14) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to “External heater output” in Chapter 8-4.
Function number
Setting value
Setting description
Factory setting
66
00
-4.0 °F (-20 °C)
♦
01
-0.4 °F (-18 °C)
02
3.2 °F (-16 °C)
03
6.8 °F (-14 °C)
04
10.4 °F (-12 °C)
05
14.0°F (-10 °C)
06
17.6 °F (-8 °C)
07
21.2 °F (-6 °C)
08
24.8 °F (-4 °C)
15) Outdoor temperature zone boundary temperature B
Setting required if changing of the outdoor temperature setting for heat pump only zone is required
when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details,
refer to “External heater output” in Chapter 8-4.
Function number
Setting value
Setting description
Factory setting
67
00
42.8 °F (6 °C)
♦
01
14.0 °F (-10 °C)
02
17.6 °F (-8 °C)
03
21.2 °F (-6 °C)
04
24.8 °F (-4 °C)
05
28.4°F (-2 °C)
06
32.0 °F (0 °C)
07
35.6 °F (2 °C)
08
39.2 °F (4 °C)
09
42.8 °F (6 °C)
10
46.4 °F (8 °C)
11
50.0 °F (10 °C)
12
53.6 °F (12 °C)
13
57.2 °F (14 °C)
14
60.8 °F (16 °C)
15
64.4 °F (18 °C)
16) Standby time for auxiliary equipment operation
Sets the standby time until the auxiliary equipment operation starts during primary equipment opera-
tion.
For details, refer to Chapter 8-4.
Function number
Setting value
Setting description
Factory setting
71
00
Disable
♦
01
1 minute
02
2 minutes
•
•
•
•
•
•
98
98 minutes
99
99 minutes
- 56 -
11-1. Function settings by using remote controller
11. Function settings
WALL MOUNTED
ASUG09-12LMAS
WALL MOUNTED
ASUG09-12LMAS