might be a lightning strike To prevent electric shock hazard turn off the air conditioner by using the remote controller and do not touch the unit or the power plug during thunderstorm The appliance shall be stored in a room without continuously operating ignition sourc...

Page 2: ...nt of refrigerant leakage be sure to keep away from re or any Àammables and consult authorized service personnel If you see lightning or hear thunder there might be a lightning strike To prevent electric shock hazard turn off the air conditioner by using the remote controller and do not touch the unit or the power plug during thunderstorm The appliance shall be stored in a room without continuousl...

Page 3: ...tems Do not expose animals or plants to the direct airÀow Do not drink the drainage from the air conditioner Do not pull the power supply cable to disconnect the plug Do not touch the aluminum ns of heat exchanger built in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit Do not direct the airÀow at replaces or heating apparatus Do not block or cover the int...

Page 4: ...RY mode may cause condensation to form and the drops may damage your property 6 Power diffuser In conjunction with movement of the vertical airÀow direction louver the angle of the power diffuser moves as follows Vertical airÀow direction louver Power diffuser 3 7 6 5 4 2 1 3 2 1 4 In SWING operation power diffuser does not move 7 Drain hose 8 Remote controller signal receiver CAUTION For appropri...

Page 5: ...th the button operation and only shows the necessary indicators for each setting 5 POWERFUL button Activates the POWERFUL operation The unit will operate at maximum power and strong airÀow to quickly cool down the room When activated the indoor unit will emit 3 short beeps To turn off press the POWERFUL button again The indoor unit will then emit 2 short beeps POWERFUL operation is automatically t...

Page 6: ... asleep comfortably with gradual temperature control See page 6 13 ON OFF timer button Activates the ON OFF timer 14 NEXT button Used for adjusting the timer setting 15 BACK button Used for adjusting the timer setting 16 RESET button When you press the RESET button press it gently by using the tip of a ballpoint pen or other small object in correct direction as shown in this gure RESET See page 2 ...

Page 7: ...EEP indicator is on Erases the indicator To help you to fall asleep comfortably and prevent excessive cooling in sleep the SLEEP timer controls the temperature setting automatically in accordance with the set time shown as follows The air conditioner completely turns off after the set time has elapsed Set temperature Set time 1 hour 2 C 1 C In COOL or DRY mode WEEKLY timer ON and OFF timer can be ...

Page 8: ...e SELECT button to set the temperature If you want to move on to the next setting press the NEXT button return to step 4 and con gure the next setting 8 To complete the setting press the SEND button If you want to cancel the setting midway please press the TIMER SETTING button instead of pressing the SEND button Notes Ɣ When canceling the WEEKLY timer select No Timer Operation in Step 5 in the WEE...

Page 9: ...LEEP timer will be prioritized This product is designed to be compatible with Air Conditioning Demand Response program To utilize the function you need a separate arrangement with your electricity supplier Please check availability in the place of use When your electricity supplier activates one of the following 3 Demand Response DR modes the air conditioner switches over to the appropriate operat...

Page 10: ...he malfunction of the air conditioner If you encounter such a malfunction turn off the circuit breaker once Then turn it on again and resume operation by using the remote controller Temperature and Humidity Range Permissible ranges of temperature and humidity are as follows COOL DRY Indoor temperature About 18 C to 32 C Indoor humidity Below approximately 80 If the air conditioner is used continuo...

Page 11: ...shaft properly insert the shaft until it snaps Then close the intake grille b a a b b 4 Press 4 places on the intake grille to close it completely Cleaning the air lters Mind that you have a periodical cleaning of the air lters to prevent reducing the operation ef ciency of the product Using of clogged air lter with dust will lower the product performance and may cause airÀow reduction or increase...

Page 12: ...once every 3 months under normal use By setting the fan speed high the air cleaning effect increases Ion deodorization lter UTR FA16 2 Light blue 1 sheet The lter deodorizes by powerfully decomposing absorbed odors using the oxidizing and reducing effects of ions generated by the ultra ne particle ceramic To maintain the deodorizing effect clean the lter once every 3 months as follows 1 Remove the...

