NOTES ON INSTALLING CENTRAL DRAIN PAN
Make sure to design and install drain pan to cover the all drain hole on base completely.
●
The gap between drain pan and base should be less than 2mm.
●
Be careful of the foot place during the working or design process.
●
If the foundation or foot place makes working difficult, the metal fittings should be used as
●
shown below.
Keep in mind that a drain pan not having the recommended outside dimensions can cause a
●
water leakage or cannot be installed.
Gaps other than the drain holes cause a water leakage. Completely close all the gaps in the
●
bottom and sides by welding.
No gap
Drain pan
No gap
10.8
60.7
10.8
60.7
Central drain pan
Front View
The central drain pan shall have
the width of this value or more.
795 or more
672
38
59
38
Central
drain pan
Left-side View
Base
The central drain pan shall have
the height of this value or more.
620 or more
16 or less
Foot place
46 or less
Metal fittings
Use metal fittings if necessary.
(Unit : mm)