background image

En-4

PREPARATION

 

 CAUTION!

Take care to prevent infants from
accidentally swallowing batteries.

When not using the Remote Control Unit
for an extended period, remove the
batteries to avoid possible leakage and
damage to the unit.

If leaking battery fluid comes in contact
with your skin, eyes, or mouth, immedi-
ately wash with copious amounts of
water, and consult your physician.

Dead batteries should be removed
immediately and disposed of properly,
either in a battery collection receptacle
or to the appropriate authority.

Do not attempt to recharge dry batteries.

Never mix new and used batteries, or
batteries of different types.
Batteries should last about one year
under normal use. If the Remote Con-
trol Unit’s operating range becomes ap-
preciably reduced, replace the batteries
and press the RESET button with the tip
of a ballpoint pen or other small object.

Turn on the Power

1

Connect the Power Supply Plug (Fig. 1 

F

) to an electri-

cal outlet; in the case of a direct line connection, turn
on the circuit breaker.

Load Batteries (AAA/R03/LR03 

×××××

 2)

1

Press and slide the battery compartment lid on the re-
verse side to open it.

Slide in the direction of the arrow while pressing the 

 mark.

2

Insert batteries.

Be sure to align the battery polarities (

) correctly.

3

Close the battery compartment lid.

Set the Current time

1

Press the CLOCK ADJUST button (Fig. 6 

X

).

Use the tip of a ball-point pen or other small object to press the button.

2

Use the TIMER SET ( 

 

 

) buttons (Fig. 6 

V

) to ad-

just the clock to the current time.

button:

Press to advance the time.

button:

Press to reverse the time.

(Each time the buttons are pressed, the time will be advanced/reversed in
one-minute increments; hold the buttons depressed to change the time
quickly in ten-minute increments.)

3

Press the CLOCK ADJUST button  (Fig. 6 

X

) again.

This completes the time setting and starts the clock.

To Use the Remote Control Unit

The Remote Control Unit must be pointed at signal receiver (Fig. 3 

4

) to operate

correctly.

Operating Range: About 23 ft.

When a signal is properly received by the air conditioner, a beeping sound will
be heard.

If no beep is heard, press the Remote Control Unit button again.

Remote Control Unit Holder

3

To remove the Remote
Control Unit (when use at
hand).

1

Mount the Holder.

2

Set the Remote Control
Unit.

Screws

Insert

Press in

Slide up

Pull out

Summary of Contents for AOU15RLQ

Page 1: ......

Page 2: ......

Page 3: ......

Page 4: ...s swings automatically up and down so that the air speeds to every nook and corner of your room REMOVABLE OPEN PANEL The indoor unit s Open Panel can be removed for easy clean ing and maintenance MILDEW RESISTANT FILTER The AIR FILTER has been treated to resist mildew growth thus allowing cleaner use and easier care SUPER QUIET OPERATION When the FAN CONTROL button is used to select QUIET the unit...

Page 5: ... Outdoor Unit G Intake Port H Outlet Port I Pipe Unit J Drain port bottom NAME OF PARTS Refer to the folded out page on the cover Fig 6 Remote Control Unit K Signal Transmitter L MASTER CONTROL button M FAN CONTROL button N START STOP button O AIR CLEAN button P COIL DRY button Q SET button R SET TEMP button S SLEEP button T SWING button U TIMER MODE button V TIMER SET buttons W TEST RUN button Th...

Page 6: ...slide the battery compartment lid on the re verse side to open it Slide in the direction of the arrow while pressing the mark 2 Insert batteries Be sure to align the battery polarities correctly 3 Close the battery compartment lid Set the Current time 1 Press the CLOCK ADJUST button Fig 6 X Use the tip of a ball point pen or other small object to press the button 2 Use the TIMER SET buttons Fig 6 ...

Page 7: ...ress the FAN CONTROL button Fig 6 M Each time the button is pressed the fan speed changes in the following order AUTO HIGH MED LOW QUIET About three seconds later the entire display will reappear When set to AUTO Heating Fan operates so as to optimally circulate warmed air However the fan will operate at very low speed when the temperature of the air issued from the indoor unit is low Cooling As t...

