( Fig. 1 : Limit of maximum speed based on outdoor temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation speed of the compressor.
* If the room temperature is
2°C
higher than a set temperature, the compressor operation
speed will attain to maximum performance.
Minimum
speed
Maximum
speed
Maximum
speed
ASYA09LEC
18rps
62rps
64rps
ASYA12LEC
18rps
80rps
96rps
When outdoor
temperature drops
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi
Me
Lo
Quiet
A zone
64rps
50rps
42rps
30rps
B zone
64rps
50rps
42rps
30rps
C zone
64rps
50rps
42rps
30rps
09LEC
D zone
42rps
35rps
30rps
23rps
A zone
96rps
61rps
51rps
33rps
B zone
96rps
61rps
51rps
33rps
C zone
96rps
61rps
51rps
33rps
12LEC
D zone
57rps
42rps
36rps
27rps
( Table 1 : Compressor speed range )
When the compressor operates for 30 minutes continuously at over the maximum speed ,
the maximum speed is changed from Maximum speed to Maximum speed .
01-01
* When the room temperature is between
+2°C
to
-2.5°C
of the setting temperature,
the compressor speed is controlled within the range shown in Table1.
However, the maximum speed is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
* If the room temperature is
2.5°C
lower than a set temperature, the compressor will be
stopped.
10°C
E zone
F zone
0°C
12°C
2°C
When outdoor
temperature rises
F zone
E zone
F zone
E zone
52rps
45rps
40rps
29rps
52rps
45rps
40rps
29rps
57rps
42rps
36rps
27rps
57rps
42rps
36rps
27rps