background image

En-3

5.2. Outdoor unit wiring

(1)  Remove the outdoor unit Switch cover A, B.
(2)  Remove the outdoor unit Cord clamp and Nylon clamp.
(3)  Bend the end of the cord as shown in the 

¿

 gure.

(4)  Connect the end of the connection cord fully into the terminal block.
(5)  Fasten the sheath with a cord clamp.
(6)  Fasten the sheath with a nylon clamp.
(7)  Install the Switch cover A, B.

Cord clamp

Nylon clamp

N

L

3

2

1

1 2

3

Outdoor unit terminal block

Indoor unit terminal block

Connection cord

Earth screw

Earth screw

Power supply Cord

N

L

3

2

1

25mm

1

2mm

5mm

5mm

12mm

20mm

Cord clamp

Earth 

screw

20mm

1

2mm

5mm

5mm

12mm

20mm

Connection Cord

Power supply Cord

Connection cord wiring

Run the connection cord to the rear of the outdoor unit within the 

A

 range of the arrows 

shown in the figure.

(The Switch cover B becomes difficult to install.)

A

Connection and 
Power supply cord
Nylon clamp

Screw

HOLE

HOLE

 CAUTION

Match the terminal block numbers and connection cord colors with those of the indoor 
unit.
Erroneous wiring may cause burning of the electric parts.

Connect the connection cords 

¿

 rmly to the terminal block. Imperfect installation may 

cause a 

¿

 re.

Always fasten the outside covering of the connection cord with the cord clamp. (If the 
insulator is chafed, electric leakage may occur.)

Securely earth the power cord.

Do not use the earth screw for an external connector. Only use for interconnection 
between two units.

5.3. Connecting the piping

CONNECTION

(1)  Install the outdoor unit wall cap (supplied with the optional installation set or pro-

cured at the site) to the wall pipe.

(2)  Connect the outdoor unit and indoor unit pip-

ing.

(3)  After matching the center of the 

À

 are surface 

and tightening the nut hand tight, tighten the 
nut to the speci

¿

 ed tightening torque with a 

torque wrench. (Table 1)

FLARING

(1)  Cut the connection pipe to the necessary 

length with a pipe cutter.

(2)  Hold the pipe downward so that cuttings will 

not enter the pipe and remove the burrs.

(3)  Insert the flare nut onto the pipe and flare 

the pipe with a 

À

 aring tool.

Insert the flare nut (always use the flare nut 
a t t a c h e d  t o  t h e  i n d o o r  a n d  o u t d o o r  u n i t s 
respectively) onto the pipe and perform the 

À

 are 

processing with a 

À

 are tool.

Use the special R410A  

À

 are tool, or the conventional (for R22) 

À

 are tool.

When using the conventional 

À

 are tool, always use an allowance adjustment gauge and 

secure the A dimension shown in table 2.

BENDING PIPES

(1)  When bending the pipe, be careful not to crush it.
(2)  To prevent breaking of the pipe, avoid sharp bends.

Bend the pipe with a radius of curvature of 70mm or over.

(3)  If the copper pipe is bend the pipe or pulled to often, it will become stiff. Do not 

bend the pipes more than three times at one place.

Tighten with two wrenches.

Torque 
wrench

Wrench (

¿

 xed)

Flare nut

Indoor unit pipe

Connection 

pipe

To prevent gas leakage, coat the 

À

 are 

surface with refrigerator oil.

Table 1 

Flare nut size and tightening torque

Flare nut

Diameter (mm)

 ✕

 

Torque (N•m

)

6.35  mm dia.

17

 

✕ 

16 ~ 18

9.52  mm dia.

22

 

✕ 

32 ~ 42

Table 2 

Pipe outside diameter

Pipe outside

diameter

A (mm)

Flare tool for

R410A, clutch type

Conventional (R22) 

À

 are tool

Clutch type

Wing nut type

ø 6.35 mm (1/4")

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø 9.52 mm (3/8")

0 to 0.5

1.0 to 1.5

1.5 to 2.0

 CAUTION

Fasten a 

À

 are nut with a torque wrench as instructed in this manual. If fastened too 

tight, the 

À

 are nut may be broken after a long period of time and cause a leakage of 

refrigerant.

During installation, make sure that the refrigerant pipe is attached 

¿

 rmly before you run 

the compressor. Do not operate the compressor under the condition of refrigerant piping 
not attached properly with 2-way or 3-way valve open. This may cause abnormal pres-
sure in the refrigeration cycle that leads to breakage and even injury.

5.4. Air purge

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do not operate it during 
the following work.

 CAUTION

Refrigerant must not be discharged into atmosphere.

After connecting the piping , check the joints for gas leakage with gas leak detector. 

 (1)  Check if the piping connections are secure.
 (2)  Check that the stems of 2-way valve and 3-way valve are closed fully.
 (3)  Connect the gauge manifold charge hose to the charging port of the 3-way valve (side 

with the projection for pushing in the valve core).

 (4)  Open the low pressure side valve of the gauge manifold fully.
 (5)  Operate the vacuum pump and start pump down.
 (6)  Slowly loosen the 

À

 are nut of the 3-way valve and check if air enters, then retighten 

the 

À

 are nut.

(When the 

À

 are nut is loosened the operating sound of the vacuum pump changes 

and the reading of the compound pressure gauge goes from minus to zero.)

 (7)  Pump down the system for at least 15 minutes, then check if the compound pressure 

gauge reads -0.1 MPa (-76 cmHg, -1 bar).

 (8)  At the end of pump down, close the low pressure side gauge of the gauge manifold 

fully and stop the vacuum pump.

 (9)  Slowly loosen the valve stem of the 3-way valve. When the compound pressure 

gauge reading reaches 0.1-0.2 MPa, retighten the valve stem and disconnect the 
charge hose from the 3-way valve charging port.

Check if [L] is 

À

 ared uniformly and 

is not cracked or scratched.

Die

A

Pipe

9319205007_IM_EN.indd   3

12/29/2010 9:16:49 AM

Summary of Contents for AOYG09-12LEC

Page 1: ...h s i l g n E INSTALLATION MANUAL For authorized service personnel only INSTALLATION MANUAL 2 OUTDOOR UNIT PART NO 9319205007 ...

Page 2: ... change in the composition of the gas and liquid phases And always charge from the liquid phase where refrigerant composition is stable 2 2 Special tools for R410A Tool name Contents of change Gauge manifold Pressure is high and cannot be measured with a conven tional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended the gauge ...

Page 3: ...ht of the outdoor units and install positively so that the units will not topple or fall CAUTION Do not install where there is the danger of combustible gas leakage Do not install near heat sources In places where the outdoor temperature drops to 0 ÛC or lower the drain water may freeze and may stop up the drain or cause other outdoor unit trouble Therefore take measures so that the drain water wi...

Page 4: ...curvature of 70mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Tighten with two wrenches Torque wrench Wrench xed Flare nut Indoor unit pipe Connection pipe To prevent gas leakage coat the Àare surface with refrigerator oil Table 1 Flare nut size and tightening torque Flare nut Diameter mm Torque N m ...

Page 5: ...ash slowly OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage 6 PUMP DOWN 6 1 Pump down PUMP DOWN OPERATION FORCED COOLING OPERATION To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the cooling operation or for...

Reviews: