- (02 - 01) -
O
U
TD
O
O
R U
N
IT
A
O
TG5
4L
C
TL
O
U
TD
O
O
R U
N
IT
A
O
TG5
4L
C
TL
FEATURE
1.
FEATURES
Energy saving technology (ALL DC)
z
DC twin rotary compressor
C
om
pr
es
so
r
ef
fic
ie
nc
y
High
High
Compressor capacity
DC Twin Rotary compressor
DC twin rotary compressor
Efficiency in all load regions is good.
Especially good performance from low to
medium at normal operation.
High efficiency
compressor motor
Optimized refrigerant
flow design
Highly accurate parts
DC fan motor
Miniaturized, low noise,
high efficiency, multi-stage
DC fan motor is mounted.
Peak cut operation
z
Peak cut mode
(Optional parts: UTY-XWZXZ3)
Suppresses maximum capacity and performs energy-saving operation and can prevent breaker
tripping.
This function performs operation by setting a peak current value and reducing the power
consumption.
* Performance drops by reducing the power consumption preferentially.
Level 1 ... Performs operation which suppresses the power consumption to almost 0% by
stopping the compressor.
Level 2 ... Performs operation which suppresses the power consumption to 50% of the rated
power consumption value.
Level 3 ... Performs operation which suppresses the power consumption to 75% of the rated
power consumption value.
Level 4 ... Performs operation which suppresses the power consumption to the rated power
consumption value (100%).
W
Capacity
Time
Setting level
Peak cut
Control
device
Signal input
High install ability long piping correspondence
z
Pre-charge
length
30m
Max pipe
length
75
m
Max height
difference
30
m
Long piping provides an outdoor unit and indoor
unit layout margin.
Summary of Contents for AOTG54LCTL
Page 1: ...DESIGN TECHNICAL MANUAL INDOOR OUTDOOR AOTG54LCTL ARTG54LHTC AIR CONDITIONER Duct type ...
Page 2: ...1 INDOOR UNIT DTR_AR056E_05 2016 04 27 DUCT TYPE ARTG54LHTC ...
Page 14: ... 01 11 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC DIMENSIONS 444 MODEL ARTG54LH Unit mm ...
Page 16: ... 01 13 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC WIRING DIAGRAMS 555 MODEL ARTG54LH ...
Page 41: ...SINGLE TYPE AOTG54LCTL 2 OUTDOOR UNIT DTR_AO114E_04 2016 04 27 ...
Page 49: ... 02 07 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL REFRIGERANT CIRCUIT 555 MODEL AOTG54LC ...
Page 50: ... 02 08 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL WIRING DIAGRAMS 666 MODEL AOTG54LC ...