2005.12.06
1
SPECIFICATIONS
TYPE
COOLING
COOLING & HEATING
INDOOR UNIT
ARG45FUAN, ARY45FUAN
ARG45UUAN, ARY45UUAN
OUTDOOR UNIT
AOG45FMAXT, AOY45FMAXT
AOG45UMAXT, AOY45UMAXT
COOLING CAPACITY
(kW)
12.7
12.7
HEATING CAPACITY
(kW)
-------
14.3
POWER SOURCE
(V)
400
FREQUENCY
(Hz)
50
RUNNING
CURRENT
COOLING
7.70
7.70
(A)
HEATING
-------
7.70
INPUT WATTS
(kW)
COOLING
4.38
4.38
HEATING
-------
4.39
E.E.R.
(kW /kW)
COOLING
2.90
2.90
HEATING
-------
3.26
STARTING CURRENT
(A)
67
MOISTURE REMOVAL
( /hr)
510
TYPE
Hermetic type, 2 pole, Single phase,
Induction motor, Rotary
DISCRIMINATION
BN52YEAMT
REFRIGERANT
R410A
(g)
3,400
3,400
DISCRIMINATION
MFA-45PTAT
HIGH
1,280
INDOOR
MED
1,200
FAN SPEED
LOW
1,100
(r.p.m.)
DISCRIMINATION
MFB-30PTT
OUTDOOR
780
AIR FLOW
INDOOR
2,450
(m
3
/ h)
OUTDOOR
6,100
DIMENSIONS
INDOOR
270 x 1,135 x 700
H x W x D (mm) OUTDOOR
1,165 x 900 x 330
WEIGHT
INDOOR
52 / 45
GROSS / NET (kg) OUTDOOR
116 / 109
120 / 113
MAX PIPE LENGTH / HEIGHT
(m)
50 / 30
REMOTE CONTROLLER TYPE
WIRED
ELECTRICAL DATA
COMPRESSOR
Note : The above list shows values at the external static pressure of
98Pa (10mm Ag), setting the fan speed high notch.
Note : The above list shows values at the external static pressure of
98Pa (10mm Ag), setting the fan speed high notch.
Summary of Contents for AOG45FMAXT
Page 7: ...CIRCUIT DIAGRAM Models ARG45FUAN ARY45FUAN Models AOG45FMAXT AOY45FMAXT 2005 12 06 6 ...
Page 16: ...3 2 5 31 1 6 4 3 15 Models AOG45FMAXT AOG45UMAXT AOY45FMAXT AOY45UMAXT 2005 12 05 ...
Page 17: ...15 16 14 13 7 8 9 10 11 12 16 Models AOG45FMAXT AOG45UMAXT AOY45FMAXT AOY45UMAXT 2005 12 05 ...
Page 18: ...38 18 15 17 39 16 20 23 25 17 Models AOG45FMAXT AOY45FMAXT 2005 12 05 ...
Page 19: ...21 20 19 18 17 16 15 25 24 22 23 29 18 Models AOG45UMAXT AOY45UMAXT 2005 12 05 ...
Page 20: ...37 A 36 35 34 34 28 19 Models AOG45FMAXT AOY45FMAXT 2005 12 05 ...
Page 21: ...28 26 27 35 34 34 20 Models AOG45UMAXT AOY45UMAXT 2005 12 05 ...
Page 25: ...0504J2845 ...