2. CURRENT RELEASE CONTROL
Current release operation value / Release value
01-24
OT
Control / Release
7..0A / 6.5A
17°C
Heating operation
AOYG09KMCBN
AOYG12KMCBN
AOYG14KMCBN
OT
Control / Release
7.0A / 6.5A
17°C
5°C
OT : Outdoor temperature
OT
Control / Release
7.0A / 6.5A
9.0A / 8.5A
10.0A / 9.5A
10.0A / 9.5A
17°C
10°C
5°C
12°C
9.5A / 9..0A
9.5A / 9.0A
9.0A / 8.5A
5°C
12°C
8.0A / 7.5A
8.0A / 7.5A
8.0A / 7.5A
Compressor frequency is controlled so that the outdoor unit input current
does not exceeds current limit value that was set up with outdoor temperature.
Compressor frequency returns to the designated frequency of indoor unit
at the time when the frequency becomes lower than the release value.
Cooling, Dry operation
OT
Control / Release
4.5A / 4.0A
50°C
OT
Control / Release
4.5A / 4.0A
50°C
AOYG09KMCBN
AOYG12KMCBN
AOYG14KMCBN
OT
Control / Release
4.5A / 4.0A
4.5A / 4.0A
6.0A / 5.5A
50°C
46°C
46°C
6.0A / 5.5A
4.5A / 4.0A
46°C
4.5A / 4.0A
4.5A / 4.0A
40°C
40°C
8.5A / 8.0A
8.5A / 8.0A
40°C
12°C
12°C
6.5A / 6.0A
6.5A / 6.0A
12°C
5.5A / 5.0A
5.5A / 5.0A
8.5A / 8.0A
2°C
2°C
6.5A / 6.0A
2°C
5.5A / 5.0A