11-21 EXTERNAL CONNECT KIT
This kit allows to operate the air conditioner, such as stopping and starting, using an external
device, and output the operation status of the air conditioner.
Only operation and stop signals will be output.
•
Use the remote control to check the operation mode, temperature, and airflow.
Check the error information on the display area of the main unit.
Operation mode, temperature, and airflow cannot be set by external input. Use the remote
•
controller to set.
If the air-conditioner is activated by external input, it will operate in the settings before stop.
•
To change the settings, use the remote controller.
11-2-11 CONTROL INPUT SETTING
You can control air conditioner ON / OFF operation by external input.
•
Signal specification
z
No voltage ON/OFF continuous signal.
•
Contact capacity : DC12V 10mA
•
ON
OFF
ON
ON
OFF
OFF
OPERATION
STOP
External input signal
Remote controller signal
Indoor unit status
Installation example
z
For remote operation
•
Orange
External
input
External
output
1
3 Yellow
Indoor unit
External device
( Field supply )
Print circuit
board
For external timer operation
•
Orange
External
input
External
output
1
3 Yellow
Indoor unit
External device
( Field supply )
Print circuit
board