SU MO TU WE TH FR SA
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button simultane-
ously for 2 seconds or more to start the test run.
Unit number (usually 0)
Error code
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication E:EE is displayed, follow the following items
to perform the self-diagnosis. E:EE indicates an error has occurred.
1. REMOTE CONTROLLER DISPLAY
1) Stop the air conditioner operation.
2) Press the set temperature buttons
simultaneously for 5 sec-
onds or more to start the self-diagnosis.
Refer to the following tables for the description of each error code.
Test run display
(3) Press the set temperature buttons
simultaneously for 5 sec-
onds or more to stop the self-diagnosis.
Ex. Self-diagnosis
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor short-
circuited
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor short-
circuited
Power source connection error
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor short-circuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor short-circuited
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
02
03
04
05
06
07
08
09
0A
0b
0c
0d
0E
0F
11
12
13
14
Error code
Error contents
Communication error
(indoor unit
remote controller)
Communication error
(indoor unit
outdoor unit)
00
01
ERROR CONTENTS
When a malfunction occurs in the outdoor unit, the LEDs on the circuit
board light to indicate the error. Refer to the following table for the de-
scription of each error according to the LEDs.
When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high pressure
abnormal, the LED lamp lights continuously for 24 hours, as long as the
power is not turned off.
Quick flash continued
Quick flash continued
1 quick flash repeated
Lighting continued
2 quick flash repeated
Lighting continued
3 quick flash repeated
Lighting continued
4 quick flash repeated
Lighting continued
5 quick flash repeated
Lighting continued
Communication signal error
6 quick flash repeated
Lighting continued
7 quick flash repeated
Lighting continued
8 quick flash repeated
Lighting continued
High pressure abnormal
5 quick flash repeated
Dislighting continued
Discharge temperature
abnormal (24h)
6 quick flash repeated
Dislighting continued
Error display
LED1
LED2
Error contents
0.1 sec.
OFF
ON
0.1 sec.
OFF
ON
0.5 sec.
2 sec.
OFF
ON
OFF
ON
0.5 sec.
2 sec.
OFF
ON
OFF
ON
0.5 sec.
2 sec.
OFF
ON
OFF
ON
2. OUTDOOR UNIT
ERROR : Heat & Cool model (Reverse cycle) only
Model abnormal or
EEPROM abnormal
Power source
connection error
Discharge temperature
sensor error
Outdoor heat
exchanger temperature
sensor error
Outdoor temperature
sensor error
Indoor unit error
Discharge temperature
abnormal
High pressure
abnormal (24h)
2005.04.11
10
Summary of Contents for AOY30FNBWL
Page 3: ...Unit mm DIMENSIONS INDOOR UNIT 2005 04 11 2 ...
Page 13: ...111 56 108 110 41 150 40 67 139 138 164 2005 04 11 12 ...
Page 14: ...816 817 287 236 553 956 223 288 287 875 2005 04 11 13 ...
Page 15: ...1 34 2 3 4 5 35 6 7 Models AOY30FNBWL AOY30UNBWL 2005 04 11 14 ...
Page 16: ...13 36 12 11 10 9 8 14 13 Models AOY30FNBWL AOY30UNBWL 2005 04 11 15 ...
Page 17: ...23 38 24 39 16 15 21 37 18 17 22 37 Model AOY30FNBWL 2005 04 11 16 ...
Page 18: ...22 37 37 23 38 40 20 18 19 32 41 42 21 15 16 24 17 39 Model AOY30UNBWL 2005 04 11 17 ...
Page 19: ...27 29 26 33 31 28 Model AOY30FNBWL 2005 04 11 18 ...
Page 20: ...29 46 43 44 45 Model AOY30UNBWL 27 26 25 31 30 28 2005 04 11 19 ...
Page 24: ...0502G2755 ...