6-2. Model: AOYG12KATA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
Height difference H (m)
Indoor unit is higher than outdoor
unit *
1
15
—
—
—
0.903
10
—
—
0.964
0.918
7.5
—
0.988
0.968
0.922
5
0.992
0.992
0.972
0.925
0
1.000
1.000
0.980
0.933
Indoor unit is lower than outdoor
unit *
2
-5
1.000
1.000
0.980
0.933
-7.5
—
1.000
0.980
0.933
-10
—
—
0.980
0.933
-15
—
—
—
0.933
HEATING
Pipe length (m)
5
7.5
10
15
Height difference H (m)
Indoor unit is higher than outdoor
unit *
1
15
—
—
—
0.943
10
—
—
1.010
0.943
7.5
—
1.000
1.010
0.943
5
1.000
1.000
1.010
0.943
0
1.000
1.000
1.010
0.943
Indoor unit is lower than outdoor
unit *
2
-5
0.995
0.995
1.005
0.939
-7.5
—
0.993
1.002
0.936
-10
—
—
0.999
0.934
-15
—
—
—
0.925
6-3. Model: AOYG14KATA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
15
—
—
—
0.953
0.950
10
—
—
0.983
0.968
0.966
7.5
—
0.988
0.987
0.972
0.970
5
0.992
0.992
0.991
0.976
0.974
0
1.000
1.000
0.999
0.984
0.982
Indoor unit is lower than
outdoor unit *
2
-5
1.000
1.000
0.999
0.984
0.982
-7.5
—
1.000
0.999
0.984
0.982
-10
—
—
0.999
0.984
0.982
-15
—
—
—
0.984
0.982
HEATING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
15
—
—
—
0.918
0.891
10
—
—
0.981
0.918
0.891
7.5
—
1.000
0.981
0.918
0.891
5
1.000
1.000
0.981
0.918
0.891
0
1.000
1.000
0.981
0.918
0.891
Indoor unit is lower than
outdoor unit *
2
-5
0.995
0.995
0.976
0.914
0.886
-7.5
—
0.993
0.974
0.912
0.884
-10
—
—
0.972
0.909
0.882
-15
—
—
—
0.900
0.873
- 64 -
6-2. Model: AOYG12KATA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG09-18KATA
OUTDOOR UNIT
AOYG09-18KATA