10. SAFETY DEVICES
AO S09LD
AO S12LD
AO S18LD
Current fuse
(NEAR THE TERMINAL)
Fan motor protection
Thermal protection program
OFF : 100
+15
-10
°C
ON : 95
+15
-10
°C
Compressor protection
Thermal protection program
(DISCHARGE TEMP.)
OFF : 110°C
ON : After 7 minutes
Model
20A 250V
15A 250V
3.15A 250V
OFF : 135
+5
-5
°C
ON : 95
+15
-15
°C
Protection form
Circuit protection
Current fuse
(MAIN PRINTED CIRCUIT BOARD)