Multiple outdoor unit installation
• Provide at least 10 in (250 mm) of space between the outdoor units if multiple units are in-
stalled.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side.
When 4 units or more are arranged in a line, provide the space as shown in the following ex-
ample “
When an obstruction in the upper space:
”.
•
When the upper space is open:
Unit: in (mm)
Obstacles at rear only
Obstacles at front only
10 (250) or more
8 (200)
or more
10 (
250
) or
mo
re
40 (1,000)
or more
Obstacles at front and rear
10 (
250
) or
mo
re
8 (200) or more
40 (1,000) or more
•
When an obstruction in the upper space:
Unit: in (mm)
Obstacles at rear and above.
10 (250)
or more
10 (250)
or more
60 (1,500)
or more
60 (1,500)
or more
8 (200) or more
Max. 11 (300)
- 67 -
3-1. Models: AOUH09LMAH1 and AOUH12LMAH1
3. Installation space
OUTDOOR UNIT
AOUG09-12LMAH1
OUTDOOR UNIT
AOUG09-12LMAH1