Page 8: ...ll operate at very low fan speed for about 3 to 5 minutes after which it will switch to the selected fan setting This period of time is provided to allow the indoor unit to warm up before begin full operation When the room temperature is very low frost may form on the outside unit and its performance may be reduced In order to remove such frost the unit will automatically enter the defrost cycle f...

Page 9: ...he operation install the intake filter and then use the START STOP button to restart the operation Use the FAN CONTROL button to change the fan speed Refer to page 5 The plasma filter unit operates most effectively at the highest fan speed The AIR CLEAN Indicator Lamp green will flash to inform you that the periodic cleaning of the plasma filter unit is required Refer to page 13 14 AIR CLEANING OP...

Page 10: ...onds later the entire display will reappear About the Program timer The program timer allows you to integrate OFF timer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operatio...

Page 11: ... Timer Operation Press the START STOP button About the SLEEP Timer To prevent excessive warming or cooling during sleep the SLEEP timer function automatically modifies the thermostat setting in accordance with the set time setting When the set time has elapsed the air conditioner completely stops During Cooling Dry operation When the SLEEP timer is set the thermostat setting is auto matically rais...

Page 12: ...utton Horizontal right left airflow direction is adjusted manually by moving the Air Flow Direction Louvers Whenever making horizontal airflow adjustments start air conditioner operation and be sure that the vertical air direction louvers are stopped Vertical Air Direction Adjustment Press the SET button Fig 6 Q Each time the button is pressed the air direction range will change as follows 1 2 3 4...

Page 13: ...or Lamp orange Fig 3 8 and the COIL DRY Display Fig 7 c will light Then it will disappear after 30 minutes To cancel COIL DRY Operation Press the START STOP button Fig 6 N during COIL DRY Operation The COIL DRY Indicator Lamp orange Fig 3 8 and the COIL DRY Display Fig 7 c will go out Then the operation stops About COIL DRY Operation Press the COIL DRY button again during COIL DRY Operation COIL D...

Page 14: ...close the Intake Grille 1 Align the sides of the air filter with the panel and push in fully making sure the two lower tabs are returned properly to their holes in the panel 2 Close the Intake Grille For purposes of example the illustration shows the unit without Intake Grille installed Dust can be cleaned from the air filter either with a vacuum cleaner or by washing the filter in a solution of m...

Page 15: ...to 113 F for 10 to 15 minutes If the plasma filter unit is extremely dirty extremely dilute a mild synthetic laun dry detergent low alkalinity or isotope detergent to 15 times the standard concentration and allow the plasma filter unit to soak in it 2 Gently move up and down and to the right and left A soft sponge can also be used to wipe the surface 3 Rinse with clean water 4 Shake the plasma fil...

Page 16: ...nts the two ends of its lower side as well as two center points of the lower side as shown in the figure to close it If after cleaning the dust collection unit the operation indicator lamp and the timer indicator lamp flash during Air Cleaning please ensure that the unit is not damp and that the intake grille is properly closed If after having checked that the unit is fully dry and that the intake...

Page 17: ...aned once every six months Please only install filters that are licensed by our company Regarding storage and care of the filter please avoid exposing it to high temperatures and high humidity Also use it as soon as possible after opening its packaging Hook Filter case Filter Case Hook Hook Hook Click When removing the filter please follow these steps backwards How to install or remove the Air cle...

Page 18: ... operation is started fan speed is temporarily very low to allow internal parts to warm up During Heating operation if the room temperature rises above the thermostat setting the outdoor unit will stop and the indoor unit will operate at very low fan speed If you wish to warm the room further set the thermostat for a higher setting During Heating operation the unit will temporarily stop opera tion...

Page 19: ...ing performance is being produced we recommend you use this air conditioner in conjunction with another kind of heating appliance Heat pump air conditioners heat your entire room by recirculating air throughout the room with the result that some time may be required after first starting the air con ditioner until the room is heated Microcomputer controlled Automatic Defrosting When using the Heati...

Page 20: ...listed above the heat exchanger may freeze leading to water leakage and other damage Do not use this unit for any purposes other than the Cooling Dehumidifying and air circulation of rooms in ordinary dwellings If the unit is used for long periods under high humidity conditions condensation may form on the surface of the indoor unit and drip onto the floor or other objects underneath About 80 or m...

Reviews: