En-8
Flaring
21 21 11
Use special pipe cutter and flare tool exclusive for R410A.
•
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that the cuttings will not enter the pipe and remove
any burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor and outdoor
units respectively) onto the pipe and perform the flare processing with a flare tool.
Leakage of refrigerant may result if other flare nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
L
Check if [L] is flared uniformly
and is not cracked or scratched.
Pipe
A
B
Die
Pipe outside
diameter [mm (in1)]
Dimension A (mm)
Dimension B 0
- 014
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8)
13.2
12.70 (1/2)
16.6
15.88 (5/8)
19.7
When using conventional flare tools to flare R410A pipes, the dimension A should
•
be approximately 0.5mm more than indicated in the table (for flaring with R410A
flare tools) to achieve the specified flaring. Use a thickness gauge to measure the
dimension A.
Pipe outside
diameter
[mm (in1)]
Width across flats
of Flare nut
[mm]
6.35 (1/4)
17
9.52 (3/8)
22
12.70 (1/2)
26
15.88 (5/8)
29
Width across flats
Bending pipes
21 21 21
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
•
curvature of 100mm or more.
If the pipe is bent repeatedly at the same place, it will break.
•
If pipes are shaped by hand, be careful not to collapse them.
•
Do not bend the pipes at an angle of more than 90°.
•
When pipes are repeatedly bent or stretched, the material will harden, making it
•
difficult to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.
•
Pipe connection
21 21 21
CAUTION
Be sure to install the pipe against the port on the indoor unit and the outdoor unit
•
correctly. If the centering is improper, the flare nut cannot be tightened smoothly.
If the flare nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the outdoor unit pipe until immediately before
•
connecting the connection pipe.
After installing the piping, make sure that the connection pipes do not touch the
•
compressor or outer panel. If the pipes touch the compressor or outer panel, they
will vibrate and produce noise.
(1) Detach the caps and plugs from the pipes.
(2) Center the pipe against the port on the outdoor unit, and then turn the flare nut
by hand.
(3) Tighten the flare nut of the connection pipe at the outdoor unit valve connector.
(4) After tightening the flare nut by hand, use a torque wrench to fully tighten it.
3-way valve (Liquid)
3-way valve (Gas)
Connection pipe
(Liquid)
Flare nut
Connection pipe
(Gas)
Flare nut
CAUTION
Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order
•
to tighten the flare nut correctly.
Outer panel may be distorted if fastened only with a wrench. Be sure to fix the
•
elementary part with a holding wrench (spanner) and fasten with a torque wrench
(refer to below diagram). Do not apply force to the blank cap of the valve or hang a
wrench, etc., on the cap. If blank cap is broken, it may cause leakage of refrigerant.
Blank cap
Flare nut
90°
Torque wrench
Holding
wrench
Torque wrench
Flare nut
[mm (in1)]
Tightening torque
[N·m (lgf·cm)]
6.35 (1/4) dia.
16 to 18 (160 to 180)
9.52 (3/8) dia.
32 to 42 (320 to 420)
12.70 (1/2) dia.
49 to 61 (490 to 610)
15.88 (5/8) dia.
63 to 75 (630 to 750)
19.05 (3/4) dia.
90 to 110 (900 to 1100)
Handling precautions for the valves
21 21 41
Mounted part of Blank cap is sealed for protection.
•
Fasten blank cap tightly after opening valves.
•
Operating the valves
Use a hexagon wrench (size 4mm).
•
Opening (1) Insert the hexagon wrench into the valve shaft, and turn it
•
counterclockwise.
(2) Stop turning when the valve shaft can no longer be turned.
(Open position)
Closing
(1) Insert the hexagon wrench into the valve shaft, and turn it
•
clockwise.
(2) Stop turning when the valve shaft can no longer be turned.
(Closed position)
Opening direction
Hexagon wrench
Seal (blank cap
installation portion)
Liquid pipe
Gas pipe
Opening direction
ELECTRICAL WIRING
21
The precautions of electrical wiring
21 11
WARNING
Wiring connections must be performed by a qualified person in accordance with
•
specifications.
The rated supply of this product is 50Hz, 230V. Use a voltage within the range of
198-264V.
Before connecting the wires, make sure the power supply is OFF.
•
Be sure to install a breaker of the specified capacity. When selecting breaker,
•
please comply with the laws and the regulations of each country. One breaker
must be installed on the power supply of the outdoor unit. Wrong selection and
setup of the breaker will cause electric shock or fire.
Be sure to install an earth leakage breaker. Otherwise, it will cause electric shock
•
or fire.
Do not connect AC power supply to the transmission line terminal board.
•
Improper wiring can damage the entire system.
Connect the connector cord securely to the terminal.
•
Faulty installation can cause a fire.
Make sure to secure the insulation portion of the connector cable with the cord
•
clamp. A damaged insulation can cause a short circuit.
Never install a power factor improvement condenser. Instead of improving the
•
power factor, the condenser may overheat.
Before servicing the unit, turn the power supply switch OFF. Then, do not touch
•
electric parts for 10 minutes due to the risk of electric shock.
Make sure to perform grounding work. Improper grounding work can cause
•
electric shocks.