If you use a wireless remote control, the lamp
on the photo detector unit will output error codes
by way of blinking patterns.
If you use a wired type remote control, error
codes will appear on the remote control display.
See the lamp blinking patterns and error codes
in the table. An error display is displayed only
during running.
Indoor unit lamps
Wired
remote
control
INDOOR UNIT
and WIRED REMOTE CONTROL
E R R O R D E T E C T I O N
Description
OPERATION
(green)
TIMER
(orange)
ECONOMY
(green)
(1)
(1)
Serial communication error
(1)
(2)
Wired remote control communica
(1)
(5)
Check run unfinished
(2)
(1)
Unit number or Refrigerant circu
address setting error
[Simultaneous Multi]
(2)
(2)
Indoor unit capacity error
(2)
(3)
Combination error
(2)
(4)
Connection unit number error
•
(indoor slave unit)
[Simultaneous Multi]
Connection unit number error
•
(indoor unit or branch unit)
[Flexible Multi]
(2)
(7)
Master unit, slave unit set-up
error [Simultaneous Multi]
(3)
(2)
Indoor unit PCB model informa
(3)
(5)
Manual auto switch error
(4)
(1)
Inlet air temp. sensor error
(4)
(2)
Indoor unit Heat Ex. Middle tem
sensor error
(5)
(1)
Indoor unit fan motor error
(5)
(3)
Drain pump error
(5)
(7)
Damper error
(5)
(15)
Indoor unit error
(6)
(2)
Outdoor unit main PCB model
information error or
communication error
(6)
(3)
Inverter error
(6)
(4)
Active filter error, PFC circu
(6)
(5)
Trip terminal L error
: 0.5s on / 0.5s off
: 0.1s on / 0.1s off
( ) : Number of flashing
This is possible only on a wired remote control.
If an error occurs, the following display will be shown.
(“Er” will appear in the set room temperature display.)
Error code
EX. Self-diagnosis
2013.03.26
10
(3)
(1)
Power supply interruption error
Summary of Contents for AOYG24LALA
Page 12: ...11 10 9 4 6 1 8 7 2 3 5 PARTS INDOOR UNIT 2013 03 25 11 11 8 9 1 6 4 3 2 7 Ref 5 10 ...
Page 13: ...26 25 INDOOR UNIT 22 23 24 21 2013 03 25 12 23 24 26 21 22 25 Ref ...
Page 14: ...INDOOR UNIT 33 32 31 35 36 2013 03 25 13 31 M 33 T 34 T 32 P 35 R R P 36 R Ref 34 ...
Page 15: ...PARTS OUTDOOR UNIT 14 2013 05 27 3 11 5 1 2 7 6 9 4 10 8 ...
Page 16: ...OUTDOOR UNIT 15 33 35 28 29 34 21 30 27 2013 05 29 26 22 23 24 25 ...
Page 19: ...1302G4179 ...