- 12 -
W
A
LL
MOU
N
TED
ASYG30, 36LMTA
3. Specifications
Type
Wall mounted
Inverter heat pump
Model name
ASYG30LMTA
ASYG36LMTA
Power supply
230 V ~ 50 Hz
Available voltage range
198—264 V
Capacity
Cooling
Rated
kW
8.00
9.40
Btu/h
27,300
32,100
Min.—Max.
kW
2.9—9.0
2.9—10.0
Btu/h
9,900—30,700
9,900—34,100
Heating
Rated
kW
8.80
10.10
Btu/h
30,000
34,500
Min.—Max.
kW
2.2—11.0
2.7—11.2
Btu/h
7,500—37,500
9,200—38,200
Input power
Cooling
Rated
kW
2.33
3.16
Min.—Max.
0.50—3.30
0.50—4.33
Heating
Rated
2.41
2.96
Min.—Max.
0.50—3.30
0.50—4.33
Fan
HIGH
W
60
60
MED
35
35
LOW
20
20
QUIET
11
11
Current
Cooling
Rated
A
10.2
13.9
Heating
10.5
13.0
EER
Cooling
kW/kW
3.43
2.97
COP
Heating
3.65
3.41
Sensible capacity
Cooling
kW
1.85
2.55
Power factor
Cooling
%
99
99
Heating
99
99
Moisture removal
L/h (pints/h)
2.7 (4.8)
3.7 (6.5)
Maximum operating current *1
Cooling
A
14.5
19.0
Heating
14.5
19.0
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,380
1,380
MED
1,130
1,130
LOW
910
910
QUIET
710
710
Heating
HIGH
1,380
1,380
MED
1,130
1,130
LOW
910
910
QUIET
710
710
Type × Q'ty
Cross flow fan × 1
Motor output
W
61
Sound pressure level *2
Cooling
HIGH
dB(A)
50
50
MED
44
44
LOW
38
38
QUIET
31
31
Heating
HIGH
49
49
MED
44
44
LOW
39
39
QUIET
33
33
Heat exchanger type
Dimensions (H × W × D)
mm
Main: 462 × 900 × 26.6
Sub1: 126 × 900 × 13.3
Sub2: 84 × 900 × 13.3
Fin pitch
1.2
Rows × Stages
Main: 2 × 22, Sub1: 1 × 6, Sub2: 1 × 4
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
Polystyrene
Color
White
Approximate color of Munsell N 9.25/
Dimensions
(H × W × D)
Net
mm
340 × 1,150 × 280
Gross
450 × 1,270 × 405
Weight
Net
kg
18
Gross
24
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas
Ø 15.88 (Ø 5/8)
Method
Flare
Drain hose
Material
PVC
Size
mm
Ø 13.8 (I.D.), Ø 15.8 to Ø 16.7 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wireless (Wired [option])
NOTES:
Specifications are based on the following conditions:
–Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
–Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
–Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: Maximum current is maximum value when operated within the operation range.
*2: Sound pressure level:
–Measured values in manufacturer’s anechoic chamber.
–Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Summary of Contents for AOYG30LMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG30LMTA ASYG36LMTA ...
Page 20: ... 16 WALL MOUNTED ASYG30 36LMTA 5 Wiring diagram ...
Page 27: ... 23 WALL MOUNTED ASYG30 36LMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 52: ... 48 WALL MOUNTED ASYG30 36LMTA ...
Page 53: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG30LMTA AOYG36LMTA ...
Page 59: ... 55 OUTDOOR UNIT AOYG30 36LMTA 3 Refrigerant circuit ...
Page 60: ... 56 OUTDOOR UNIT AOYG30 36LMTA 4 Wiring diagram ...