- (01 - 15) -
D
U
C
T T
YP
E
A
R
TG
54
LH
TC
D
U
C
T T
YP
E
A
R
TG
54
LH
TC
HEATING CAPACITY
6-2.
This table is created using the rated capacity.
MODEL
: ARTG54LH
shows rated capacity
The data is based on the following conditions. Pipe length: 7.5m, Height difference: 0m
AFR: Air Flow Rate (
m
3
/min)
TC : Total Capacity (kW)
IP : Input Power (kW)
AFR
59.2
Indoor temperature
°CDB
16
18
20
22
24
Outdoor temperature
°CDB
°CWB
TC
IP
TC
IP
TC
IP
TC
IP
TC
IP
-15
-16
12.79
4.91
12.48
5.01
12.18
5.11
11.88
5.21
11.57
5.31
-10
-11
14.22
4.91
13.88
5.01
13.54
5.11
13.20
5.21
12.86
5.31
-5
-7
15.76
4.92
15.39
5.02
15.01
5.12
14.63
5.22
14.26
5.32
0
-2
16.98
4.91
16.57
5.01
16.17
5.11
15.77
5.21
15.36
5.31
5
3
18.62
4.89
18.17
4.99
17.73
5.09
17.29
5.19
16.84
5.29
7
6
16.80
4.20
16.40
4.28
16.00
4.37
15.60
4.46
15.20
4.54
10
8
18.44
3.92
18.00
4.00
17.56
4.08
17.12
4.16
16.68
4.25
15
10
19.80
3.89
19.33
3.97
18.86
4.05
18.39
4.13
17.92
4.19
20
15
19.23
3.82
18.77
3.90
18.31
3.98
17.85
4.06
17.40
4.12
24
18
19.91
3.75
19.43
3.83
18.96
3.91
18.48
3.99
18.01
4.05
Summary of Contents for AOTG54LCTL
Page 1: ...DESIGN TECHNICAL MANUAL INDOOR OUTDOOR AOTG54LCTL ARTG54LHTC AIR CONDITIONER Duct type ...
Page 2: ...1 INDOOR UNIT DTR_AR056E_05 2016 04 27 DUCT TYPE ARTG54LHTC ...
Page 14: ... 01 11 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC DIMENSIONS 444 MODEL ARTG54LH Unit mm ...
Page 16: ... 01 13 DUCT TYPE ARTG54LHTC DUCT TYPE ARTG54LHTC WIRING DIAGRAMS 555 MODEL ARTG54LH ...
Page 41: ...SINGLE TYPE AOTG54LCTL 2 OUTDOOR UNIT DTR_AO114E_04 2016 04 27 ...
Page 49: ... 02 07 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL REFRIGERANT CIRCUIT 555 MODEL AOTG54LC ...
Page 50: ... 02 08 OUTDOOR UNIT AOTG54LCTL OUTDOOR UNIT AOTG54LCTL WIRING DIAGRAMS 666 MODEL AOTG54LC ...