Page 13: ...ow speed and the airÀow is reduced In COOL mode the indoor unit fan may stop from time to time when the outdoor unit is stopped 4 When monitoring operation is performed in AUTO mode the fan rotates at very low speed Before you call for or request servicing troubleshoot a problem by performing following checks Symptom Diagnostic See page Does not operate at all Has the circuit breaker been turned o...

Page 14: ...deterioration of those items Do not e pose animals or plants to the direct airÀow Do not drink the drainage from the air conditioner Do not pull the power supply cable to disconnect the plug Do not touch the aluminum ns of heat e changer built in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit Do not direct the airÀow at replaces or heating apparatus Do no...

Page 15: ...on 4 7 during COOL or DRY mode may cause condensation to form and the drops may damage your property 6 Power diffuser In conjunction with movement of the vertical airÀow direction louver the angle of the power diffuser moves as follows Vertical airÀow direction louver Power diffuser 3 7 6 5 4 2 1 3 2 1 4 In SWING operation power diffuser does not move 7 Drain hose 8 Remote controller signal receiv...

Page 16: ...e display is linked with the button operation and only shows the necessary indicators for each setting 5 POWERFUL button Activates the POWERFUL operation The unit will operate at ma imum power and strong airÀow to quickly cool down the room When activated the indoor unit will emit 3 short beeps To turn off press the POWERFUL button again The indoor unit will then emit 2 short beeps POWERFUL operat...

Page 17: ... that helps you to fall asleep comfortably with gradual temperature control See page 6 13 ON OFF timer button Activates the ON OFF timer 14 NEXT button Used for adjusting the timer setting 15 BACK button Used for adjusting the timer setting 16 RESET button When you press the RESET button press it gently by using the tip of a ballpoint pen or other small object in correct direction as shown in this...

Page 18: ...SLEEP button while the SLEEP indicator is on Erases the indicator To help you to fall asleep comfortably and prevent e cessive cooling in sleep the SLEEP timer controls the temperature setting automatically in accordance with the set time shown as follows The air conditioner completely turns off after the set time has elapsed Set temperature Set time 1 hour 2 C 1 C In COOL or DRY mode WEEKLY timer...

Page 19: ...NEXT button 7 Press the SELECT button to set the temperature If you want to move on to the ne t setting press the NEXT button return to step 4 and con gure the ne t setting 8 To complete the setting press the SEND button If you want to cancel the setting midway please press the TIMER SETTING button instead of pressing the SEND button Notes Ɣ When canceling the WEEKLY timer select No Timer Operatio...

Page 20: ...LEEP timer page 6 the SLEEP timer will be prioritized This product is designed to be compatible with Air Conditioning Demand Response program To utilize the function you need a separate arrangement with your electricity supplier Please check availability in the place of use When your electricity supplier activates one of the following 3 Demand Response DR modes the air conditioner switches over to...

Page 21: ...transmitter may cause the malfunction of the air conditioner If you encounter such a malfunction turn off the circuit breaker once Then turn it on again and resume operation by using the remote controller Temperature and Humidity Range Permissible ranges of temperature and humidity are as follows COOL DRY Indoor temperature About 1 C to 32 C Indoor humidity Below appro imately 0 If the air conditi...

Page 22: ... panel a To latch each shaft properly insert the shaft until it snaps Then close the intake grille b a a b b 4 Press 4 places on the intake grille to close it completely Cleaning the air lters Mind that you have a periodical cleaning of the air lters to prevent reducing the operation ef ciency of the product Using of clogged air lter with dust will lower the product performance and may cause airÀo...

Page 23: ...pened Replace the lter once every 3 months under normal use By setting the fan speed high the air cleaning effect increases Ion deodorization lter UTR FA16 2 Light blue 1 sheet The lter deodorizes by powerfully decomposing absorbed odors using the o idizing and reducing effects of ions generated by the ultra ne particle ceramic To maintain the deodorizing effect clean the lter once every 3 months ...

Page 24: ...he fan rotates at very low speed and the airÀow is reduced In COOL mode the indoor unit fan may stop from time to time when the outdoor unit is stopped 4 When monitoring operation is performed in AUTO mode the fan rotates at very low speed Before you call for or request servicing troubleshoot a problem by performing following checks Symptom Diagnostic See page Does not operate at all Has the circu...