2-2. E: 11.X. Serial communication error (Serial forward transfer
error) (Indoor unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 11
Outdoor unit
"Error code table (Outdoor unit)"
Detective actuator Indoor unit
Main PCB
→hen the indoor unit cannot receive the serial signal
from outdoor unit more than 2 minutes after power on,
or the indoor unit cannot receive the serial signal more
than 15 seconds during normal operation.
Fan motor
Forecast of cause
Connection failure
External cause
Main PCB failure
Indoor unit fan motor failure
Check point 1. Reset the power and operate
Does error indication show again?
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
If there is an abnormal condition, correct it by referring to the installation manual or the
DESIGN
& TECHNICAL MANUAL
.
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 187 V (AC 208 V -10%) to AC 253 V (AC 230 V +10%) appears at
outdoor unit terminal L—N.
+
-
2-2. E: 11.↓. Serial communication error (Serial forward transfer error) (Indoor unit)
- (03-15) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...